Permit Application Status

PRCOM20122456


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20122456
Building Permit - Commercial
Certificate of Occupancy
JOHN CALVIN MANOR INC
ALTERATION COMMERCIAL
INTERIOR REMODEL
11/05/2012
12/09/2013
04/22/2013
08/07/2014
Locations
Contacts
4SIGHT GROUP LLC, Address:7920 WARD PKWY, Phone:(816) 802-8400  
JOHN CALVIN MANOR INC, Address:310 NW MURRAY  
4SIGHT GROUP LLC, Address:7920 WARD PKWY, Phone:(816) 802-8400  
PROSPERITY ELECTRIC LLC, Address:1601 E 18TH ST #205, Phone:(816) 318-6050  
LMG CONSTRUCTION, Address:3011 ROANOKE RD, Phone:(816) 474-0333  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 03/28/2014 03/25/2014
Brian Austerman
Misc
Corrective Action Required
03/25/2014

See alarm plan review for PRCOM 20122453
Building Plan Review Approved 10/22/2012 12/09/2013
Mike Weisenborn
Business License
Resolved
10/25/2012

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Provide the name of the licensed general contractor. A minimum of a Class B license will be required.
License contractors
Resolved
12/09/2013

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - I don't see where Allan's Electric or KC Plumbing have a current business license with the City of Lee's Summit. Current licenses will be required prior to permit issuance.
Misc
Resolved
12/09/2013

I have spoken with the building inspector for this project and he has requested that we issue separate permits for each building in the project. This will aid in inspection requests and project tracking. Action required - Please provide a separate project value for each building.
Licensed Contractors Approved 12/31/2013 12/09/2013
Mike Weisenborn
Corrective Action Required
03/25/2014

Internal Plan Review (Res) Rejected 10/22/2012 10/24/2012
Mike Weisenborn
True
Fire Plan Review Approved with Conditions 10/22/2012 10/24/2012
Jim Eden
Address numbers required
Corrective Action Required
10/24/2012

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Maintain addressing on the buildings and numbering of the apartments on the interior doors and exterior doors of apartments on grade. Verified at inspection.
Construction documents for fire alarm systems
Corrective Action Required
10/24/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide plans and specifications for ugrades and alaterations to the alarm system.
Misc
Corrective Action Required
10/24/2012

1411.2 Maintenance. Required means of egress shall be maintained during construction and demolition, remodeling or alterations and additions to any building.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $554.72 $554.72 Paid 12/09/2013
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
All Rough Inspection - Commercial Failed 3/28/2014 3/28/2014 at 12:00 AM 03/28/2014
Misc
Corrective Action Required
03/28/2014
BUILDING 4: EXAMPLE ISSUES POINTED OUT TO G.C. AT UNITS 400 & 402
All Rough Inspection - Commercial Partial 3/31/2014 3/31/2014 at 12:00 AM 03/31/2014
Misc
Partial Correction
03/31/2014
BUILDING 4: OK TO COVER WALL & CEILING FRAMING AND CONCEALED SYSTEMS AT: UNITS 400-407 EXCEPT AT SHOWERS AND THROUGH-WALL HVAC UNITS;
All Rough Inspection - Commercial Partial 4/7/2014 4/7/2014 at 12:00 AM 04/07/2014
Misc
Partial Correction
03/31/2014
BUILDING 4: OK TO COVER WALL & CEILING FRAMING AND CONCEALED SYSTEMS AT: UNITS 400-407; WIRING AT ALL ELECTRICAL BOXES TO BE APPROVED BEFORE DEVICES ARE INSTALLED.
All Rough Inspection - Commercial Partial 4/9/2014 4/9/2014 at 12:00 AM 04/09/2014
Misc
Partial Correction
04/07/2014
BUILDING 4: OK TO COVER WALL & CEILING FRAMING AND CONCEALED SYSTEMS AT: UNITS 400-407; 408-415 AFTER SOME EXISTING BOXES ARE FULLY SECURED TO STUDS; WIRING AT ALL ELECTRICAL BOXES TO BE APPROVED BEFORE DEVICES ARE INSTALLED. ENSURE ALL METALLIC BOXES ARE BONDED AND EQUIPMENT GROUNDING CONDUCTORS ARE CONNECTED WITH WIRE NUTS OR CRIMP CONNECTORS.
Rough Electrical Inspection - Commercial Partial 4/11/2014 at 12:00 AM 04/11/2014
Misc
Partial Correction
04/11/2014
EQUIPMENT GROUND CONTINUITY AND GROUNDING OF METALLIC BOXES APPROVED FROM 400 THRU 407;
All Rough Inspection - Commercial Partial 4/16/2014 4/16/2014 at 12:00 AM 04/16/2014
Misc
Partial Correction
04/09/2014
BUILDING 4: OK TO COVER WALL & CEILING FRAMING AND CONCEALED SYSTEMS AT: UNITS 400-415; WIRING AT ALL ELECTRICAL BOXES TO BE APPROVED BEFORE DEVICES ARE INSTALLED. ENSURE ALL METALLIC BOXES ARE BONDED AND EQUIPMENT GROUNDING CONDUCTORS ARE CONNECTED WITH WIRE NUTS OR CRIMP CONNECTORS.
All Rough Inspection - Commercial Partial 4/17/2014 4/17/2014 at 12:00 AM 04/17/2014
Misc
Partial Correction
04/16/2014
BUILDING 4: OK TO COVER WALL & CEILING FRAMING AND CONCEALED SYSTEMS AT: UNITS 400-415; WIRING AT ALL ELECTRICAL BOXES TO BE APPROVED BEFORE DEVICES ARE INSTALLED. ENSURE ALL METALLIC BOXES ARE BONDED AND EQUIPMENT GROUNDING CONDUCTORS ARE CONNECTED WITH WIRE NUTS OR CRIMP CONNECTORS.
Partial Correction
04/17/2014
*UNITS 416-419, IN WALL AT KITCHEN AREA AND BATHROOMS APPROVED TO COVER
Rough Electrical Inspection - Commercial Passed 4/30/2014 at 12:00 AM 04/30/2014
Misc
Resolved
04/30/2014
EQUIPMENT GROUND CONTINUITY AND GROUNDING OF METALLIC BOXES APPROVED FROM 400 THRU 407;
Alarm Test Partial 5/14/2014 at 12:00 AM 05/14/2014
Occupancy Inspection - Codes Commercial Failed 5/14/2014 5/14/2014 at 12:00 AM 05/14/2014
Misc
Corrective Action Required
05/14/2014
CORRIDOR NOT READY FOR FINAL INSPECTION.
Misc
Corrective Action Required
05/14/2014
EXHAUST AT BATHROOMS TO BE TESTED.
Misc
Corrective Action Required
05/14/2014
Sec. 7-1408.1. Hinges. Hinges for exterior swinging doors shall comply with the following: A. At least two (2) wood screws, three (3) inches in length, penetrating at least one inch into wall structure shall be used. Solid wood fillers or shims shall be used to eliminate any space between the wall structure and door frame behind each hinge. Exception: Hinges within a door frame installed directly adjacent to a sidelight. B. Hinges for out-swinging doors shall be equipped with mechanical interlock to preclude the removal of the door from the exterior.
Misc
Corrective Action Required
05/14/2014
404: - ANTI-TIP PROVISION AT RANGE INOP - DISPOSAL RECEPT NOT TIGHT TO BOX
Misc
Corrective Action Required
05/14/2014
408: - BA RECEPT NOT HOT FOR TEST - RECEPT @ LR S WALL NOT GROUNDED
Misc
Corrective Action Required
05/14/2014
409: BA RECEPT NOT HOT
Misc
Corrective Action Required
05/14/2014
405: DISPOSAL RECEPT NOT TIGHT TO BOX
Misc
Corrective Action Required
05/14/2014
403: - "SOFT" RECEPT AT CLOSET - LIGHT AT COURTYARD DOOR INOP
Misc
Corrective Action Required
05/14/2014
401: DISPOSAL RECEPT NOT SOLID TO BOX
Misc
Corrective Action Required
05/14/2014
NORTH ATTIC: - CLOSE ALL HOLES/GAPS IN N DRAFT STOP - HVAC DUCT N OF N DRAFT STOP DAMAGED. CHECK FOR AIR FLOW OBSTUCTION
Misc
Corrective Action Required
05/14/2014
SUFFICIENCY OF ATTIC INSULATION VS. R-38 TO BE DETERMINED.
Misc
Corrective Action Required
05/14/2014
IDENTIFY AND LABEL ALL ELECTRICAL EQUIPMENT AND LABEL CIRCUITS. NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS NOR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Corrective Action Required
05/14/2014
METTALIC ELECTRICAL FEEDER CONDUIT IN CONTACT WITH EARTH AT CRAWL SPACE: PROVIDE ENGINEER LETTER REGARDING SERVICABILITY OF CONDUIT AT RUSTED LOCATIONS.
Occupancy Inspection - Codes Commercial Temporary C of O 5/16/2014 5/16/2014 at 12:00 AM 05/16/2014
Misc
Corrective Action Required
05/14/2014
CORRIDOR NOT READY FOR FINAL INSPECTION.
Misc
Resolved
05/16/2014
EXHAUST AT BATHROOMS TO BE TESTED.
Misc
Corrective Action Required
05/14/2014
Sec. 7-1408.1. Hinges. Hinges for exterior swinging doors shall comply with the following: A. At least two (2) wood screws, three (3) inches in length, penetrating at least one inch into wall structure shall be used. Solid wood fillers or shims shall be used to eliminate any space between the wall structure and door frame behind each hinge. Exception: Hinges within a door frame installed directly adjacent to a sidelight. B. Hinges for out-swinging doors shall be equipped with mechanical interlock to preclude the removal of the door from the exterior.
Misc
Resolved
05/16/2014
404: - ANTI-TIP PROVISION AT RANGE INOP - DISPOSAL RECEPT NOT TIGHT TO BOX
Misc
Resolved
05/16/2014
408: - BA RECEPT NOT HOT FOR TEST - RECEPT @ LR S WALL NOT GROUNDED
Misc
Resolved
05/16/2014
409: BA RECEPT NOT HOT
Misc
Resolved
05/16/2014
405: DISPOSAL RECEPT NOT TIGHT TO BOX
Misc
Resolved
05/16/2014
403: - "SOFT" RECEPT AT CLOSET - LIGHT AT COURTYARD DOOR INOP
Misc
Resolved
05/16/2014
401: DISPOSAL RECEPT NOT SOLID TO BOX
Misc
Resolved
05/16/2014
NORTH ATTIC: - CLOSE ALL HOLES/GAPS IN N DRAFT STOP - HVAC DUCT N OF N DRAFT STOP DAMAGED. CHECK FOR AIR FLOW OBSTUCTION
Misc
Resolved
05/16/2014
SUFFICIENCY OF ATTIC INSULATION VS. R-38 TO BE DETERMINED.
Misc
Resolved
05/16/2014
IDENTIFY AND LABEL ALL ELECTRICAL EQUIPMENT AND LABEL CIRCUITS. NEC 408.4: LABELING OF ELECTRICAL CIRCUIT POSITIONS AT PANEL(S): EACH BREAKER POSITION MUST BE LABELED. MUST BE LEGIBLE, SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS NOR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE".
Misc
Resolved
05/16/2014
METTALIC ELECTRICAL FEEDER CONDUIT IN CONTACT WITH EARTH AT CRAWL SPACE: PROVIDE ENGINEER LETTER REGARDING SERVICABILITY OF CONDUIT AT RUSTED LOCATIONS.
Occupancy Inspection - Fire Temporary C of O 5/16/2014 5/16/2014 at 12:00 AM 05/16/2014
Miscellaneous Inspection Partial 5/22/2014 at 12:00 AM 05/22/2014
Miscellaneous Inspection Passed 5/23/2014 at 12:00 AM 05/23/2014
Occupancy Inspection - Codes Commercial Temporary C of O 5/29/2014 5/29/2014 at 12:00 AM 05/29/2014
Misc
Corrective Action Required
05/16/2014
INSTALL ADDRESS ON UNITS PER FIRE DEPT. INSTRUCTION.
Misc
Resolved
05/29/2014
Sec. 7-1408.1. Hinges. Hinges for exterior swinging doors shall comply with the following: A. At least two (2) wood screws, three (3) inches in length, penetrating at least one inch into wall structure shall be used. Solid wood fillers or shims shall be used to eliminate any space between the wall structure and door frame behind each hinge. Exception: Hinges within a door frame installed directly adjacent to a sidelight. B. Hinges for out-swinging doors shall be equipped with mechanical interlock to preclude the removal of the door from the exterior.
Alarm Test Passed 5/29/2014 at 12:00 AM 05/29/2014
Occupancy Inspection - Fire Temporary C of O 5/29/2014 5/29/2014 at 12:00 AM 05/29/2014
Misc
Corrective Action Required
05/29/2014
- address the building on all four sides (16110 - need permanent addressing of apartments on the exterior and in the corridor. - remove all dust covers from the smoke detectors
All Rough Inspection - Commercial Passed 6/5/2014 at 12:00 AM 06/05/2014
Misc
Resolved
06/05/2014
BUILDING 4: OK TO COVER WALL & CEILING FRAMING AND CONCEALED SYSTEMS AT: UNITS 400-415; WIRING AT ALL ELECTRICAL BOXES TO BE APPROVED BEFORE DEVICES ARE INSTALLED. ENSURE ALL METALLIC BOXES ARE BONDED AND EQUIPMENT GROUNDING CONDUCTORS ARE CONNECTED WITH WIRE NUTS OR CRIMP CONNECTORS.|*UNITS 416-419, IN WALL AT KITCHEN AREA AND BATHROOMS APPROVED TO COVER
Occupancy Inspection - Codes Commercial Temporary C of O 6/5/2014 at 12:00 AM 06/05/2014
Misc
Corrective Action Required
05/29/2014
INSTALL ADDRESS ON UNITS PER FIRE DEPT. INSTRUCTION.
Occupancy Inspection - Codes Commercial Temporary C of O 6/18/2014 at 12:00 AM 06/18/2014
Misc
Corrective Action Required
06/05/2014
INSTALL ADDRESS ON UNITS PER FIRE DEPT. INSTRUCTION.
Occupancy Inspection - Codes Commercial Temporary C of O 7/8/2014 at 12:00 AM 07/08/2014
Misc
Partial Correction
07/08/2014
INSTALL ADDRESS ON UNITS PER FIRE DEPT. INSTRUCTION. PER 7/8/14 E-MAIL MESSAGE SIGNS ARE EXPECTED BY 7/18/14.
All Rough Inspection - Commercial Passed 7/21/2014 at 12:00 AM 07/21/2014
Occupancy Inspection - Codes Commercial Temporary C of O 7/24/2014 at 12:00 AM 07/24/2014
Misc
Partial Correction
07/08/2014
INSTALL ADDRESS ON UNITS PER FIRE DEPT. REQUIREMENT.
Occupancy Inspection - Fire Passed 8/7/2014 at 12:00 AM 08/07/2014
Misc
Corrective Action Required
08/07/2014
- address the building on all four sides (16110 - need permanent addressing of apartments on the exterior and in the corridor. - remove all dust covers from the smoke detectors
Occupancy Inspection - Codes Commercial Full C of O 8/7/2014 8/7/2014 at 12:00 AM 08/07/2014
Misc
Resolved
08/07/2014
INSTALL ADDRESS ON UNITS PER FIRE DEPT. REQUIREMENT.
Documents & Images
Date Uploaded File Type Document Name
05/02/2013 PRCOM20122246prext.pdf
12/09/2013 Letter Codes Plan Review Conditions
12/09/2013 Letter Codes Building Permit
12/18/2013 Letter Fire Building Plan Review
03/25/2014 Letter Fire (Alarm) Plan Review Notice
03/31/2014 Letter Inspection Summary
04/07/2014 Letter Inspection Summary
04/09/2014 Letter Inspection Summary
04/11/2014 Letter Inspection Summary
04/17/2014 Letter Application Expired Notice
04/17/2014 Letter Inspection Summary
04/30/2014 Letter Inspection Summary
05/14/2014 Letter Inspection Summary
05/16/2014 Letter Codes Temporary Certificate of Occupancy
05/23/2014 Letter DOC052314-033.pdf
05/29/2014 Letter Codes Temporary Certificate of Occupancy
06/05/2014 Letter Codes Temporary Certificate of Occupancy
06/18/2014 Letter Codes Temporary Certificate of Occupancy
07/08/2014 Letter Codes Temporary Certificate of Occupancy
07/21/2014 Letter Inspection Summary
07/24/2014 Letter Codes Temporary Certificate of Occupancy
08/06/2014 DOC080614
08/07/2014 Letter Field Certificate of Occupancy
08/08/2014 Letter Codes Final Certificate of Occupancy
08/18/2014 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home