Permit Application Status

PRCOM20120415


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20120415
Building Permit - Commercial
Certificate of Occupancy
SCHLOTZHAUER ROBERT A
ALTERATION COMMERCIAL
VEHICLE SPRAY BOOTH INSTALLATION
03/09/2012
03/22/2012
09/16/2012
08/09/2012
Locations
Contacts
APPLE ELECTRIC INTEGRATED SOLUTIONS INC, Address:PO BOX 998, Phone:(913) 837-5285  
CENTRAL PLUMBING HTG & A/C INC, Address:P O BOX 218, Phone:(816) 942-6355  
CRAIG A LUEBBERT, ARCHITECT, LLC, Address:396 SW WINTERGARDEN DR, Phone:(816) 536-3472  
SCHLOTZHAUER ROBERT A, Address:2451 NE DOUGLAS  
AIRTECH ENGINEERING, Address:9265 FLINT ST, Phone:(913) 888-5900  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 03/27/2012 03/22/2012
Codes Admin
True
Building Plan Review Approved 03/21/2012 03/22/2012
Mike Weisenborn
License contractors
Resolved
03/22/2012

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the mechanical, electrical and plumbing contractors licensed in the City of Lee's Summit.
Internal Plan Review (Res) Rejected 03/21/2012 03/20/2012
Mike Weisenborn
License Tax Codes Approved 03/21/2012 03/19/2012
Mike Weisenborn
Fire Plan Review Approved 03/21/2012 03/13/2012
Brian Austerman
Misc
Corrective Action Required
03/13/2012

1504.4 Fire protection. Spray booths and spray rooms shall be protected by an approved automatic fire-extinguishing system complying with Chapter 9. Protection shall also extend to exhaust plenums, exhaust ducts and both sides of dry filters when such filters are used. Action Required: Fire protection shall extend into plenums, ducts and shall cover filters if applicable.
Construction documents - Fire protection systems
Corrective Action Required
03/13/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action Required: Provide construction documents on any alterations to the sprinkler system
Construction documents for fire alarm systems
Corrective Action Required
03/13/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action Required: Provide construction documents for any alterations to the fire alarm system
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Alteration to Commercial $82.48 $82.48 Paid 03/22/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Gas Piping Inspection - Commercial Partial 4/20/2012 4/20/2012 at 12:00 AM 04/20/2012
Misc
Partial Correction
04/20/2012
VISUAL INSPECTION AND PRESSURE TEST APPROVED FOR 3" & DOWN STEEL PIPING FROM OUTSIDE BLDG NE CORNER OVERHEAD TO W PAINT BOOTH HEATER. SUBSEQUENT INSPECTION REQUIRED WHEN E PAINT BOOTH IS INSTALLED.
Rough Electrical Inspection - Commercial Partial 4/24/2012 4/24/2012 at 12:00 AM 04/24/2012
Misc
Corrective Action Required
04/24/2012
-ELECTRICAL TO 1ST PAINT BOOTH INSTALLED
Sprinkler - Flow Test Passed 4/24/2012 at 1:00 AM 04/24/2012
Alarm Test Passed 4/25/2012 at 3:30 AM 04/25/2012
Misc
Corrective Action Required
04/24/2012
PRCOM20120415 sprinkler system and paint booths need to be monitored by an alarm monitoing company. sprinkler system needs the annual cert. inspection. sprinkler riser back flow prev. will be due for annual test in july.
Occupancy Inspection - Codes Commercial Partial 4/26/2012 at 12:00 AM 04/26/2012
Misc
Corrective Action Required
04/26/2012
*THIS INSPECTION ONLY COVERS THE 1ST SPRAY BOOTH. THE 2ND SPRAY BOOTH IS NOT INSTALLED YET. CORRECT THE FOLLOWING FOR THE 1ST SPRAY BOOTH: -OUTSIDE DIFFUSERS -SECURE ALL THE MC CABLES ABOVE THE BOOTH -CONDUIT TO MIXING RM SEALED BOTH SIDE? *OK TO USE THE BOOTH
Occupancy Inspection - Fire Temporary C of O 4/26/2012 at 12:00 AM 04/26/2012
Misc
Corrective Action Required
04/26/2012
(1) material Safety Data sheets need to be on site (2) label all exterior doors with the NFPA placards and the msds hazard ratings (3) paint booths need to be monitored by the FACP and alarm co. (4) install knox box by the FDC and a access key (5) test second paint booth after install is complete.
Occupancy Inspection - Codes Commercial Failed 05/22/2012
Misc
Corrective Action Required
04/26/2012
*THIS INSPECTION ONLY COVERS THE 1ST SPRAY BOOTH. THE 2ND SPRAY BOOTH IS NOT INSTALLED YET. CORRECT THE FOLLOWING FOR THE 1ST SPRAY BOOTH: -OUTSIDE DIFFUSERS -SECURE ALL THE MC CABLES ABOVE THE BOOTH -CONDUIT TO MIXING RM SEALED BOTH SIDE? *OK TO USE THE BOOTH
Corrective Action Required
05/22/2012
MUST RECIEVE PLANNING APPROVAL FOR THIS PROJECT BEFORE CLOSING THIS PERMIT. CONCERNS AS TO THE ACCESSABLE PARKINIG.
Rough Electrical Inspection - Commercial Passed 07/31/2012
Misc
Resolved
07/31/2012
-ELECTRICAL TO 1ST PAINT BOOTH INSTALLED
Gas Piping Inspection - Commercial Passed 07/31/2012
Misc
Resolved
07/31/2012
VISUAL INSPECTION AND PRESSURE TEST APPROVED FOR 3" & DOWN STEEL PIPING FROM OUTSIDE BLDG NE CORNER OVERHEAD TO W PAINT BOOTH HEATER. SUBSEQUENT INSPECTION REQUIRED WHEN E PAINT BOOTH IS INSTALLED.
Occupancy Inspection - Codes Commercial Not Ready 7/31/2012 7/31/2012 at 12:00 AM 07/31/2012
Misc
Corrective Action Required
07/31/2012
-FIRE DEPT APPROVAL REQUIRED. DEFICIENCIES ON SEPARATE LIST -PLANNING DEPT APPROVAL FOR ACCESSIBLE PARKING SPACE IN ADDITION, CORRECT THE FOLLOWING: -SECURE ALL THE MC CABLES PER CODE ABOVE BOTH BOOTHS *DO NOT USE THE EAST SPRAY BOOTH
Occupancy Inspection - Fire Not Ready 7/31/2012 at 12:00 AM 08/08/2012
Misc
Corrective Action Required
04/26/2012
(1) material Safety Data sheets need to be on site (2) label all exterior doors with the NFPA placards and the msds hazard ratings (3) paint booths need to be monitored by the FACP and alarm co. (4) install knox box by the FDC and a access key (5) test second paint booth after install is complete.
Alarm Test Failed 7/31/2012 at 12:00 AM 08/08/2012
Alarm Test Passed 8/8/2012 at 8:00 AM 08/08/2012
Misc
Corrective Action Required
04/24/2012
PRCOM20120415 sprinkler system and paint booths need to be monitored by an alarm monitoing company. sprinkler system needs the annual cert. inspection. sprinkler riser back flow prev. will be due for annual test in july.
Occupancy Inspection - Fire Passed 8/8/2012 at 12:00 AM 08/08/2012
Misc
Corrective Action Required
08/08/2012
(1) material Safety Data sheets need to be on site (2) label all exterior doors with the NFPA placards and the msds hazard ratings (3) paint booths need to be monitored by the FACP and alarm co. (4) install knox box by the FDC and a access key (5) test second paint booth after install is complete.
Occupancy Inspection - Codes Commercial Full C of O 8/8/2012 8/8/2012 at 12:00 AM 08/08/2012
Misc
Resolved
08/08/2012
-FIRE DEPT APPROVAL REQUIRED. DEFICIENCIES ON SEPARATE LIST -PLANNING DEPT APPROVAL FOR ACCESSIBLE PARKING SPACE IN ADDITION, CORRECT THE FOLLOWING: -SECURE ALL THE MC CABLES PER CODE ABOVE BOTH BOOTHS *DO NOT USE THE EAST SPRAY BOOTH
Occupancy Inspection - Planning Passed 08/09/2012
Corrective Action Required
08/10/2012
The single dead deciduous tree along the south of the entry driveway shall be replaced with another tree of comparable size per Ordinance #7128.
Documents & Images
Date Uploaded File Type Document Name
03/20/2012 Letter Plan Review Conditions
03/22/2012 Letter Building Permit
04/24/2012 Letter Inspection Summary
04/26/2012 Letter Inspection Summary
05/22/2012 Letter Inspection Summary
07/31/2012 Letter Inspection Summary
08/08/2012 Letter Field Certificate of Occupancy
08/09/2012 Letter Final Certificate of Occupancy
08/10/2012 Letter Planning Inspection Summary
06/25/2013 Letter Fire Building Plan Review
07/02/2013 Letter Plan Review Conditions
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home