Permit Application Status

PRCOM20122007


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20122007
Building Permit - Commercial
Certificate of Occupancy
CBL LEES SUMMIT EAST LLC
CHANGE OF TENANT
TENANT FINISH FOR MEXICAN RESTAURANT
09/05/2012
09/18/2012
10/13/2014
11/05/2012
Locations
Contacts
CROSSLAND CONSTRUCTION COMPANY INC, Address:PO BOX 45, Phone:(620) 429-1414  
TEMP-CON LLC, Address:15670 S KEELER ST, Phone:(913) 768-4888  
PALMER ELECTRIC CO, Address:6600 ROYAL ST, BLDG B, Phone:(816) 479-2587  
ERISMAN PLUMBING & DITCHING, Address:PO BOX 492, Phone:(660) 747-5528  
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 10/12/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
10/12/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received October 4, 2012.
Installation acceptance testing
Corrective Action Required
10/12/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm and flow tests.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
10/12/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing system shall have documentation of current annual inspection.
Alarm Plan Review Released for Construction 10/02/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
10/02/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received October 1, 2012.
Installation acceptance testing
Corrective Action Required
10/02/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule alarm test. The test shall be completed prior to regular business hours and shall be coordinated with the sprinkler and hood contractors.
Internal Plan Review (Res) Approved 09/17/2012 09/13/2012
Mike Weisenborn
True
Building Plan Review Approved 09/17/2012 09/13/2012
Mike Weisenborn
Health Dept Review
Resolved
09/13/2012

For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required - Provide documentation of plan review approval. Mike Weisenborn 09/13/2012 8:43 AM - Received
Health Dept Inspection
Corrective Action Required
09/12/2012

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required - This comment is for information purposes.
License Tax Codes Approved 09/17/2012 09/13/2012
Mike Weisenborn
Fire Plan Review Approved with Conditions 09/17/2012 09/10/2012
Brian Austerman
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
09/10/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action Required: Have a current certification on the existing hood prior to the final
Portable fire extinguishers - general
Corrective Action Required
09/10/2012

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action Required: Provide a minimum size of 2A10B:C extinguishers, verified at inspection
Construction documents - Fire protection systems
Corrective Action Required
09/10/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: if any alterations to the sprinkler system are made submit chop drawings for approval
Construction documents for fire alarm systems
Corrective Action Required
09/10/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: If any alterations to the alarm system are made submit shop drawings for approval
Zoning Review Approved 09/17/2012 09/06/2012
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $1,021.25 $1,021.25 Paid 09/18/2012
8331507-Sewer Connection Fee $150.00 $150.00 Paid 09/18/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 9/19/2012 9/19/2012 at 12:00 AM 09/19/2012
Underslab Electrical Inspection - Commercial Passed 9/19/2012 at 12:00 AM 09/19/2012
In-wall Inspection Failed 10/8/2012 (8:00 to 5:00) 10/8/2012 at 12:00 AM 10/08/2012
Misc
Corrective Action Required
10/08/2012
SLIP TRACK NOT CONSTRUCTED PER DRAWINGS. SEE 14/A4.0
Misc
Corrective Action Required
10/08/2012
TENSION STUDS NOT SUPPORTED NOR BRACED PER DRAWINGS. SEE 2/A2.0
Misc
Corrective Action Required
10/08/2012
SUPPORT CANOPIES PER DRAWINGS. SEE SHEET S1.0
Misc
Corrective Action Required
10/08/2012
SUPPORT VERTICAL PEX WATER TUBING AT 4' INTERVALS PER IPC 308.5
Misc
Corrective Action Required
10/08/2012
IPC 305.8; IRC P2603 PROTECTION FROM PENETRATION OF PVC / ABS / PEX / COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING TO RECEIVE SCREWED OR NAILED COVERING: PROTECT PIPE WITH MINIMUM 1/16" THICK HARDENED STEEL SHIELD PLATES. SHIELD PLATES SHALL COVER THE AREA OF THE MEMBER WHERE THE PIPE PENETRATES. SHIELD PLATES SHALL EXTEND A MINIMUM OF 2" ABOVE BASE PLATES / TRACKS AND BELOW TOP PLATES / TRACKS. CHECK ALL.
In-wall Inspection Partial 10/9/2012 at 12:00 AM 10/09/2012
Misc
Resolved
10/09/2012
SLIP TRACK NOT CONSTRUCTED PER DRAWINGS. SEE 14/A4.0
Misc
Corrective Action Required
10/09/2012
TENSION STUDS NOT SUPPORTED NOR BRACED PER DRAWINGS. SEE 2/A2.0
Misc
Resolved
10/09/2012
SUPPORT CANOPIES PER DRAWINGS. SEE SHEET S1.0
Misc
Resolved
10/09/2012
SUPPORT VERTICAL PEX WATER TUBING AT 4' INTERVALS PER IPC 308.5
Misc
Corrective Action Required
10/09/2012
IPC 305.8: TWO BOCA PLATES YET TO BE INSTALLED AT BASE TRACK
Misc
Partial Correction
10/09/2012
AFTER TWO ADDITIONAL BOCA PLATES ARE IN PLACE OK TO COVER WALLS AND CANOPIES WHEN READY -- EXCEPT DO NOT COVER HANGING STRUCTURE ABOVE SERVING LINE PRIOR TO APPROVAL..
In-wall Inspection Passed 10/11/2012 10/11/2012 at 12:00 AM 10/11/2012
Misc
Resolved
10/11/2012
TENSION STUDS NOT SUPPORTED NOR BRACED PER DRAWINGS. SEE 2/A2.0
Misc
Resolved
10/11/2012
IPC 305.8: TWO BOCA PLATES YET TO BE INSTALLED AT BASE TRACK
Misc
Resolved
10/11/2012
AFTER TWO ADDITIONAL BOCA PLATES ARE IN PLACE OK TO COVER WALLS AND CANOPIES WHEN READY -- EXCEPT DO NOT COVER HANGING STRUCTURE ABOVE SERVING LINE PRIOR TO APPROVAL..
In-wall Inspection Partial 10/23/2012 at 12:00 AM 10/23/2012
Misc
Partial Correction
10/23/2012
OK TO PROCEED WITH PLUMBING ADDITIONS SHOWN ON REVISED DRAWING P1.1 USING 1-1/2" PVC DRAIN PIPING IN LIEU OF 2" WHEREVER ALLOWED BY IPC.
In-wall Inspection Passed 10/24/2012 at 12:00 AM 10/24/2012
Alarm Test Passed 10/1/2012 at 9:00 AM 11/01/2012
Above Ceiling Inspection Passed 11/1/2012 11/1/2012 at 12:00 AM 11/01/2012
Occupancy Inspection - Codes Commercial Partial 11/2/2012 11/2/2012 at 12:00 AM 11/02/2012
Misc
Corrective Action Required
11/02/2012
RESOLVE FIRE DEPT ISSUES
Misc
Corrective Action Required
11/02/2012
ROOFTOP INSPECTION
Misc
Corrective Action Required
11/02/2012
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600-3: IF INTERNALLY LIGHTED MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN.
Misc
Corrective Action Required
11/02/2012
PER ICC/ANSI A117.1 SECTION 604.6: WATER CLOSET FLUSH VALVE HANDLE MUST BE AT FREE SIDE OF TANK
Misc
Corrective Action Required
11/02/2012
IPC 608: BACKFLOW PREVENTION DEVICE REQUIRED AT POTABLE WATER-FED EQUIPMENT. AT CARBONATED BEVERAGE DISPENSING EQUIPMENT USE ASSE 1022 LISTED DEVICE.
Misc
Corrective Action Required
11/02/2012
APPLY ESCHUTCHEONS AT ALL EXPOSED PLUMBING PENETRATIONS OF WALL AND PARTITIONS.
Misc
Corrective Action Required
11/02/2012
RESTORE/REPLACE DETERIORATED SUITE LABELS AT RTU's
Misc
Corrective Action Required
11/02/2012
OK TO SET UP FOR BUSINESS. NO PUBLIC OR CUSTOMERS PRIOR TO APPROVAL.
Occupancy Inspection - Fire Temporary C of O 11/2/2012 at 12:00 AM 11/02/2012
Misc
Corrective Action Required
11/02/2012
-grease pan needed on left side of hhod, right side pan needs to be installed - install sprinkler head eschution rings as needed throughout - two sidewall spklr heads need to be altered according to plans. -OK TO SET UP AND TRAIN, HOOD NOT TO BE USED UNTIL GREASE PANS ARE INSTALLED - DUCT DETECTION TO BE TESTED AFTER INSTALLATION IS COMPLETED
Occupancy Inspection - Codes Commercial Full C of O 11/5/2012 11/5/2012 at 12:00 AM 11/05/2012
Misc
Resolved
11/05/2012
RESOLVE FIRE DEPT ISSUES
Misc
Resolved
11/05/2012
ROOFTOP INSPECTION
Misc
Resolved
11/05/2012
INSTALLATION OF LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. PER NEC 600-3: IF INTERNALLY LIGHTED MUST BE UL SHOP-LABELED PER 600.3. INSTALL NO NON-LISTED SIGN.
Misc
Resolved
11/05/2012
PER ICC/ANSI A117.1 SECTION 604.6: WATER CLOSET FLUSH VALVE HANDLE MUST BE AT FREE SIDE OF TANK
Misc
Resolved
11/05/2012
IPC 608: BACKFLOW PREVENTION DEVICE REQUIRED AT POTABLE WATER-FED EQUIPMENT. AT CARBONATED BEVERAGE DISPENSING EQUIPMENT USE ASSE 1022 LISTED DEVICE.
Misc
Resolved
11/05/2012
APPLY ESCHUTCHEONS AT ALL EXPOSED PLUMBING PENETRATIONS OF WALL AND PARTITIONS.
Misc
Resolved
11/05/2012
RESTORE/REPLACE DETERIORATED SUITE LABELS AT RTU's
Misc
Resolved
11/05/2012
OK TO SET UP FOR BUSINESS. NO PUBLIC OR CUSTOMERS PRIOR TO APPROVAL.
Occupancy Inspection - Fire Passed 11/5/2012 at 12:00 AM 11/05/2012
Misc
Corrective Action Required
11/02/2012
-grease pan needed on left side of hhod, right side pan needs to be installed - install sprinkler head eschution rings as needed throughout - two sidewall spklr heads need to be altered according to plans. -OK TO SET UP AND TRAIN, HOOD NOT TO BE USED UNTIL GREASE PANS ARE INSTALLED - DUCT DETECTION TO BE TESTED AFTER INSTALLATION IS COMPLETED
Misc
Corrective Action Required
11/05/2012
ALL PENDING ISSUES HAVE BEEN RESOLVED
Documents & Images
Date Uploaded File Type Document Name
09/13/2012 Letter Plan Review Conditions
09/18/2012 Letter Building Permit
09/19/2012 Letter Inspection Summary
10/08/2012 Letter Inspection Summary
10/09/2012 Letter Inspection Summary
10/11/2012 Letter Inspection Summary
10/11/2012 Letter Inspection Summary
10/12/2012 Letter Fire (Sprinkler) Plan Review
10/23/2012 Letter Inspection Summary
10/24/2012 Letter Inspection Summary
11/01/2012 Letter Inspection Summary
11/02/2012 Letter Inspection Summary
11/02/2012 Letter Fire Loss Reduction Form
11/05/2012 Letter Field Certificate of Occupancy
11/05/2012 Letter Fire Loss Reduction Form
11/06/2012 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home