Permit Application Status

PRCOM20130151


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20130151
Building Permit - Commercial
Certificate of Occupancy
RAINTREE VILLAGE SHOPPING CENTER LLC
CHANGE OF TENANT
BAR RENOVATION
02/04/2013
03/04/2013
08/11/2013
05/31/2013
Locations
Contacts
BAKER BROTHERS CONTRACTORS INC, Address:611 E MANOR RD, Phone:(816) 461-6629  
INTEGRITY PLUMBING SERVICES LLC, Address:405 SW Nelson Dr., Phone:(816) 803-9032  
SBC ARCHITECTURAL SERVICES, Address:3009 ELMIRA CT, Phone:(816) 797-7225  
RAINTREE VILLAGE SHOPPING CENTER LLC, Address:3215 NE CARNEGIE DR STE 400  
PARKER'S ELECTRIC INC, Address:P O BOX 4110, Phone:(816) 252-1182  
MCGRATH HEATING & COOLING LLC, Address:250 S GEOSPACE DR, Phone:(816) 257-7377  
Reviews
Review Type Outcome Est. Completion Date Completed
Building Plan Review Approved with Conditions 03/08/2013 03/01/2013
Mike Weisenborn
Bldg - Accessibility - Toilet and bathing facilities
Resolved
03/01/2013

2006 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible. Action required - The private toilet does not meet this requirement. Make needed corrections.
Plumb - Indirect Waste General
Corrective Action Required
03/01/2013

2006 IPC Section 801.2 - Protection. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that discharge to the drainage system, shall be provided with protection against backflow, flooding fouling, contamination and stoppage of the drain. Action required - The ice machine drain and the 4 compartment sink shall be protected by an indirect waste. This will be verified on inspection.
Screening - Rooftop equipment
Corrective Action Required
03/01/2013

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required - The rooftop condensing unit shall be installed so that it no part of it is higher than the building parapet. This will be verified on inspection.
Misc
Corrective Action Required
03/01/2013

Specifications on the beer cooler condensing unit have not been provided. Action required - Provide specifications so that we can determine if additional structural information is required.
Health Dept Review
Resolved
03/01/2013

For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required -I have emailed Chris to make sure that they are ok with us issuing the permit.
Health Dept Inspection
Corrective Action Required
03/01/2013

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required - This comment is for information purposes.
Fire Plan Review Approved with Conditions 03/08/2013 03/01/2013
Mike Weisenborn
Misc
Corrective Action Required
03/01/2013

1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Repost occupant load at the entrance, verified at inspection
Address numbers required
Corrective Action Required
03/01/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing over new entry door and all other exterior doors are to match. verified at inspection
Construction documents - Fire protection systems
Corrective Action Required
03/01/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. If required provide plans for modifications to the sprinkler system for approval
Construction documents for fire alarm systems
Corrective Action Required
03/01/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. If required provide alarm plans for any modifications to the alarm system for approval
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
03/01/2013

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Sprinkler system is to have a current certification at time of final inspection, for information only
Misc
Corrective Action Required
03/01/2013

Provide dry pendant(s) in the cooler for sprinkler coverage. Verified at inspection
Licensed Contractors Approved 02/14/2013 02/13/2013
Mike Weisenborn
License contractors
Resolved
02/13/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the name of the licensed electrical contractor. This information is required for permit approval.
Building Plan Review Rejected 02/14/2013 02/12/2013
Mike Weisenborn
Bldg - Accessibility - Toilet and bathing facilities
Corrective Action Required
02/12/2013

2006 IBC 1109.2 - Toilet and bathing facilities. Toilet rooms and bathing facilities shall be accessible. Where a floor level is not required to be connected by an accessible route, the only toilet rooms or bathing facilities provided within the facility shall not be located on the inaccessible floor. At least one of each type of fixture, element, control or dispenser in each accessible toilet room and bathing facility shall be accessible. Action required - The private toilet does not meet this requirement. Make needed corrections.
Plumb - Indirect Waste General
Corrective Action Required
02/12/2013

2006 IPC Section 801.2 - Protection. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that discharge to the drainage system, shall be provided with protection against backflow, flooding fouling, contamination and stoppage of the drain. Action required - The ice machine drain and the 4 compartment sink shall be protected by an indirect waste. This will be verified on inspection.
Screening - Rooftop equipment
Corrective Action Required
02/12/2013

Planning and Development - Commercial businesses located along existing public streets shall be subject to the following design standards: a. buildings shall be designed with four (4) sided architecture, the same level of finish on all sides (no "back"); b. rooftop or ground-level mechanical equipment shall be totally screened from view by using either parapet walls at the same height of the mechanical units for rooftop mounts or by providing screening for ground mounted units acceptable to the Director; c. Wherever possible, parking areas and pedestrian walks shall connect internally to parking areas and pedestrian walks of existing adjoining businesses. Provisions shall be make for future connections to adjoining property not yet developed or redeveloped. Action required - The rooftop condensing unit shall be installed so that it no part of it is higher than the building parapet. This will be verified on inspection.
Misc
Corrective Action Required
02/12/2013

Specifications on the beer cooler condensing unit have not been provided. Action required - Provide specifications so that we can determine if additional structural information is required.
Health Dept Review
Corrective Action Required
02/12/2013

For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action Required -I have emailed Chris to make sure that they are ok with us issuing the permit.
Health Dept Inspection
Corrective Action Required
02/12/2013

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required - This comment is for information purposes.
Fire Plan Review Approved with Conditions 02/14/2013 02/06/2013
Brian Austerman
Misc
Corrective Action Required
02/06/2013

1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Repost occupant load at the entrance, verified at inspection
Address numbers required
Corrective Action Required
02/06/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing over new entry door and all other exterior doors are to match. verified at inspection
Construction documents - Fire protection systems
Corrective Action Required
02/06/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. If required provide plans for modifications to the sprinkler system for approval
Construction documents for fire alarm systems
Corrective Action Required
02/06/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. If required provide alarm plans for any modifications to the alarm system for approval
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
02/06/2013

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Sprinkler system is to have a current certification at time of final inspection, for information only
Misc
Corrective Action Required
02/06/2013

Provide dry pendant(s) in the cooler for sprinkler coverage. Verified at inspection
Fire Plan Review Approved with Conditions 02/14/2013 02/06/2013
Brian Austerman
Misc
Corrective Action Required
02/06/2013

1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Repost occupant load at the entrance, verified at inspection
Address numbers required
Corrective Action Required
02/06/2013

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing over new entry door and all other exterior doors are to match. verified at inspection
Construction documents - Fire protection systems
Corrective Action Required
02/06/2013

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. If required provide plans for modifications to the sprinkler system for approval
Construction documents for fire alarm systems
Corrective Action Required
02/06/2013

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. If required provide alarm plans for any modifications to the alarm system for approval
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
02/06/2013

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Sprinkler system is to have a current certification at time of final inspection, for information only
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $261.44 $261.44 Paid 03/04/2013
$261.44
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 3/7/2013 3/7/2013 at 12:00 AM 03/07/2013
Underslab Electrical Inspection - Commercial Passed 03/07/2013
In-wall Inspection Passed 03/14/2013
All Rough Inspection - Commercial Passed 3/12/2013 3/12/2013 at 12:00 AM 03/14/2013
Misc
Corrective Action Required
03/12/2013
OK TO ONE SIDE
Occupancy Inspection - Codes Commercial Failed 4/19/2013 4/19/2013 at 12:00 AM 04/19/2013
Misc
Corrective Action Required
04/19/2013
*POST OCCUPANT LOAD, POST ACCESSABLE SIGNAGE AT BATHROOMS. *INSTALL GRAB BARS IN REAR RESTROOM. *INSTALL VERTICAL GRAB BAR IN TWO MAIN RESTROOMS *RECEPTACLE AT REAR OF THE BAR SHOULD BE GFCI PROTECTED *RE-LABEL SERVICE PANEL ACCORDING TO ACTUAL WIRING. *COMPLETE KITCHEN EQUIPMENT AND OBTAIIN HEALTH DEPARTMENT APPROVAL.
Occupancy Inspection - Fire Temporary C of O 4/19/2013 at 12:00 AM 04/19/2013
Misc
Corrective Action Required
04/19/2013
-post occupant loads in bar / dining area and patio area -need fire extinguisher in cabinet located by the bar, rated 2A-10BC minimum - proper nozzel placement under hood once appl. are set under the hood - check all of the exit and emergency lighting for battery operation
Occupancy Inspection - Codes Commercial Full C of O 5/29/2013 05/31/2013
Misc
Resolved
05/31/2013
*POST OCCUPANT LOAD, POST ACCESSABLE SIGNAGE AT BATHROOMS. *INSTALL GRAB BARS IN REAR RESTROOM. *INSTALL VERTICAL GRAB BAR IN TWO MAIN RESTROOMS *RECEPTACLE AT REAR OF THE BAR SHOULD BE GFCI PROTECTED *RE-LABEL SERVICE PANEL ACCORDING TO ACTUAL WIRING. *COMPLETE KITCHEN EQUIPMENT AND OBTAIIN HEALTH DEPARTMENT APPROVAL.
Occupancy Inspection - Fire Passed 5/31/2013 at 12:00 AM 05/31/2013
Misc
Corrective Action Required
05/29/2013
-post occupant loads in bar / dining area and patio area -need fire extinguisher in cabinet located by the bar, rated 2A-10BC minimum - proper nozzel placement under hood once appl. are set under the hood - check all of the exit and emergency lighting for battery operation
Documents & Images
Date Uploaded File Type Document Name
02/12/2013 Letter Plan Review Conditions
03/01/2013 Letter Plan Review Conditions
03/04/2013 Letter Building Permit
03/07/2013 Letter Inspection Summary
03/12/2013 Letter Inspection Summary
03/14/2013 Letter Inspection Summary
04/19/2013 Letter Inspection Summary
04/19/2013 Letter Fire Loss Reduction Form
05/31/2013 Letter Field Certificate of Occupancy
05/31/2013 Letter Fire Loss Reduction Form
06/03/2013 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
08/22/2013 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home