Summary
PRCOM20114797
Building Permit - Commercial
Final Completion
SOUTHWESTERN BELL TELEPHONE
ADD/ALTER OTHER
GENERATOR INSTALLATION
08/30/2011
09/19/2011
03/10/2012
07/21/2015
Locations
Contacts
SOUTHWESTERN BELL TELEPHONE, Address:ONE SBC CENTER 36-M-1  
CELESTE INSTALLATIONS, Address:16730 NW 89TH ST, Phone:(816) 536-3499  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 09/22/2011 09/16/2011
Mike Weisenborn
License Tax Codes Approved 09/12/2011 09/16/2011
Mike Weisenborn
Fire Plan Review Approved 09/22/2011 09/15/2011
Jim Eden
Misc
Resolved
09/15/2011

Provide specifications for the generator fuel tanks including size.
Misc
Resolved
09/15/2011

Fire Department- 2006 IFC 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. Action required: Provide 704 placard, product identification label and no smoking signage on the generator/tank. Verified at inspection.
Internal Plan Review (Res) Rejected 09/12/2011 09/12/2011
Mike Weisenborn
Building Plan Review Approved 09/12/2011 09/12/2011
Mike Weisenborn
Fire Plan Review Rejected 09/12/2011 09/01/2011
Jim Eden
Misc
Corrective Action Required
09/01/2011

Provide specifications for the generator fuel tanks including size.
Misc
Corrective Action Required
09/01/2011

Fire Department- 2006 IFC 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. Action required: Provide 704 placard, product identification label and no smoking signage on the generator/tank. Verified at inspection.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Add/Alter Other $30.00 $30.00 Paid 09/19/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underground Electrical Inspection - Commercial Partial 9/19/2011 at 12:00 AM 11/10/2011
Misc
Corrective Action Required
11/10/2011
OK TO ENCASE AND COVER ONE 2" AND THREE 1" PVC SCH 40 CONDUITS + ONE TINNED COPPER GROUNDING CONDUCTOR FROM ATS TO GENERATOR LOCATION CONTINGENT ON ENGINEER CLARIFICATION THAT: 1) CONCRETE ENCASEMENT IS ACCEPTABLE ALTERNATIVE TO 36" BURIAL DEPTH AND 2) SEALTITE PROTECTION FOR BURIED GROUNDING CONDUCTOR APPLIES ONLY WHERE CONDUCTOR IS ABOVE GRADE.
Underground Electrical Inspection - Commercial Passed 11/10/2011 at 12:00 AM 11/10/2011
Misc
Resolved
11/10/2011
OK TO ENCASE AND COVER ONE 2" AND THREE 1" PVC SCH 40 CONDUITS + ONE TINNED COPPER GROUNDING CONDUCTOR FROM ATS TO GENERATOR LOCATION CONTINGENT ON ENGINEER CLARIFICATION THAT: 1) CONCRETE ENCASEMENT IS ACCEPTABLE ALTERNATIVE TO 36" BURIAL DEPTH AND 2) SEALTITE PROTECTION FOR BURIED GROUNDING CONDUCTOR APPLIES ONLY WHERE CONDUCTOR IS ABOVE GRADE.
Final Electrical Inspection - Commercial Partial 11/15/2011 at 12:00 AM 11/15/2011
Misc
Partial Correction
11/15/2011
NO CODES ISSUES; RESOLVE LABELING REQUIREMENT WITH FIRE DEPARTMENT.
Occupancy Inspection - Fire Temporary C of O 11/15/2011 at 12:00 AM 11/15/2011
Misc
Corrective Action Required
11/15/2011
(1) place a NFPA placard on the fuel cell with the MSDS hazard rating of the fuel (2) identify the type of fuel being utilized with a label on the fuel cell "DIESEL"
Documents & Images
Date Uploaded File Type Document Name
09/12/2011 Letter Plan Review Conditions
09/15/2011 Letter Generator Ltr
09/15/2011 Letter Generator Specs
09/19/2011 Letter Building Permit
09/19/2011 Letter Inspection Summary
09/19/2011 Letter Inspection Summary
11/10/2011 Letter Inspection Summary
11/11/2011 Activity Document 20111111152557472.pdf
11/15/2011 Letter Inspection Summary
11/15/2011 Letter Fire Loss Reduction Form
06/25/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Building Plan Review
07/20/2015 Letter Inspection Summary
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home