Permit Application Status

PRCOM20120199


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20120199
Building Permit - Commercial
Final Completion
DOUGLAS STATION SHOPPING CENTER LLC
ALTERATION COMMERCIAL
ELECTRICAL FOR LIGHT FIXTURES/APPLIANCES
02/08/2012
02/08/2012
04/30/2012
Locations
Contacts
RONALD JOHNSON CONSTRUCTION LLC, Address:9305 E 227TH STREET, Phone:(816) 507-3030  
DOUGLAS STATION SHOPPING CENTER LLC, Address:3215 NE CARNEGIE DR STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 02/21/2012 02/21/2012
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
02/21/2012

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide plans for any alterations to the fire protection systems within the building.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
02/21/2012

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The hood fire suppression system and building fire protection systems shall have documentation of a current 6 month inspection for the hood system and annual inspection for the building fire protection.
Posting of occupant load
Corrective Action Required
02/21/2012

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Verified at inspection.
Internal Plan Review (Res) Approved 02/21/2012 02/08/2012
Codes Admin
True
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $30.00 $30.00 Paid 02/08/2012
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Miscellaneous Inspection Failed 3/27/2012 at 12:00 AM 03/27/2012
Misc
Corrective Action Required
03/27/2012
TWO FIRE PROTECTION SPRINKLER HEAD ESCUTCHEONS MISSING AT KITCHEN
Misc
Corrective Action Required
03/27/2012
INDIVIDUAL BACKFLOW PREVENTION IS REQUIRED AT WATER-FED EQUIPMENT TO PREVENT CROSS-CONTAMINATION
Misc
Corrective Action Required
03/27/2012
DRAIN TO BE INSTALLED AT ESPRESSO MACHINE
Misc
Corrective Action Required
03/27/2012
CLEAR ANY ISSUES WITH LS FIRE DEPARTMENT
Final Electrical Inspection - Commercial Failed 3/27/2012 at 12:00 AM 03/27/2012
Misc
Corrective Action Required
03/27/2012
PANEL SCHEDULES TO BE VERIFIED
Misc
Corrective Action Required
03/27/2012
ELECTRICAL RECEPTACLE BELOW COFFEE MACHINES TO BE GFCI PROTECTED
Miscellaneous Inspection Passed 4/3/2012 at 12:00 AM 04/03/2012
Misc
Resolved
04/03/2012
TWO FIRE PROTECTION SPRINKLER HEAD ESCUTCHEONS MISSING AT KITCHEN
Misc
Resolved
04/03/2012
INDIVIDUAL BACKFLOW PREVENTION IS REQUIRED AT WATER-FED EQUIPMENT TO PREVENT CROSS-CONTAMINATION
Misc
Resolved
04/03/2012
DRAIN TO BE INSTALLED AT ESPRESSO MACHINE
Misc
Resolved
04/03/2012
CLEAR ANY ISSUES WITH LS FIRE DEPARTMENT
Final Electrical Inspection - Commercial Passed 4/3/2012 at 12:00 AM 04/03/2012
Misc
Resolved
04/03/2012
PANEL SCHEDULES TO BE VERIFIED
Misc
Resolved
04/03/2012
ELECTRICAL RECEPTACLE BELOW COFFEE MACHINES TO BE GFCI PROTECTED
Documents & Images
Date Uploaded File Type Document Name
02/08/2012 Letter Building Permit
02/08/2012 Activity Document 20120208130844231.pdf
03/27/2012 Letter Inspection Summary
04/03/2012 Letter Inspection Summary
06/25/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home