Review Type |
Outcome |
Est. Completion Date |
Completed |
Alarm Plan Review
|
Released for Construction
|
|
01/04/2012
|
|
Jim Eden
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Plans received 12/28/2011.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule an alarm test. Tests shall be conducted prior to the regular hours of the neighboring tenants.
|
|
Misc
Corrective Action Required
Duct detector activations shall be handled as supervisory alarms only.
Verified at inspection.
|
|
|
Sprinkler Plan Review
|
Released for Construction
|
|
12/16/2011
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Plans recieved December 8, 2011. The correct address is 880 NW Blue Pkwy, Suite E.
|
|
Fire protection equipment identification
Corrective Action Required
2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Valves shall be clearly marked to indicate thae area served.
|
|
Misc
Corrective Action Required
Confirm adequate coverage to the wall in the space to the right (east ?).
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Call (816) 969-1300 to schedule tests and inspection.
|
|
|
Internal Plan Review (Res)
|
Approved
|
|
11/18/2011
|
|
Codes Admin
|
|
True
|
Building Plan Review
|
Approved
|
11/04/2011
|
11/04/2011
|
|
Joe Frogge
|
|
Misc
Provide accessible fitting room per 2006 IBC 1109.12.1 and 2003 ICC/ANSI A117.1
Action Required - make needed corrections.
|
|
License Tax Application
A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
|
|
License contractors
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances.
Action Required - provide list of sub-contractors
Permit may not be issued prior to listing of subs.
|
|
Business License
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action Required - provide name of general contractor. Permit may not be issued prior to listing general contractor.
|
|
|
Fire Plan Review
|
Approved
|
11/04/2011
|
11/03/2011
|
|
Brian Austerman
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
PROVIDE PLANS FOR SPRINKLER SYSTEM ALTERATIONS
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
PROVIDE PLANS FOR ALARM SYSTEM ALTERATIONS
|
|
Misc
Corrective Action Required
1008.1.8.4 Bolt locks.
Manually operated flush bolts or surface bolts are not permitted.
CNANGE DOOR 107 HARDWARE TO BE 1/4 TURN THUMB LATCH
|
|
|
Internal Plan Review (Res)
|
Rejected
|
|
10/19/2011
|
|
Joe Frogge
|
|
|
Building Plan Review
|
Rejected
|
10/20/2011
|
10/19/2011
|
|
Joe Frogge
|
|
Misc
Corrective Action Required
Provide accessible fitting room per 2006 IBC 1109.12.1 and 2003 ICC/ANSI A117.1
Action Required - make needed corrections.
|
|
License Tax Application
Corrective Action Required
A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
|
|
License contractors
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances.
Action Required - provide list of sub-contractors
Permit may not be issued prior to listing of subs.
|
|
Business License
Corrective Action Required
Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances.
Action Required - provide name of general contractor. Permit may not be issued prior to listing general contractor.
|
|
Accessibility - Drinking fountains - Spout height
Corrective Action Required
ICC/ANSI A117.1 2003 602.4 - Spout outlet height. Spout outlets of wheelchair accessible drinking fountains shall be 36 inches maximum above the floor. Spout outlets of drinking fountains for standing persons shall be 38 inches minimum and 43 inches maximum above the floor.
Action required - provide information as to how specified unit satisfies both requirements.
|
|
|
Zoning Review
|
Approved
|
10/20/2011
|
10/19/2011
|
|
Codes Admin
|
|
|
License Tax Codes
|
Approved
|
10/20/2011
|
10/19/2011
|
|
Codes Admin
|
|
|
Fire Plan Review
|
Approved
|
10/20/2011
|
10/11/2011
|
|
Brian Austerman
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Provide plans for any sprinkler system modifications
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Provide drawings for any alarm system modifications
|
|
Misc
Corrective Action Required
2006 IFC 1008.1.8 Door operations.
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.
Panic hardware or 1/4 thumb latch only shall be used on exit doors. Double keyed deadbolts are not allowed. For information only.
|
|
Address numbers required
Corrective Action Required
2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Provide addressing on all doors leading into the space
|
|
|