Permit Application Status

PRCOM20115441


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20115441
Building Permit - Commercial
Certificate of Occupancy
CBL LEES SUMMIT EAST LLC
NEW TENANT FINISH
TENANT FINISH
09/30/2011
10/31/2011
10/14/2014
01/26/2012
Locations
Contacts
CBL LEES SUMMIT EAST LLC, Address:2030 HAMILTON PLACE BLVD STE 500  
SOUP DESIGN, Address:6300 BROOKSIDE PLAZA, STE 511 I  
CAMM CONSTRUCTION INC, Address:PO BOX 1417, Phone:(816) 607-3602  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
CATES ELECTRIC LLC, Address:4568 MEADOW LANE, Phone:(913) 915-2953  
STEVE THE PLUMBER INC, Address:601 S STELLA, Phone:(913) 226-6140  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 11/04/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
11/04/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans recieved November 3, 2011.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
11/04/2011

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action required: The existing sprinkler system shall have documentation of a current annual inspection.
Installation acceptance testing
Corrective Action Required
11/04/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule a test of the alarm and sprinkler system.
Fire protection equipment identification
Corrective Action Required
11/04/2011

2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Action required: The flow control valve shall be marked to identify the area (suites) served by the valve. Verified at inspection.
Fire Plan Review Approved 10/12/2011 11/01/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
11/01/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Provide plans for sprinkler modification.
Construction documents for fire alarm systems
Corrective Action Required
11/01/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide plans for alarm system modification.
Portable fire extinguishers - general
Corrective Action Required
11/01/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Provide a minimum of two, 2A:10B:C fire extinguishers. Verified at inspection.
Fire Plan Review Approved 11/02/2011 11/01/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
10/28/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit plans for review for sprinkler system modifications
Construction documents for fire alarm systems
Corrective Action Required
10/28/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Submit plans for review for any fire alarm modifications
Portable fire extinguishers - general
Corrective Action Required
10/28/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required - Provide extinguishers as required by the Fire Department. A minimum of two, 2A:10B:C fire extinguishers. Verified at inspection.
Fire Plan Review Rejected 10/12/2011 11/01/2011
Jim Eden
Portable fire extinguishers - conspicuous locations
Corrective Action Required
10/06/2011

2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. PROVIDE A MINIMUM OF TWO 2A10B:C EXTINGUISHERS
Address numbers required
Corrective Action Required
10/06/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). PROVIDE ADDRESSING ON ALL DOORS INTO THE SOACE INCLUDING SUITE NUMBERS
Construction documents - Fire protection systems
Corrective Action Required
10/06/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. PROVIDE CONSTRUCTION DOCUMENTS FOR ANY FIRE SPRINKLER MODIFICATIONS
Construction documents for fire alarm systems
Corrective Action Required
10/06/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. PROVIDE CONSTRUCTION DOCUMENTS FOR ANY FIRE ALARM SYSTEM MODIFICATIONS
Misc
Corrective Action Required
10/06/2011

2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. PROVIDE DUCT SMOKE DETECTION ON UNITS 2000 CFM OR GREATER THAT SHUT DOWN THE SYSTEM UPON ACTIVATION AND TRANSMIT A SUPERVISORY SIGNAL TO THE ALARM PANEL
Misc
Corrective Action Required
10/06/2011

2006 IFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. MARKED EXITS SHALL NOT HAVE KEYED DEADBOLTS ON THE INTERIOR, PANIC HARDWARE OR 1/4 TURN THUMB LATCH SHALL ONLY BE ALLOWED
Internal Plan Review (Res) Approved 11/02/2011 10/28/2011
Mike Weisenborn
Building Plan Review Approved 11/02/2011 10/28/2011
Mike Weisenborn
Misc
Corrective Action Required
10/28/2011

The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff. Action required - This comment is for information purposes.
License contractors
Resolved
10/28/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the m/e/p subcontractors.
Tenant Finish Plans Required
Resolved
10/28/2011

Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Separate permits shall be obtained prior to performing any work which requires permits. Action required - This comment is for information purposes.
Building Plan Review Rejected 10/20/2011 10/28/2011
Mike Weisenborn
Misc
Corrective Action Required
10/13/2011

The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff. Action required - This comment is for information purposes.
Misc
Resolved
10/14/2011

The suite/unit letter for this space has not been provided. Action required - Provide additional information.
License contractors
Corrective Action Required
10/13/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the m/e/p subcontractors.
Bldg - Accessibility - Drinking fountains minimum number
Resolved
10/14/2011

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - If a drinking fountain is being installed, this requirement has to be met. Make needed corrections.
Tenant Finish Plans Required
Corrective Action Required
10/13/2011

Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Separate permits shall be obtained prior to performing any work which requires permits. Action required - This comment is for information purposes.
Internal Plan Review (Res) Approved 10/26/2011
Codes Admin
Fire Plan Review Approved 10/20/2011 10/14/2011
Mike Weisenborn
Construction documents - Fire protection systems
Corrective Action Required
10/17/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Submit plans for review for sprinkler system modifications
Construction documents for fire alarm systems
Corrective Action Required
10/17/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Submit plans for review for any fire alarm modifications
License Tax Codes Approved 10/14/2011 10/14/2011
Mike Weisenborn
Internal Plan Review (Res) Rejected 10/12/2011 10/06/2011
Mike Weisenborn
Building Plan Review Rejected 10/12/2011 10/06/2011
Mike Weisenborn
Misc
Corrective Action Required
10/06/2011

The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff. Action required - This comment is for information purposes.
Misc
Corrective Action Required
10/06/2011

The suite/unit letter for this space has not been provided. Action required - Provide additional information.
License contractors
Corrective Action Required
10/06/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - Provide the names of the m/e/p subcontractors.
Bldg - Accessibility - Drinking fountains minimum number
Corrective Action Required
10/06/2011

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - If a drinking fountain is being installed, this requirement has to be met. Make needed corrections.
Tenant Finish Plans Required
Corrective Action Required
10/06/2011

Tenant finish plans shall be submitted to the Codes Administration Department prior to any interior alteration or improvments. Separate permits shall be obtained prior to performing any work which requires permits. Action required - This comment is for information purposes.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Alteration to Commercial $395.88 $395.88 Paid 10/26/2011
8331507-Sewer Connection Fee $240.00 $240.00 Paid 10/26/2011
9110078-Valuation Fee for New Tenent Finish $514.09 $514.09 Paid 10/31/2011
$909.97
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Electrical Inspection - Commercial Passed 11/1/2011 (8:00 to 5:00) 11/1/2011 at 12:00 AM 11/01/2011
Underslab Plumbing Inspection - Commercial Passed 11/1/2011 (8:00 to 5:00) 11/1/2011 at 12:00 AM 11/01/2011
In-wall Inspection Partial 11/1/2011 at 12:00 AM 11/01/2011
Misc
Partial Correction
11/01/2011
OK TO COVER WHEN READY WALL FRAMING + IN-WALL SYSTEMS AT FOLLOWING LOCATIONS: EAST, SOUTH, AND WEST PERIMETER WALLS;
In-wall Inspection Passed 11/2/2011 at 12:00 AM 11/02/2011
Gas Service Inspection - Commercial Passed 11/2/2011 at 12:00 AM 11/02/2011
Gas Piping Inspection - Commercial Not Ready 11/2/2011 at 12:00 AM 11/02/2011
Misc
Corrective Action Required
11/02/2011
INSTALLATION OF SUPPORTS OF ROOFTOP PIPING IN PROGRESS; MAINTAIN MAX 10' SPACING
Misc
Corrective Action Required
11/02/2011
EXPOSED GAS PIPING TO BE PAINTED BEFORE FINAL INSPECTION
In-wall Inspection Partial 11/8/2011 (8:00 to 5:00) 11/8/2011 at 12:00 AM 11/08/2011
Misc
Resolved
11/10/2011
OK TO HANG REMAINING GWB AT SALES AREA WALLS; COLUMN WRAPS, AND SOFFITS -- CONTINGENT ON SOFFIT/BULKHEAD TENSION SUPPORT STUDS BEING SCREWED BOTH FLANGES AT UPPER ENDS.
Electrical Service Inspection Passed 11/10/2011 at 12:00 AM 11/10/2011
In-wall Inspection Passed 11/10/2011 at 12:00 AM 11/10/2011
Misc
Resolved
11/10/2011
OK TO HANG REMAINING GWB AT SALES AREA WALLS; COLUMN WRAPS, AND SOFFITS -- CONTINGENT ON SOFFIT/BULKHEAD TENSION SUPPORT STUDS BEING SCREWED BOTH FLANGES AT UPPER ENDS.
Above Ceiling Inspection Partial 11/2/2011 at 12:00 AM 11/11/2011
Misc
Resolved
11/16/2011
OK TO COVER WHEN READY ACT CEILING FRAMING + ABOVE-CEILING SYSTEMS @ FOLLOWING SPACES: SALES AREA; REAR CORRIDOR;
Above Ceiling Inspection Passed 11/16/2011 at 12:00 AM 11/16/2011
Alarm Test Passed 11/17/2011 at 12:00 AM 11/17/2011
Sprinkler - Flow Test Passed 11/17/2011 at 12:00 AM 11/17/2011
Occupancy Inspection - Fire Passed 11/17/2011 at 12:00 AM 11/17/2011
Occupancy Inspection - Codes Commercial Temporary C of O 11/17/2011 11/17/2011 at 12:00 AM 11/17/2011
Misc
Corrective Action Required
11/17/2011
RESTROOMS: FLOORS TO BE FINISHED NON-ABSORBENT AND FREE OF JOINTS/CRACKS; BASE TO BE INSTALLED
Misc
Corrective Action Required
11/17/2011
FLOOR SINK: COMPLETE CAULK JOINT AT WALL
Misc
Corrective Action Required
11/17/2011
WATER HEATER: INSTALL E.T. PER DRWG; RAISE TO FACILITATE FULL DRAIN TO FLOOR SINK; ENSURE TPR PIPE TERMINATES NO MORE THAN 6" AFF
Misc
Corrective Action Required
11/17/2011
PERMANENT TAG GAS SERVICE 910 M
Misc
Corrective Action Required
11/17/2011
IN-USE COVER REQUIRED AT RTU ELECTRICAL RECEPTACLE
Misc
Corrective Action Required
11/17/2011
EXTERIOR LIGHTED SIGN MUST BE MANUFACTURED BY UL CERTIFIED COMPANY AND BE LABELED ACCORDINGLY.
Occupancy Inspection - Codes Commercial Temporary C of O 11/21/2011 at 12:00 AM 12/05/2011
Misc
Resolved
11/21/2011
RESTROOMS: FLOORS TO BE FINISHED NON-ABSORBENT AND FREE OF JOINTS/CRACKS; BASE TO BE INSTALLED
Misc
Resolved
11/21/2011
FLOOR SINK: COMPLETE CAULK JOINT AT WALL
Misc
Resolved
11/21/2011
WATER HEATER: INSTALL E.T. PER DRWG; RAISE TO FACILITATE FULL DRAIN TO FLOOR SINK; ENSURE TPR PIPE TERMINATES NO MORE THAN 6" AFF
Misc
Resolved
11/21/2011
PERMANENT TAG GAS SERVICE 910 M
Misc
Resolved
11/21/2011
IN-USE COVER REQUIRED AT RTU ELECTRICAL RECEPTACLE
Misc
Corrective Action Required
11/17/2011
EXTERIOR LIGHTED SIGN MUST BE MANUFACTURED BY UL CERTIFIED COMPANY AND BE LABELED ACCORDINGLY.
Occupancy Inspection - Codes Commercial Temporary C of O 12/5/2011 at 12:00 AM 12/05/2011
Misc
Corrective Action Required
11/21/2011
EXTERIOR LIGHTED SIGN MUST BE MANUFACTURED BY UL CERTIFIED COMPANY AND BE LABELED ACCORDINGLY.
Occupancy Inspection - Codes Commercial Temporary C of O 12/15/2011 at 12:00 AM 12/15/2011
Occupancy Inspection - Codes Commercial Temporary C of O 12/20/2011 at 12:00 AM 12/20/2011
Occupancy Inspection - Codes Commercial Temporary C of O 1/20/2012 at 12:00 AM 01/20/2012
Misc
Corrective Action Required
01/20/2012
EXTERIOR LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED
Occupancy Inspection - Codes Commercial Full C of O 1/26/2012 at 12:00 AM 01/26/2012
Misc
Resolved
01/26/2012
EXTERIOR LIGHTED SIGN SUBJECT TO APPROVAL WHEN INSTALLED
Documents & Images
Date Uploaded File Type Document Name
10/06/2011 Letter Plan Review Conditions
10/26/2011 Letter Building Permit
10/26/2011 Letter Plan Review Conditions
10/31/2011 Letter Building Permit
11/01/2011 Letter Inspection Summary
11/02/2011 Letter Inspection Summary
11/08/2011 Letter Inspection Summary
11/10/2011 Letter Inspection Summary
11/11/2011 Letter Inspection Summary
11/16/2011 Letter Inspection Summary
11/17/2011 Letter Fire Loss Reduction Form
11/17/2011 Letter Temporary Certificate of Occupancy
11/21/2011 Letter Inspection Summary
12/05/2011 Letter Temporary Certificate of Occupancy
12/15/2011 Letter Temporary Certificate of Occupancy
12/20/2011 Letter Temporary Certificate of Occupancy
01/20/2012 Letter Temporary Certificate of Occupancy
01/26/2012 Letter Field Certificate of Occupancy
01/27/2012 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire (Sprinkler) Plan Review
08/27/2013 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home