Permit Application Status

PRCOM20113275


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20113275
Building Permit - Commercial
Certificate of Occupancy
SUMMIT NORTHRIDGE LLC
NEW TENANT FINISH
TENANT FINSH FOR A DENTAL OFFICE IN PREVIOUSLY UNOCCUPIED SPACE
06/24/2011
08/04/2011
10/14/2014
11/02/2011
Locations
Contacts
GRUNLOH BUILDING INC, Address:901 NORTH SECOND ST, Phone:(217) 342-2221  
S & S ELECTRICAL CONTRACTING LLC, Address:574 NW 1921 RD, Phone:(816) 847-2433  
CHIEF HEATING & COOLING INC, Address:920 NW TECHNOLOGY DR, Phone:(816) 246-4646  
HAMPTON PLUMBING INC, Address:P O BOX 552, Phone:(816) 628-5069  
SUMMIT NORTHRIDGE LLC, Address:605 W 47TH ST STE 200  
Reviews
Review Type Outcome Est. Completion Date Completed
Alarm Plan Review Released for Construction 10/12/2011
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
10/12/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Plans received October 12, 2011.
Installation acceptance testing
Corrective Action Required
10/12/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule a test. Testing shall be done before the regular business hours of the neighboring tenants.
Sprinkler Plan Review Released for Construction 09/29/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
09/29/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received September 28, 2011.
Misc
Corrective Action Required
09/29/2011

A visual inspection will be completed at the occupancy inspection.
Internal Plan Review (Res) Approved 08/05/2011 08/04/2011
Mike Weisenborn
License Tax Codes Approved 08/05/2011 08/04/2011
Mike Weisenborn
Can not add the general contractor until he has a valid business license.
Building Plan Review Approved 08/05/2011 08/04/2011
Mike Weisenborn
Business License
Resolved
08/04/2011

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Please verify that the general contractor has a valid Class B General Contractors License. I was unable to find you in our system.
Bldg - Types of construction - General
Resolved
08/04/2011

2006 IBC 602.1 - General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602. Action required - The construction type set for the shell building was Type II-B. Make needed corrections.
Plumb - Separate facilities
Corrective Action Required
07/29/2011

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Label the restrooms on the plans. Mike Weisenborn August 04, 2011 - Signage will be verified on inspection.
Accessibility - Water closet - Grab bars
Resolved
08/04/2011

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - The vertical grab bar is not shown on the plans. Make needed corrections.
Bldg - Toilet rooms - Floor surface and walls
Resolved
08/04/2011

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - Make needed corrections for the rear toilet room.
Accessibility - Maneuvering Clearance at Doors.
Resolved
08/04/2011

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The door to the rear toilet does not meet this requirement. Make needed corrections.
Bldg - Toilet rooms - Walls
Corrective Action Required
07/29/2011

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - This applies not only to the wall behind the toilet but any sidewall within the specified destance. If paint is to be used in this area it must be an epoxy paint. Make needed corrections. Mike Weisenborn August 04, 2011 - Epoxy paint will be used in the men's restroom per the responce letter.
Misc
Resolved
08/04/2011

Sheets M1, P1, E1 and N1 are not sealed and signed by an engineer licensed in the State of Missouri. Action Required - Provide three (3) copies of sealed and signed sheets.
Mech - Outdoor air required
Resolved
08/04/2011

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action Required - Provide calculations for the outdoor air and how it will be obtained.
Misc
Resolved
08/04/2011

The three exhaust fans are shown to be tied into one common exhaust with nothing to keep the exhaust from one fan to be pushed into another space. Action Required - Make needed corrections.
Misc
Resolved
08/04/2011

The sizes of the mechanical ducts are not provided on the plans. Action Required - Add additional information.
Misc
Resolved
08/04/2011

I am unable to locate details for the construction of the water heater shelf. Action Required - Provide additional information.
Misc
Resolved
08/04/2011

Sizing of all waste, vent and water piping is not provide. Action Required - Provide addtional detail on the plans.
Fire Plan Review Rejected 08/05/2011 08/01/2011
Jim Eden
Misc
Corrective Action Required
08/01/2011

2006 IFC 3006.2 Interior supply location. Medical gases shall be stored in areas dedicated to the storage of such gases without other storage or uses. Where containers of medical gases in quantities greater than the permit amount are located inside buildings, they shall be in a 1-hour exterior room, a 1-hour interior room or a gas cabinet in accordance with Section 3006.2.1, 3006.2.2 or 3006.2.3.2006 IFC 3006.2.1 One-hour exterior rooms. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be self-closing smoke- and draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms shall have at least one exterior wall that is provided with at least two vents. Each vent shall not be less than 36 square inches (0.023 m2) in area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with at least one automatic sprinkler to provide container cooling in case of fire. Action required: Make corrections to meet the requirements for exterior gas storage. 08/01/2011 Provide a detail for room construction along with mechanical plans for the room vents that meet the requirements of this section.
Misc
Resolved
08/01/2011

The door to the gas storage room shall be marked "compressed gasses" and have a an NFPA 704 placard on the room door and front and rear doors of the building. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
08/01/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for the sprinkler system alteration.
Construction documents for fire alarm systems
Corrective Action Required
08/01/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for the alarm system alteration.
Portable fire extinguishers - conspicuous locations
Resolved
08/01/2011

2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Action required: Move the fire extinguisher from utility area to a conspicuous location at the front of the building.
Address numbers required
Resolved
08/01/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Verified at inspection.
Misc
Resolved
08/01/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required: Confirm if exterior emergency lights are present as part of the shell building or provide.
Internal Plan Review (Res) Rejected 07/07/2011
Mike Weisenborn
Fire Plan Review Rejected 07/07/2011 07/07/2011
Jim Eden
Misc
Corrective Action Required
07/07/2011

2006 IFC 3006.2 Interior supply location. Medical gases shall be stored in areas dedicated to the storage of such gases without other storage or uses. Where containers of medical gases in quantities greater than the permit amount are located inside buildings, they shall be in a 1-hour exterior room, a 1-hour interior room or a gas cabinet in accordance with Section 3006.2.1, 3006.2.2 or 3006.2.3.2006 IFC 3006.2.1 One-hour exterior rooms. A 1-hour exterior room shall be a room or enclosure separated from the remainder of the building by fire barriers with a fire-resistance rating of not less than 1 hour. Openings between the room or enclosure and interior spaces shall be self-closing smoke- and draft-control assemblies having a fire protection rating of not less than 1 hour. Rooms shall have at least one exterior wall that is provided with at least two vents. Each vent shall not be less than 36 square inches (0.023 m2) in area. One vent shall be within 6 inches (152 mm) of the floor and one shall be within 6 inches (152 mm) of the ceiling. Rooms shall be provided with at least one automatic sprinkler to provide container cooling in case of fire. Action required: Make corrections to meet the requirements for interior gas storage.
Misc
Corrective Action Required
07/07/2011

The door to the gas storage room shall be marked "compressed gasses" and have a an NFPA 704 placard on the room door and front and rear doors of the building. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
07/07/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for the sprinkler system alteration.
Construction documents for fire alarm systems
Corrective Action Required
07/07/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for the alarm system alteration.
Portable fire extinguishers - conspicuous locations
Corrective Action Required
07/07/2011

2006 IFC 906.5- Conspicuous location. Portable fire extinguishers shall be located in conspicuous locations where they will be readily accessible and immediately available for use. These locations shall be along normal paths of travel, unless the fire code official determines that the hazard posed indicates the need for placement away from normal paths of travel. Action required: Move the fire extinguisher from utility area to a conspicuous location at the front of the building.
Address numbers required
Corrective Action Required
07/07/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Verified at inspection.
Misc
Corrective Action Required
07/07/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required: Confirm if exterior emergency lights are present as part of the shell building or provide.
Building Plan Review Rejected 07/07/2011 07/07/2011
Mike Weisenborn
Business License
Corrective Action Required
07/06/2011

Lee's Summit Code of Ordinance, Section7-130.10 - Business License. It shall be unlawfull for any person to engage in the construction contracting business without first obtaining a business license as required under the applicable provisions of Chapter 28 of the Lee's Summit Code of Ordinances. Action required - Please verify that the general contractor has a valid Class B General Contractors License. I was unable to find you in our system.
Bldg - Types of construction - General
Corrective Action Required
07/07/2011

2006 IBC 602.1 - General. Buildings and structures erected or to be erected, altered or extended in height or area shall be classified in one of the five construction types defined in Sections 602.2 through 602.5. The building elements shall have a fire-resistance rating not less than that specified in Table 601 and exterior walls shall have a fire-resistance rating not less than that specified in Table 602. Action required - The construction type set for the shell building was Type II-B. Make needed corrections.
Plumb - Separate facilities
Corrective Action Required
07/07/2011

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - Label the restrooms on the plans.
Accessibility - Water closet - Grab bars
Corrective Action Required
07/07/2011

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - The vertical grab bar is not shown on the plans. Make needed corrections.
Bldg - Toilet rooms - Floor surface and walls
Corrective Action Required
07/07/2011

2006 IBC 1210.1 - Floors. In other than dwelling units, toilet and bathing room floors shall have a smooth, hard, nonabsorbent surface that extends upward onto the walls at least 6 inches. Action required - Make needed corrections for the rear toilet room.
Accessibility - Maneuvering Clearance at Doors.
Corrective Action Required
07/07/2011

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The door to the rear toilet does not meet this requirement. Make needed corrections.
Bldg - Toilet rooms - Walls
Corrective Action Required
07/07/2011

2006 IBC 1210.2 - Walls. Walls within 2 feet of urinals and water closets shall have a smooth, hard, nonabsorbent surface, to a height of 4 feet above the floor, and except for structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. Exceptions: 1. Dwelling units and sleeping units. 2. Toilet rooms that are not accessible to the public and which have not more than one water closet. Accessories such as grab bars, towel bars, paper dispensers and soap dishes, provided on or within walls, shall be installed and sealed to protect structural elements from moisture. Action required - This applies not only to the wall behind the toilet but any sidewall within the specified destance. If paint is to be used in this area it must be an epoxy paint. Make needed corrections.
Misc
Corrective Action Required
07/07/2011

Sheets M1, P1, E1 and N1 are not sealed and signed by an engineer licensed in the State of Missouri. Action Required - Provide three (3) copies of sealed and signed sheets.
Mech - Outdoor air required
Corrective Action Required
07/07/2011

2006 IMC 403.2 - Outdoor air required. The minimum ventilation of outdoor air shall be determined in accordance with Section 403.3. Exception: Where the registered design professional demonstrates that an engineered ventilation system design will prevent the maximum concentration of contaminants from exceeding the obtainable by the rate of outdoor air ventilation determined in accordance with Section 403.3, the minimum required rate of outdoor air shall be reduced in accordance with such engineered system design. Action Required - Provide calculations for the outdoor air and how it will be obtained.
Misc
Corrective Action Required
07/07/2011

The three exhaust fans are shown to be tied into one common exhaust with nothing to keep the exhaust from one fan to be pushed into another space. Action Required - Make needed corrections.
Misc
Corrective Action Required
07/07/2011

The sizes of the mechanical ducts are not provided on the plans. Action Required - Add additional information.
Misc
Corrective Action Required
07/07/2011

I am unable to locate details for the construction of the water heater shelf. Action Required - Provide additional information.
Misc
Corrective Action Required
07/07/2011

Sizing of all waste, vent and water piping is not provide. Action Required - Provide addtional detail on the plans.
Zoning Review Approved 07/07/2011 07/01/2011
Chris Hughey
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New Tenent Finish $448.39 $448.39 Paid 08/04/2011
8331507-Sewer Connection Fee $540.00 $540.00 Paid 08/04/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Partial 8/5/2011 (8:00 to 5:00) 8/5/2011 at 12:00 AM 08/05/2011
Misc
Partial Correction
08/05/2011
UNDER-SLAB PVC DWV PIPING OK TO COVER WHEN READY
Underslab Electrical Inspection - Commercial Passed 8/10/2011 8/10/2011 at 12:00 AM 08/10/2011
Underslab Plumbing Inspection - Commercial Passed 8/10/2011 8/10/2011 at 12:00 AM 08/10/2011
In-wall Inspection Passed 8/18/2011 8/19/2011 at 12:00 AM 08/19/2011
Above Ceiling Inspection Not Ready 9/9/2011 9/9/2011 at 12:00 AM 09/09/2011
Misc
Corrective Action Required
09/09/2011
NO TILE TO BE PLACED BEFORE ABOVE-CEILING INSPECTION
Above Ceiling Inspection Failed 9/13/2011 9/12/2011 at 12:00 AM 09/12/2011
Misc
Resolved
09/12/2011
NO TILE TO BE PLACED BEFORE ABOVE-CEILING INSPECTION
Misc
Corrective Action Required
09/12/2011
TEMPORARY LIGHTING FIXTURES AND WIRING TO BE REMOVED FROM ABOVE CEILING
Misc
Corrective Action Required
09/12/2011
SOME CEILING SUPPORT WIRES NOT RUN STRAIGHT FROM BAR JOISTS TO GRID -- EXAMPLE: WAITING AREA; CHECK ALL
Misc
Corrective Action Required
09/12/2011
LIGHT FIXTURES NOT INSTALLED AT SPACES: TILITIY; BREAK; MEN'S
Misc
Corrective Action Required
09/12/2011
JUNCTION BOXES OPEN FOR EXTERIOR SIGN INSTALLATION
Above Ceiling Inspection Failed 9/13/2011 (8:00 to 5:00) 9/13/2011 at 12:00 AM 09/13/2011
Misc
Resolved
09/13/2011
TEMPORARY LIGHTING FIXTURES AND WIRING TO BE REMOVED FROM ABOVE CEILING
Misc
Resolved
09/13/2011
SOME CEILING SUPPORT WIRES NOT RUN STRAIGHT FROM BAR JOISTS TO GRID -- EXAMPLE: WAITING AREA; CHECK ALL
Misc
Resolved
09/13/2011
LIGHT FIXTURES NOT INSTALLED AT SPACES: UILITIY; BREAK; MEN'S
Misc
Resolved
09/13/2011
JUNCTION BOXES OPEN FOR EXTERIOR SIGN INSTALLATION
Misc
Corrective Action Required
09/13/2011
EXHAUST FANS PER DRAWINGS NOT FOUND INSTALLED
Above Ceiling Inspection Not Ready 9/15/2011 9/15/2011 at 12:00 AM 09/15/2011
Misc
Corrective Action Required
09/13/2011
EXHAUST FANS PER DRAWINGS NOT FOUND INSTALLED
Above Ceiling Inspection Passed 9/16/2011 at 12:00 AM 09/16/2011
Misc
Resolved
09/16/2011
EXHAUST FANS PER DRAWINGS NOT FOUND INSTALLED
Miscellaneous Inspection Passed 9/23/2011 at 12:00 AM 09/23/2011
Occupancy Inspection - Codes Commercial Partial 9/27/2011 9/27/2011 at 12:00 AM 09/27/2011
Misc
Corrective Action Required
09/27/2011
FLOOR SINK AT UTILITY RM: SEAL PERIMETER TO WALL TO PREVENT DETERIORATION OF GWB
Misc
Corrective Action Required
09/27/2011
PLASTER TRAP TO BE INSTALLED AT WORK AREA
Misc
Corrective Action Required
09/27/2011
RESOLVE FIRE DEPARTMENT ISSUES
Occupancy Inspection - Fire Not Ready 9/27/2011 at 12:00 AM 09/27/2011
Misc
Corrective Action Required
09/28/2011
Med -Gas room sould comply with the guidelines set in IFC 2006 3006.2.1-2.2 one hour interior and exterior rooms The amounts of oxidizing gases allowed in the closet shall not exceed 504 cubic feet at NTP. Piping for the med gases shall be labeled by stenciling or adhesive markers, labels shall show the name of the gas/vaccum system or the chemical symbol,pipe labels shall be located as follows: (1) at intervalsof not more than 20 ft. (2) at least once in or above every room (3) on both sides of walls or partitions penetrated by the piping (4) At least once in every story height transversed by risers Shut-off valves shall be identified as follows: (1) the name or symbol of the chemical for the system (2) the name and rooms or areas served (3) a caution to not close (or open) the valve except in an emergency Locations containing med-gases other than oxygen or med-air shall have their doors labeled. CAUTION, Med Gases, NO Smoking or open flame, Room may have insufficient oxygen, open door and allow room to ventilatre before entering. In the Med Gas closet uncover the sprinkler head and install the sprinkler eschution ring. In the Med -Gas closet seal all penetrations within the closet arond ducts, gas piping etc. Med Gas closet install hardware on the door to allow the door to be self closing. On or arond the fron and rear entrances in to 691 suite display a NFPA 704 placard indicating the MSDS hazards of the med gases present. Check throughout suite and install missing sprinkler head eschution rings as needed.
Occupancy Inspection - Codes Commercial Partial 10/3/2011 at 12:00 AM 10/03/2011
Misc
Resolved
10/03/2011
FLOOR SINK AT UTILITY RM: SEAL PERIMETER TO WALL TO PREVENT DETERIORATION OF GWB
Misc
Resolved
10/03/2011
PLASTER TRAP TO BE INSTALLED AT WORK AREA
Misc
Corrective Action Required
09/27/2011
RESOLVE FIRE DEPARTMENT ISSUES
Alarm Test Passed 10/14/2011 at 12:00 AM 10/21/2011
Occupancy Inspection - Fire Temporary C of O 9/27/2011 at 12:00 AM 10/21/2011
Occupancy Inspection - Fire Passed 10/25/2011 at 12:00 AM 10/25/2011
Occupancy Inspection - Codes Commercial Temporary C of O 10/25/2011 10/25/2011 at 12:00 AM 10/25/2011
Misc
Resolved
10/25/2011
RESOLVE FIRE DEPARTMENT ISSUES
Misc
Corrective Action Required
10/25/2011
VENT TERMINATION IN ELECT XFMR SERVICE YARD NOT SECURED TO WALL; HOLE SAW DEBRIS LEFT BEHIND
Occupancy Inspection - Codes Commercial Full C of O 11/2/2011 at 12:00 AM 11/02/2011
Misc
Resolved
11/02/2011
VENT TERMINATION IN ELECT XFMR SERVICE YARD NOT SECURED TO WALL; HOLE SAW DEBRIS LEFT BEHIND
Documents & Images
Date Uploaded File Type Document Name
07/07/2011 Letter Plan Review Conditions
08/04/2011 Letter Building Permit
08/04/2011 Letter Plan Review Conditions
08/05/2011 Letter Inspection Summary
08/10/2011 Letter Inspection Summary
08/19/2011 Letter Inspection Summary
08/19/2011 Letter Inspection Summary
09/09/2011 Letter Inspection Summary
09/12/2011 Letter Inspection Summary
09/13/2011 Letter Inspection Summary
09/15/2011 Letter Inspection Summary
09/16/2011 Letter Inspection Summary
09/27/2011 Letter Inspection Summary
09/28/2011 Letter Fire Loss Reduction Form
09/29/2011 Letter Fire (Sprinkler) Plan Review
10/25/2011 Letter Fire Loss Reduction Form
10/25/2011 Letter Fire Loss Reduction Form
10/25/2011 Letter Temporary Certificate of Occupancy
11/02/2011 Letter Field Certificate of Occupancy
11/03/2011 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire (Alarm) Plan Review Notice
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire Loss Reduction Form
06/21/2013 Letter Fire (Alarm) Plan Review Notice
06/25/2013 Letter Fire Building Plan Review
06/26/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home