Summary
PRCOM20121140
Building Permit - Commercial
Certificate of Occupancy
CML MO HAF LLC
CHANGE OF TENANT
CHANGE OF USE
05/23/2012
05/23/2012
06/07/2012
Locations
Contacts
GLASS SHACK OF HAWAII, Address:315 SE DOUGLAS ST, Phone:(816) 805-6835  
CML MO HAF LLC, Address:1010 WALNUT STE 500  
TEAM HOLIMAN LLC, Address:2348 SW WATERFALL DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 06/05/2012 05/24/2012
Brian Austerman
Misc
Corrective Action Required
05/24/2012

Emergency lighting, exits and life safety must be maintained, verified at inspection
Internal Plan Review (Res) Approved 05/23/2012
Codes Admin
True
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $30.00 $30.00 Paid 05/23/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Occupancy Inspection - Fire Temporary C of O 5/30/2012 at 12:00 AM 05/30/2012
Misc
Corrective Action Required
05/30/2012
(1) replace all painted sprinkler heads (6) (2) remove extention cords going through walls and ceilings, reroute to outlets or install additional outlets to needed areas
Occupancy Inspection - Codes Commercial Temporary C of O 5/30/2012 5/30/2012 at 12:00 AM 05/30/2012
Misc
Corrective Action Required
05/30/2012
SUPPLY AIR BRANCH DUCT NOT SUPPORTED.
Misc
Corrective Action Required
05/30/2012
NEWLY-INSTALLED ELECTRICAL BOXES AT BACK ROOM: 1) RESTORE DRYWALL TO <= 1/8" FROM BOX; 2) CLOSE BOXES
Misc
Corrective Action Required
05/30/2012
MC CABLE TO LIGHT ABOVE REAR DOOR NOT SECURED WITHIN 12" OF BOX & PANEL
Misc
Corrective Action Required
05/30/2012
PREPARE & AFFIX PANEL SCHEDULE IN SERVICE PANEL
Misc
Corrective Action Required
05/30/2012
RESTROOM MUST BE SUBSTANTIALLY ANSI COMPLIANT: 1) RAMP FLOOR TRANSITION AT DOOR OPENING 2) ELIMINATE OBSTRUCTION TO WHEELCHAIR ACCESS TO SINK + PAD PIPING 3) INSTALL ANSI-COMPLIANT GRAB BARS AT WATER CLOSET
Misc
Corrective Action Required
05/30/2012
WATER HEATER REQUIRES EXPANSION TANK
Misc
Corrective Action Required
05/30/2012
DRAIN LINE FOR WATER HEATER TPR DISCHARGE HAS REVERSE SLOPE
Occupancy Inspection - Fire Passed 6/5/2012 at 12:00 AM 06/05/2012
Occupancy Inspection - Codes Commercial Full C of O 6/7/2012 at 12:00 AM 06/07/2012
Misc
Resolved
06/07/2012
SUPPLY AIR BRANCH DUCT NOT SUPPORTED.
Misc
Resolved
06/07/2012
NEWLY-INSTALLED ELECTRICAL BOXES AT BACK ROOM: 1) RESTORE DRYWALL TO <= 1/8" FROM BOX; 2) CLOSE BOXES
Misc
Resolved
06/07/2012
MC CABLE TO LIGHT ABOVE REAR DOOR NOT SECURED WITHIN 12" OF BOX & PANEL
Misc
Resolved
06/07/2012
PREPARE & AFFIX PANEL SCHEDULE IN SERVICE PANEL
Misc
Resolved
06/07/2012
RESTROOM MUST BE SUBSTANTIALLY ANSI COMPLIANT: 1) RAMP FLOOR TRANSITION AT DOOR OPENING 2) ELIMINATE OBSTRUCTION TO WHEELCHAIR ACCESS TO SINK + PAD PIPING 3) INSTALL ANSI-COMPLIANT GRAB BARS AT WATER CLOSET
Misc
Resolved
06/07/2012
WATER HEATER REQUIRES EXPANSION TANK
Misc
Resolved
06/07/2012
DRAIN LINE FOR WATER HEATER TPR DISCHARGE HAS REVERSE SLOPE
Documents & Images
Date Uploaded File Type Document Name
05/23/2012 Letter Building Permit
05/24/2012 Drawing 20120524104008344.pdf
05/30/2012 Letter Fire Loss Reduction Form
05/30/2012 Letter Temporary Certificate of Occupancy
06/05/2012 Letter Fire Loss Reduction Form
06/05/2012 Letter Fire Loss Reduction Form
06/07/2012 Letter Field Certificate of Occupancy
06/11/2012 Letter Final Certificate of Occupancy
06/26/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home