Permit Application Status

PRCOM20115575


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20115575
Building Permit - Commercial
Certificate of Occupancy
CBL LEES SUMMIT EAST LLC
NEW TENANT FINISH
TENANT FINISH FOR TUX RENTAL
10/10/2011
11/18/2011
10/14/2014
02/10/2012
Locations
Contacts
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
SOUP DESIGN, Address:6300 BROOKSIDE PLAZA, STE 511 I  
ZIPCO CONTRACTING INC, Address:4110 N CORRINGTON AVE, Phone:(816) 471-3797  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
RELIABLE MECHANICAL SERVICES, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
MORSE ELECTRIC, Address:815 NORTH ST, Phone:(816) 785-2385  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 01/04/2012
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
01/04/2012

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Plans received 12/28/2011.
Installation acceptance testing
Corrective Action Required
01/04/2012

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule an alarm test. Tests shall be conducted prior to the regular hours of the neighboring tenants.
Misc
Corrective Action Required
01/04/2012

Duct detector activations shall be handled as supervisory alarms only. Verified at inspection.
Sprinkler Plan Review Released for Construction 12/16/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
12/16/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans recieved December 8, 2011. The correct address is 880 NW Blue Pkwy, Suite E.
Fire protection equipment identification
Corrective Action Required
12/16/2011

2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Valves shall be clearly marked to indicate thae area served.
Misc
Corrective Action Required
12/16/2011

Confirm adequate coverage to the wall in the space to the right (east ?).
Installation acceptance testing
Corrective Action Required
12/16/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule tests and inspection.
Internal Plan Review (Res) Approved 11/18/2011
Codes Admin
True
Building Plan Review Approved 11/04/2011 11/04/2011
Joe Frogge
Misc
Resolved
11/04/2011

Provide accessible fitting room per 2006 IBC 1109.12.1 and 2003 ICC/ANSI A117.1 Action Required - make needed corrections.
License Tax Application
Resolved
11/04/2011

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
License contractors
Resolved
11/04/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action Required - provide list of sub-contractors Permit may not be issued prior to listing of subs.
Business License
Resolved
11/04/2011

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action Required - provide name of general contractor. Permit may not be issued prior to listing general contractor.
Fire Plan Review Approved 11/04/2011 11/03/2011
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
11/03/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE PLANS FOR SPRINKLER SYSTEM ALTERATIONS
Construction documents for fire alarm systems
Corrective Action Required
11/03/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE PLANS FOR ALARM SYSTEM ALTERATIONS
Misc
Corrective Action Required
11/03/2011

1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. CNANGE DOOR 107 HARDWARE TO BE 1/4 TURN THUMB LATCH
Internal Plan Review (Res) Rejected 10/19/2011
Joe Frogge
Building Plan Review Rejected 10/20/2011 10/19/2011
Joe Frogge
Misc
Corrective Action Required
10/19/2011

Provide accessible fitting room per 2006 IBC 1109.12.1 and 2003 ICC/ANSI A117.1 Action Required - make needed corrections.
License Tax Application
Corrective Action Required
10/19/2011

A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
License contractors
Corrective Action Required
10/19/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action Required - provide list of sub-contractors Permit may not be issued prior to listing of subs.
Business License
Corrective Action Required
10/19/2011

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action Required - provide name of general contractor. Permit may not be issued prior to listing general contractor.
Accessibility - Drinking fountains - Spout height
Corrective Action Required
10/19/2011

ICC/ANSI A117.1 2003 602.4 - Spout outlet height. Spout outlets of wheelchair accessible drinking fountains shall be 36 inches maximum above the floor. Spout outlets of drinking fountains for standing persons shall be 38 inches minimum and 43 inches maximum above the floor. Action required - provide information as to how specified unit satisfies both requirements.
Zoning Review Approved 10/20/2011 10/19/2011
Codes Admin
License Tax Codes Approved 10/20/2011 10/19/2011
Codes Admin
Fire Plan Review Approved 10/20/2011 10/11/2011
Brian Austerman
Construction documents - Fire protection systems
Corrective Action Required
10/11/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide plans for any sprinkler system modifications
Construction documents for fire alarm systems
Corrective Action Required
10/11/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide drawings for any alarm system modifications
Misc
Corrective Action Required
10/11/2011

2006 IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. Panic hardware or 1/4 thumb latch only shall be used on exit doors. Double keyed deadbolts are not allowed. For information only.
Address numbers required
Corrective Action Required
10/11/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Provide addressing on all doors leading into the space
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $307.72 $307.72 Paid 11/18/2011
8331507-Sewer Connection Fee $120.00 $120.00 Paid 11/18/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Partial 11/30/2011 at 12:00 AM 11/30/2011
Misc
Corrective Action Required
11/30/2011
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: N & S DEMISING WALLS;
Underslab Plumbing Inspection - Commercial Passed 11/30/2011 at 12:00 AM 11/30/2011
In-wall Inspection Partial 12/8/2011 12/8/2011 at 12:00 AM 12/08/2011
Misc
Resolved
12/09/2011
AFTER CRIPPLE STUDS ABOVE DOOR OPEINGS ARE FULLY SCREWED OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS, BUT NOT HANGING BULKHEAD NOT READY AT 101 WEST
In-wall Inspection Passed 12/9/2011 at 12:00 AM 12/09/2011
Misc
Resolved
12/09/2011
OK TO COVER WHEN READY WALL FRAMING AND IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: N & S DEMISING WALLS;
Electrical Service Inspection Failed 12/12/2011 12/9/2011 at 12:00 AM 12/09/2011
Misc
Corrective Action Required
12/09/2011
ELECTRICAL SERVICE CABLE INSTALLED IS ALUMINUM; DRAWING/SPEC CALLS FOR COPPER
Electrical Service Inspection Passed 12/14/2011 at 12:00 AM 12/14/2011
Misc
Resolved
12/14/2011
ELECTRICAL SERVICE CABLE INSTALLED IS ALUMINUM; DRAWING/SPEC CALLS FOR COPPER
Gas Service Inspection - Commercial Not Ready 12/21/2011 at 12:00 AM 12/21/2011
Misc
Corrective Action Required
12/21/2011
PERMIT PRINTS NOT FOUND AT JOBSITE
Gas Piping Inspection - Commercial Not Ready 12/21/2011 at 12:00 AM 12/21/2011
Misc
Corrective Action Required
12/21/2011
PERMIT PRINTS NOT FOUND AT JOBSITE
Gas Service Inspection - Commercial Passed 12/27/2011 at 12:00 AM 12/27/2011
Misc
Corrective Action Required
12/21/2011
PERMIT PRINTS NOT FOUND AT JOBSITE
Gas Piping Inspection - Commercial Failed 12/27/2011 at 12:00 AM 12/27/2011
Misc
Corrective Action Required
12/21/2011
ROOFTOP PIPING FOR CLAMPS TO WOOD BLOCKS, PIPE MUST BE PAINTED AT OR BEFORE FINAL INSPECTION. USE CORRECT CLAMPS-PAINT PIPING RECALL WHEN COMPLETE
Above Ceiling Inspection Passed 1/4/2012 1/4/2012 at 12:00 AM 01/04/2012
Occupancy Inspection - Codes Commercial Failed 1/6/2012 1/6/2012 at 12:00 AM 01/06/2012
Misc
Corrective Action Required
01/06/2012
SLIPSHEETS UNDER ROOFTOP GAS PIPING SUPPORTS NOT ATTACHED TO BLOCKS; G.C. SUPT WAS ADVISED OF CORRECTION ALTERNATIVES.
Misc
Corrective Action Required
01/06/2012
ACCESSIBLE-COMPLIANT RECEPTION COUNTER NOT FOUND PROVIDED.
Misc
Corrective Action Required
01/06/2012
LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. MUST BE UL LISTED/LABELED.
Alarm Test Passed 1/5/2012 at 8:00 AM 01/06/2012
Sprinkler - Flow Test Passed 1/5/2012 at 8:00 AM 01/06/2012
Occupancy Inspection - Fire Passed 1/6/2012 at 12:00 AM 01/06/2012
Gas Piping Inspection - Commercial Passed 1/6/2012 at 12:00 AM 01/06/2012
Misc
Resolved
01/06/2012
ROOFTOP PIPING FOR CLAMPS TO WOOD BLOCKS, PIPE MUST BE PAINTED AT OR BEFORE FINAL INSPECTION. USE CORRECT CLAMPS-PAINT PIPING RECALL WHEN COMPLETE
Occupancy Inspection - Codes Commercial Failed 1/10/2012 1/10/2012 at 12:00 AM 01/10/2012
Misc
Corrective Action Required
01/06/2012
SLIPSHEETS UNDER ROOFTOP GAS PIPING SUPPORTS NOT ATTACHED TO BLOCKS; G.C. SUPT WAS ADVISED OF CORRECTION ALTERNATIVES.
Misc
Resolved
01/10/2012
ACCESSIBLE-COMPLIANT RECEPTION COUNTER NOT FOUND PROVIDED.
Misc
Corrective Action Required
01/06/2012
LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. MUST BE UL LISTED/LABELED.
Occupancy Inspection - Codes Commercial Temporary C of O 1/11/2012 at 12:00 AM 01/11/2012
Misc
Resolved
01/11/2012
SLIPSHEETS UNDER ROOFTOP GAS PIPING SUPPORTS NOT ATTACHED TO BLOCKS; G.C. SUPT WAS ADVISED OF CORRECTION ALTERNATIVES.
Misc
Corrective Action Required
01/10/2012
LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. MUST BE UL LISTED/LABELED.
Occupancy Inspection - Codes Commercial Temporary C of O 1/26/2012 at 12:00 AM 01/26/2012
Misc
Corrective Action Required
01/11/2012
LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. MUST BE UL LISTED/LABELED.
Occupancy Inspection - Codes Commercial Not Ready 2/9/2012 at 12:00 AM 02/09/2012
Misc
Corrective Action Required
01/26/2012
LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. MUST BE UL LISTED/LABELED. SIGN INSTALLER NO-SHOW 2/8 & 2/9.
Occupancy Inspection - Codes Commercial Temporary C of O 12/9/2011 at 12:00 AM 02/09/2012
Misc
Corrective Action Required
02/09/2012
LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. MUST BE UL LISTED/LABELED. SIGN INSTALLER NO-SHOW 2/8 & 2/9.
Occupancy Inspection - Codes Commercial Full C of O 2/10/2012 at 12:00 AM 02/10/2012
Misc
Resolved
02/10/2012
LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED. MUST BE UL LISTED/LABELED. SIGN INSTALLER NO-SHOW 2/8 & 2/9.
Documents & Images
Date Uploaded File Type Document Name
10/19/2011 Letter Plan Review Conditions
11/18/2011 Letter Plan Review Conditions
11/18/2011 Letter Building Permit
11/30/2011 Letter Inspection Summary
12/08/2011 Letter Inspection Summary
12/09/2011 Letter Inspection Summary
12/09/2011 Letter Inspection Summary
12/14/2011 Letter Inspection Summary
12/16/2011 Letter 20111216103633209.pdf
12/16/2011 Letter Fire (Sprinkler) Plan Review
12/21/2011 Letter Inspection Summary
12/27/2011 Letter Inspection Summary
01/04/2012 Letter Inspection Summary
01/04/2012 Letter Fire (Alarm) Plan Review Notice
01/06/2012 Letter Fire Loss Reduction Form
01/06/2012 Letter Inspection Summary
01/11/2012 Letter Temporary Certificate of Occupancy
01/26/2012 Letter Temporary Certificate of Occupancy
02/09/2012 Letter Temporary Certificate of Occupancy
02/09/2012 Letter Temporary Certificate of Occupancy
02/10/2012 Letter Field Certificate of Occupancy
02/10/2012 Letter Final Certificate of Occupancy
06/25/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home