Permit Application Status

PRCOM20113001


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20113001
Building Permit - Commercial
Certificate of Occupancy
LE GRAND APARTMENTS LLC
CHANGE OF TENANT
MODIFY SPACE FOR CHURCH EXPANSION
06/16/2011
07/25/2011
12/26/2011
01/26/2012
Locations
Contacts
WESTON BENNETT INC, Address:708 NW RD MIZE RD, Phone:(816) 229-4711  
LE GRAND APARTMENTS LLC, Address:25706 E SHADYBROOK LN  
MCINTOSH HEATING AND COOLING, Address:4316 WASHINGTON AVE, Phone:(816) 373-9500  
CROWN ELECTRICAL SERVICES, Address:1213 SE 11TH TER, Phone:(816) 272-5379  
ANGEL PLUMBING, Address:1205 NW CONWAY CIR, Phone:(816) 721-3649  
BOAN HEATING & COOLING INC, Address:12001 E STATE ROUTE 50, Phone:(816) 356-4508  
SOUTHPORT BUSINESS CENTER LLC, Address:1485 SW MARKET ST  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Approved 07/22/2011 10/24/2011
Brian Austerman
Alarm Plan Review Released for Construction 08/08/2011
Jim Eden
Construction documents for fire alarm systems
Corrective Action Required
08/08/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Plans recieved August 4, 2011.
Misc
Corrective Action Required
08/08/2011

New appliances shall be conected to and compatible with the existing fire alarm control panel.
Misc
Corrective Action Required
08/08/2011

Smoke detection shall be used in place of heat detection unless ambient conditions prohibit their use. Action required: Replace heat detection in the mechanical room with a smoke detector. Verified at inspection.
Installation acceptance testing
Corrective Action Required
08/08/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule an alarm test.
Internal Plan Review (Res) Approved 07/22/2011 07/25/2011
Mike Weisenborn
Building Plan Review Approved 07/22/2011 07/25/2011
Mike Weisenborn
Bldg - Occupant load calculations - Areas without fixed seats
Resolved
07/22/2011

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - Provide the occupant load calculations for each of the rooms/spaces. We will be looking at the highest possible occupant load of each space. Mike Weisenborn July 22, 2011 - This will be verified on inspection.
Bldg - Posting of occupant load
Corrective Action Required
07/15/2011

2006 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required - This will be verified on inspection.
Misc
Resolved
07/22/2011

The construction type indicate is Type V-B but the original building and subsiquent permits list the contruction type as Type II-B. Action required - Make needed corrections to the stated construction type and details for the stair and landing and corridor ceiling. Mike Weisenborn July 22, 2011 - Per resubmittal
Misc
Resolved
07/25/2011

No detail is provided for the handrails being installed. Action required - Provide additional information. Provide specific information on the height, graspability, extensions and installation.
Misc
Corrective Action Required
07/15/2011

The plans indicate that a chair lift is to be installed but information on the lift being installed has not provided. Action required - Provide specifications from the manufacture on the lift to be installed. Mike Weisenborn July 22, 2011 - The information provided on the lift indicates that it is for residential use. I went to the website indicated on the information provided and I couldn't find this model of lift. Please provide information on the lift to be installed showing that it meets the requirements of ASME A 18.1 as required by Section 1109.7 of the 2006 IBC. This information shall be provided prior to approval and installation of the lift.
Bldg - Accessibility - Drinking fountains minimum number
Corrective Action Required
07/15/2011

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - This code section does not allow for the installation of a single drinking fountain unless it meets both height requirements. Make needed corrections. Mike Weisenborn July 22, 2011 - Per the revised plans, this is now labeled a water cooler which I assume is a bottled water system. This will be verified on inspection.
Misc
Resolved
07/22/2011

The floor plan on sheet TF-2 does not provide the proposed uses of the new spaces created by the new corridor. Action required - Provide additional information on the plans. Mike Weisenborn July 22, 2011 - Additional information provided on the plans.
Misc
Resolved
07/22/2011

Sheet TF-2 shows three different wall types but the floor plans do not clearly indicate which wall type each wall is. Action required - Provide additional information on the plans.
Misc
Resolved
07/22/2011

The door schedule does not indicate the specific hardware to be installed on each of the doors. Action required - Provide additional information. Mike Weisenborn July 22, 2011 - Additional information provided.
Misc
Resolved
07/22/2011

The plumbing fixture schedule has fixtures on it that are not a part of it and the plumbing layout is mislabled. It indicates that a water closet is to be installed next to F-1 and that the drinking fountain is a lav. Action required - Make all needed corrections to the plumbing fixture table and plumbing layout. Mike Weisenborn July 22, 2011 - Per resubmittal.
Misc
Resolved
07/22/2011

The Plumbing General Notes and Misc. Plumbing Notes call specify different materials for the waste and vent piping. Action required - Make needed corrections. Mike Weisenborn July 22, 2011 - Per resubmittal.
Misc
Resolved
07/22/2011

The plumbing fixture schedule calls for a 10-gallon electric water heater and the mechanical plans indicate a much larger gas unit. Action required - Make needed corrections. Mike Weisenborn July 22, 2011 - Corrected
Misc
Resolved
07/22/2011

Mechanical unit F-1 is shown to be hung from the structure above. The plans do not indicate how it is to be attached or what it is to be hung from. Also, the plans do not provide any information indicating that the structure is capable of supporting the weight or what alterations to the structure are required. Action required - Provide additional information including information from a structural engineer indicating that either the structure is capable of supporting the weight or what alterations are required. Mike Weisenborn July 22, 2011 - Per resubmittal.
Screening - Ground mounted equipment
Resolved
07/22/2011

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required - Show how this requirement will be met. Obtain approval from Planning and Development. Mike Weisenborn July 22, 2011 - Per resubmittal.
Misc
Resolved
07/22/2011

Details for the protection of the penetrations of the rated assemblies has not been provided. Action required - Provide additional information. Mike Weisenborn July 22, 2011 - Per resubmittal.
Misc
Resolved
07/22/2011

Information on the materials to be used and how they are to be installed for the electrical work has not been provided. Action required - Provide additional information.
Accessibility - Maneuvering Clearance at Doors.
Resolved
07/22/2011

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space on the restroom side of the doors is not provided. Make needed corrections.
Misc
Corrective Action Required
07/15/2011

The plans do not indicate any alterations to the electrical or mechanical systems do to the alterations to the existing space. Action required - Make needed corrections. Mike Weisenborn July 22, 2011 - Additional information has not been provided. No work shall be performed in this area unless additional information is provided.
Misc
Resolved
07/22/2011

The floor plans on Sheet TF-2 shows a wall and door on the east end of the corridor. Action required - Make needed corrections.
Misc
Resolved
07/22/2011

The plans do not indicate how the ceiling over the corridor in the new space is to terminate. Protection to the roof deck will need to be provided. Action required - Provide additional information.
Misc
Resolved
07/22/2011

Framing details for the door door openings has not been provided. Action required - Provide additional information.
Bldg - Corridors - Construction
Resolved
07/22/2011

2006 IBC 1017.1 - Construction. Corridors shall be fire-resistance rated in accordance with Table 1017.1. The corridor walls required to be fire-resistance rated shall comply with Section 708 for fire partitions. Protection of the new corridor in the existing space is not indicated.
Fire Plan Review Approved 07/22/2011 07/25/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
07/15/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for sprinkler alterations.
Construction documents for fire alarm systems
Corrective Action Required
07/15/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for alarm system alterations.
Misc
Resolved
07/25/2011

703.2.1 Signs. Where required by the fire code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows: 1. For doors designed to be kept normally open: FIRE DOOR—DO NOT BLOCK. 2. For doors designed to be kept normally closed: FIRE DOOR—KEEP CLOSED. Action required: Provide signage or approved hold open devices (door release service). Plans show signage and mention release service. Provide plans (alarm) for release service.
Address numbers required
Resolved
07/25/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: The new spaces of the church shall have the same number of the existing church. Verified at inspection.
Misc
Corrective Action Required
07/15/2011

Indicate the occupant load of each of the news spaces created based on use and IFC Table 1004.1.1. 07/25/2011- Provide information.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
07/15/2011

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action required: The existing sprinkler system shall have documentaion of a current annual inspection.
Misc
Resolved
07/25/2011

Will the existing sprinkler system in the church be extended into the new area of the church? No.
Portable fire extinguishers - general
Resolved
07/25/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide fire extinguishers in conspicuous locations. Verified at inspection.
Fire protection equipment identification
Corrective Action Required
07/15/2011

2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Verified at inspection.
Fire-resistant-rated construction - Maintenance
Corrective Action Required
07/15/2011

2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Internal Plan Review (Res) Rejected 06/28/2011 06/29/2011
Mike Weisenborn
Fire Plan Review Rejected 06/28/2011 06/28/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
06/28/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for sprinkler alterations.
Construction documents for fire alarm systems
Corrective Action Required
06/28/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for alarm system alterations.
Misc
Corrective Action Required
06/28/2011

703.2.1 Signs. Where required by the fire code official, a sign shall be permanently displayed on or near each fire door in letters not less than 1 inch (25 mm) high to read as follows: 1. For doors designed to be kept normally open: FIRE DOOR—DO NOT BLOCK. 2. For doors designed to be kept normally closed: FIRE DOOR—KEEP CLOSED. Action required: Provide signage or approved hold open devices (door release service).
Address numbers required
Resolved
07/25/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: The new spaces of the church shall have the same number of the existing church. Verified at inspection.
Misc
Corrective Action Required
06/28/2011

Indicate the occupant load of each of the news spaces created based on use and IFC Table 1004.1.1. 07/25/2011- Use and occupant loads are still needed for assembly rooms.
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
06/28/2011

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. Action required: The existing sprinkler system shall have documentaion of a current annual inspection.
Misc
Resolved
07/25/2011

Will the existing sprinkler system in the church be extended into the new area of the church?
Portable fire extinguishers - general
Resolved
07/25/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide fire extinguishers in conspicuous locations. Verified at inspection.
Fire protection equipment identification
Resolved
07/25/2011

2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Verified at inspection.
Fire-resistant-rated construction - Maintenance
Corrective Action Required
06/28/2011

2006 IFC 703.1- Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly.
Building Plan Review Rejected 06/28/2011 06/28/2011
Mike Weisenborn
Bldg - Occupant load calculations - Areas without fixed seats
Corrective Action Required
06/27/2011

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - Provide the occupant load calculations for each of the rooms/spaces. We will be looking at the highest possible occupant load of each space.
Bldg - Posting of occupant load
Corrective Action Required
06/27/2011

2006 IBC 1004.3 - Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required - This will be verified on inspection.
Misc
Corrective Action Required
06/27/2011

The construction type indicate is Type V-B but the original building and subsiquent permits list the contruction type as Type II-B. Action required - Make needed corrections to the stated construction type and details for the stair and landing and corridor ceiling.
Misc
Corrective Action Required
06/27/2011

No detail is provided for the handrails being installed. Action required - Provide additional information. Provide specific information on the height, graspability, extensions and installation.
Misc
Corrective Action Required
06/27/2011

The plans indicate that a chair lift is to be installed but information on the lift being installed has not provided. Action required - Provide specifications from the manufacture on the lift to be installed.
Bldg - Accessibility - Drinking fountains minimum number
Corrective Action Required
06/27/2011

2006 IBC 1109.5.1 - Minimum number. No fewer than two drinking fountains shall be provided. One drinking fountain shall comply with the requirements for people who use a wheelchair and one drinking fountain shall comply with the requirements for standing persons. Action required - This code section does not allow for the installation of a single drinking fountain unless it meets both height requirements. Make needed corrections.
Misc
Corrective Action Required
06/27/2011

The floor plan on sheet TF-2 does not provide the proposed uses of the newly spaces created by the new corridor. Action required - Provide additional information on the plans.
Misc
Corrective Action Required
06/27/2011

Sheet TF-2 shows three different wall types but the floor plans do not clearly indicate which wall type each wall is. Action required - Provide additional information on the plans.
Misc
Corrective Action Required
06/27/2011

The door schedule does not indicate the specific hardware to be installed on each of the doors. Action required - Provide additional information.
Misc
Corrective Action Required
06/27/2011

The plumbing fixture schedule has fixtures on it that are not a part of it and the plumbing layout is mislabled. It indicates that a water closet is to be installed next to F-1 and that the drinking fountain is a lav. Action required - Make all needed corrections to the plumbing fixture table and plumbing layout.
Misc
Corrective Action Required
06/27/2011

The Plumbing General Notes and Misc. Plumbing Notes call specify different materials for the waste and vent piping. Action required - Make needed corrections.
Misc
Corrective Action Required
06/27/2011

The plumbing fixture schedule calls for a 10-gallon electric water heater and the mechanical plans indicate a much larger gas unit. Action required - Make needed corrections.
Misc
Corrective Action Required
06/27/2011

Mechanical unit F-1 is shown to be hung from the structure above. The plans do not indicate how it is to be attached or what it is to be hung from. Also, the plans do not provide any information indicating that the structure is capable of supporting the weight or what alterations to the structure are required. Action required - Provide additional information including information from a structural engineer indicating that either the structure is capable of supporting the weight or what alterations are required.
Screening - Ground mounted equipment
Corrective Action Required
06/27/2011

Planning and Development - Ground mounted equipment - Ground mounted equipment shall be totally screened from view by landscaping or masonry wall up to a height of the units to be screened. Action required - Show how this requirement will be met. Obtain approval from Planning and Development.
Misc
Corrective Action Required
06/27/2011

Details for the protection of the penetrations of the rated assemblies has not been provided. Action required - Provide additional information.
Misc
Corrective Action Required
06/27/2011

Information on the materials to be used and how they are to be installed for the electrical work has not been provided. Action required - Provide additional information.
Accessibility - Maneuvering Clearance at Doors.
Corrective Action Required
06/27/2011

ICC/ANSI A117.1 2003 404.2.3 - Maneuvering Clearance at Doors. Minimum maneuvering clearances at doors shall comply with Section 404.2.3 and shall include the full clear opening width of the doorway. Action required - The required clear space on the restroom side of the doors is not provided. Make needed corrections.
Misc
Corrective Action Required
06/27/2011

The plans do not indicate any alterations to the electrical or mechanical systems do to the alterations to the existing space. Action required - Make needed corrections.
Misc
Corrective Action Required
06/27/2011

The floor plans on Sheet TF-2 shows a wall and door on the east end of the corridor. Action required - Make needed corrections.
Misc
Corrective Action Required
06/27/2011

The plans do not indicate how the ceiling over the corridor in the new space is to terminate. Protection to the roof deck will need to be provided. Action required - Provide additional information.
Misc
Corrective Action Required
06/27/2011

Framing details for the door door openings has not been provided. Action required - Provide additional information.
Bldg - Corridors - Construction
Corrective Action Required
06/27/2011

2006 IBC 1017.1 - Construction. Corridors shall be fire-resistance rated in accordance with Table 1017.1. The corridor walls required to be fire-resistance rated shall comply with Section 708 for fire partitions. Protection of the new corridor in the existing space is not indicated.
License Tax Codes Approved 06/28/2011 06/27/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $163.40 $163.40 Paid 07/25/2011
8331507-Sewer Connection Fee $240.00 $240.00 Paid 07/25/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Passed 8/2/2011 9/21/2011 at 12:00 AM 08/02/2011
Electrical Service Inspection Passed 8/30/2011 at 12:00 AM 08/30/2011
All Rough Inspection - Commercial Failed 09/01/2011
Misc
Corrective Action Required
08/31/2011
1. SECURE AND SUPPORT MC IN WALL AND WITHIN12' OF BOXES. 2. SECURE MC AT BOX . 3. SUPPORT AND ABOVE CEILING
M303 EQUIPMENT AND APPLIANCE LOCATION
Corrective Action Required
09/01/2011
INSTALL DAMPERS AS SHOW ON PLANS
M305 PIPING SUPPORT
Corrective Action Required
09/01/2011
SUPPORT AND SECURE PLUMBING IN WALL. INSTALL PROTECTION PLATES PER CODE SUPPORT PEX PER CODE, ABOVE CEIING AND IN WALL
Misc
Corrective Action Required
09/01/2011
1. FIRE WALL- NO INSPECTION ON SCREW PATTERN ON SHEETROCK- RE-SCREW WALL FOR INSPECTION PENETRATIONS IN WALL REAR CORRIDOR ABOCE CEILING REPAIR PER CODE. DO NOT MUD AND TAPE REVISE PLANS FOR CHANGE IN CEILING SCHEDULE NO ROCK COVERING I BEAM GIRTER OVER CEILING IN 1HR WALL. NEUTRAL AT SOUTH SUB PANEL LOOSE.
All Rough Inspection - Commercial Partial 9/6/2011 9/6/2011 at 12:00 AM 09/06/2011
Misc
Resolved
09/06/2011
1. SECURE AND SUPPORT MC IN WALL AND WITHIN12' OF BOXES. 2. SECURE MC AT BOX . 3. SUPPORT AND ABOVE CEILING
M303 EQUIPMENT AND APPLIANCE LOCATION
Partial Correction
09/06/2011
DAMPERS AS SHOW ON PLANS SUBJECT TO APPROVAL AT ABOVE-CEILING INSPECTION
M305 PIPING SUPPORT
Partial Correction
09/06/2011
INSTALLATION OF PLUMBING PROTECTION PLATES IN PROGRESS
Misc
Resolved
09/06/2011
1. FIRE WALL- NO INSPECTION ON SCREW PATTERN ON SHEETROCK- RE-SCREW WALL FOR INSPECTION PENETRATIONS IN WALL REAR CORRIDOR ABOCE CEILING REPAIR PER CODE. DO NOT MUD AND TAPE REVISE PLANS FOR CHANGE IN CEILING SCHEDULE NO ROCK COVERING I BEAM GIRTER OVER CEILING IN 1HR WALL. NEUTRAL AT SOUTH SUB PANEL LOOSE.
Misc
Partial Correction
09/06/2011
AFTER MISSING BOCA PLATES ARE IN PLACE AT PVC PIPING AND GWB GAP AT ONE ROOF PURLIN IS CLOSED OK TO HANG GWB AT WALLS AND AT TUNNEL CORRIDOR CEILING. DO NOT TAPE/MUD RATED WALL/CEILING SURFACES PRIOR TO RATED ASSEMBLY INSPECTION & APPROVAL.
Rated Assembly Inspection Failed 9/12/2011 at 12:00 AM 09/12/2011
Misc
Corrective Action Required
09/12/2011
1. REVISE PLANS TO SHOW CHANGE IN RATED WALL/CEILING IN CORRIDOR. 2. PENETRATIONS IN WALL SHALL BE SEALED BY APPROVED METHOD. 3. 2 LAYERS INSTALLED ON CEILING IN MAIN CORRIDOR, HALL TO THE NORTH ONLY 1 LAYER INSTALLED ON CEILING. 4. 10 CANLIGHTS INSTALLED IN MAIN CORRIDOR CEILING, PROVIDE APPROVED METHOD OF OPENING/PENETRATION.
All Rough Inspection - Commercial Failed 09/20/2011
Misc
Resolved
09/20/2011
2 front doors locked- 2 rear doors locked cell number left on VM did not work. reschedule inspection when access is provided.
Misc
Corrective Action Required
09/20/2011
1. STAIR WALLS - APPROVED TO COVER EAST STAIR WALL, WEST WALL LEAVE WALL OPEN TO SEE ELECTRICAL BEHIND 2HR WALL. (ELECTRICAL NEED TERMINATED TO BOX)
Rated Assembly Inspection Failed 9/20/2011 at 12:00 AM 09/20/2011
Misc
Corrective Action Required
09/12/2011
1. REVISE PLANS TO SHOW CHANGE IN RATED WALL/CEILING IN CORRIDOR. 2. PENETRATIONS IN WALL SHALL BE SEALED BY APPROVED METHOD. 3. 2 LAYERS INSTALLED ON CEILING IN MAIN CORRIDOR, HALL TO THE NORTH ONLY 1 LAYER INSTALLED ON CEILING. 4. 10 CANLIGHTS INSTALLED IN MAIN CORRIDOR CEILING, PROVIDE APPROVED METHOD OF OPENING/PENETRATION.
Misc
Corrective Action Required
09/20/2011
REPAIR HOLES IN SOUTH CISE OF 1 HER WALL ABOVE CEILING HEIGHT. SEE PLAN SECTION FOR REPAIR, SEAL ALL PENETRATIONS PER CODE
Rated Assembly Inspection Partial 09/22/2011
Misc
Resolved
09/22/2011
Misc
Resolved
09/22/2011
Misc
Corrective Action Required
09/22/2011
INSPECTION REQUIRED FOR 2HR WALL OPENING AT STAIRS- CHECK DOORS AND SEAL WHEN INSTALLED
All Rough Inspection - Commercial Failed 9/22/2011 at 12:00 AM 09/22/2011
M303 EQUIPMENT AND APPLIANCE LOCATION
Partial Correction
09/06/2011
DAMPERS AS SHOW ON PLANS SUBJECT TO APPROVAL AT ABOVE-CEILING INSPECTION
M305 PIPING SUPPORT
Partial Correction
09/06/2011
INSTALLATION OF PLUMBING PROTECTION PLATES IN PROGRESS
Misc
Partial Correction
09/06/2011
AFTER MISSING BOCA PLATES ARE IN PLACE AT PVC PIPING AND GWB GAP AT ONE ROOF PURLIN IS CLOSED OK TO HANG GWB AT WALLS. DO NOT TAPE/MUD RATED WALLS PRIOR TO RATED ASSEMBLY INSPECTION & APPROVAL.
Misc
Corrective Action Required
09/22/2011
IN ADDITION TO ABOVE CEILING INSPECTION: 1. BATH FANS NOT VENTED 2. GAS LINE NOT INSTALLED, PROVIDE SIZING OF GAS LINE. 3. GAS PRESSURE TEST REQUIRED 4. PAINTING OF GAS LINE WHEN COMPLETE 5. SUPPORT ALL PLUMBING ABOVE CEILING PER CODE, PEX WATER PIPING AND DWV. 6. SUPPORT OF MC CABLE AND SECURE WITHIN 12" OF BOX OR FIXTURE. 7. INSPECTION OF DOORS AND STAIR FRAMING AT 2HR OPENING. 8. ROOF TOP INSPECTION. PROVIDE APPROVED LADDER FOR INSPECTION. 9. DO NOT INSTALL ANY CEILING TILES BEFORE ABOVE CEILING INSPECTION. 10. FIRE DAMPERS NOT INSTALLED 11. RETURN DUCTS NOT INSTALLED THIS IS AN UPDATED LIST ON 9-22-11 NO ABOVE CEILING INSPECTION HAS BEEN PREFORMED OR ROOF TOP INSPECTION. THIS LIST IS TO UPDATE GC. OF CURRENT ISSUES ON THE JOB , NOT A COMPLETE LIST OR COMPLETE INSPECTION. 9.
Above Ceiling Inspection Not Ready 9/28/2011 9/28/2011 at 12:00 AM 09/28/2011
All Rough Inspection - Commercial Not Ready 9/29/2011 9/29/2011 at 12:00 AM 09/29/2011
M303 EQUIPMENT AND APPLIANCE LOCATION
Partial Correction
09/22/2011
DAMPERS AS SHOW ON PLANS SUBJECT TO APPROVAL AT ABOVE-CEILING INSPECTION
M305 PIPING SUPPORT
Partial Correction
09/22/2011
INSTALLATION OF PLUMBING PROTECTION PLATES IN PROGRESS
Misc
Partial Correction
09/22/2011
AFTER MISSING BOCA PLATES ARE IN PLACE AT PVC PIPING AND GWB GAP AT ONE ROOF PURLIN IS CLOSED OK TO HANG GWB AT WALLS. DO NOT TAPE/MUD RATED WALLS PRIOR TO RATED ASSEMBLY INSPECTION & APPROVAL.
Misc
Corrective Action Required
09/22/2011
IN ADDITION TO ABOVE CEILING INSPECTION: 1. BATH FANS NOT VENTED 2. GAS LINE NOT INSTALLED, PROVIDE SIZING OF GAS LINE. 3. GAS PRESSURE TEST REQUIRED 4. PAINTING OF GAS LINE WHEN COMPLETE 5. SUPPORT ALL PLUMBING ABOVE CEILING PER CODE, PEX WATER PIPING AND DWV. 6. SUPPORT OF MC CABLE AND SECURE WITHIN 12" OF BOX OR FIXTURE. 7. INSPECTION OF DOORS AND STAIR FRAMING AT 2HR OPENING. 8. ROOF TOP INSPECTION. PROVIDE APPROVED LADDER FOR INSPECTION. 9. DO NOT INSTALL ANY CEILING TILES BEFORE ABOVE CEILING INSPECTION. 10. FIRE DAMPERS NOT INSTALLED 11. RETURN DUCTS NOT INSTALLED THIS IS AN UPDATED LIST ON 9-22-11 NO ABOVE CEILING INSPECTION HAS BEEN PREFORMED OR ROOF TOP INSPECTION. THIS LIST IS TO UPDATE GC. OF CURRENT ISSUES ON THE JOB , NOT A COMPLETE LIST OR COMPLETE INSPECTION. 9.
Above Ceiling Inspection Not Ready 9/29/2011 9/29/2011 at 12:00 AM 09/29/2011
Miscellaneous Inspection Not Ready 9/29/2011 9/29/2011 at 12:00 AM 09/29/2011
All Rough Inspection - Commercial Passed 09/30/2011
M303 EQUIPMENT AND APPLIANCE LOCATION
Resolved
09/30/2011
DAMPERS AS SHOW ON PLANS SUBJECT TO APPROVAL AT ABOVE-CEILING INSPECTION
M305 PIPING SUPPORT
Resolved
09/30/2011
INSTALLATION OF PLUMBING PROTECTION PLATES IN PROGRESS
Misc
Resolved
09/30/2011
AFTER MISSING BOCA PLATES ARE IN PLACE AT PVC PIPING AND GWB GAP AT ONE ROOF PURLIN IS CLOSED OK TO HANG GWB AT WALLS. DO NOT TAPE/MUD RATED WALLS PRIOR TO RATED ASSEMBLY INSPECTION & APPROVAL.
Misc
Resolved
09/30/2011
Above Ceiling Inspection Failed 9/30/2011 9/30/2011 at 12:00 AM 09/30/2011
Misc
Corrective Action Required
09/30/2011
ELECTRICAL EQUIPMENT CONTAMINATION, OPEN CEILING SPRAYED ELECTRICAL EQUIPMENT WITH PAINT. REPLACE J-BOXES AND RECEPTICLES
Misc
Corrective Action Required
09/30/2011
FLEX DUCT SUPPORT, 2" WIDE STRAPS REQUIRED TO BE SUPPORTED TO THE STRUCTURE EVERY 5 FEET OR PER MANUFACTURER'S INSTRUCTIONS.
Misc
Corrective Action Required
09/30/2011
PROVIDE MANUFACTURER'S INSTALLATION INSTUCTIONS FOR TWO FURNACE UNITS. ATTACH CONDENSATE DRAIN.
Misc
Corrective Action Required
09/30/2011
SUPPORT J BOX OVER ACCESSABLE ENTRANCE AT 2 HOUR WALL. PROVIDE FACEPLATE IN THE SAME HALLWAY OPPOSITE END.
Misc
Corrective Action Required
09/30/2011
Misc
Corrective Action Required
09/30/2011
LABEL FIRE DAMPER ABOVE CEILING
Misc
Corrective Action Required
09/30/2011
GAS PIPE TO ABOVE CEILING FURNACE IS UNDER SIZED. REQUIRED TO ME A MINIMUM OF 1" OKAY TO DROP BORDERS TILE ONLY.
Above Ceiling Inspection Failed 10/4/2011 at 12:00 AM 10/04/2011
Misc
Resolved
10/04/2011
ELECTRICAL EQUIPMENT CONTAMINATION, OPEN CEILING SPRAYED ELECTRICAL EQUIPMENT WITH PAINT. REPLACE J-BOXES AND RECEPTICLES
Misc
Resolved
10/04/2011
FLEX DUCT SUPPORT, 2" WIDE STRAPS REQUIRED TO BE SUPPORTED TO THE STRUCTURE EVERY 5 FEET OR PER MANUFACTURER'S INSTRUCTIONS.
Misc
Carried Forward
10/04/2011
ATTACH CONDENSATE DRAIN. LOCATION IN QUESTION
Misc
Resolved
10/04/2011
SUPPORT J BOX OVER ACCESSABLE ENTRANCE AT 2 HOUR WALL. PROVIDE FACEPLATE IN THE SAME HALLWAY OPPOSITE END.
Misc
Corrective Action Required
09/30/2011
SUPPORT MC OVER STAIRS, SUPPORT MC IN ROOMS ABOVE CEILING PER CODE. CHECK THROUGHOUT
Misc
Corrective Action Required
09/30/2011
LABEL FIRE DAMPER ABOVE CEILING
Misc
Corrective Action Required
09/30/2011
GAS PIPE TO ABOVE CEILING FURNACE IS UNDER SIZED. REQUIRED TO ME A MINIMUM OF 1" OKAY TO DROP BORDERS TILE ONLY.
Above Ceiling Inspection Failed 10/6/2011 at 12:00 AM 10/06/2011
Misc
Corrective Action Required
10/04/2011
SUPPORT MC OVER STAIRS, SUPPORT MC IN ROOMS ABOVE CEILING PER CODE. CHECK THROUGHOUT 2 LOCATIONS IN OFFICE ROOMS. DO NOT COVER UNTILL FIRE PENETRATIONS ARE INSPECTED AND APPROVED
Misc
Corrective Action Required
10/04/2011
LABEL FIRE DAMPER ABOVE CEILING
Misc
Corrective Action Required
10/04/2011
Above Ceiling Inspection Failed 10/11/2011 10/11/2011 at 12:00 AM 10/12/2011
Misc
Corrective Action Required
10/06/2011
SUPPORT MC OVER STAIRS, AT 2HR WALL ABOVE DOOR OPENING SOUTH SIDE. APPROVED TO COVER SOUTHEAST ROOM. DO NOT COVER SOUTH WEST ROOM / PENDING GAS LINE APPROVAL AND FIRE PENETRATION. DO NOT COVER UNTILL FIRE PENETRATIONS ARE INSPECTED AND APPROVED. RETURN AIR SHOWN ON PLANS TO ENTRY ROOM
Misc
Resolved
10/11/2011
LABEL FIRE DAMPER ABOVE CEILING
Misc
Resolved
10/11/2011
Final Inspection - Commercial Failed 10/14/2011
Misc
Corrective Action Required
10/06/2011
1. INSTALL GRAB BARS IN RESTROOMS PER CODE 11. PROVIDE ROOF ACCESS FOR INSPECTION. 16. PAINT ROOFTOP GAS PIPING RPOVIDE GAS TEST AFTER VALVE INSTALLED UP STREAM OF UNION ABOVE CEILING AT SOUTH WEST ROOM. SCHEDULE GAS PIPING INSPECTION, SCHEDULE FINAL OCCUPANCY INSPECTION
Above Ceiling Inspection Failed 10/14/2011 10/14/2011 at 12:00 AM 10/14/2011
Misc
Corrective Action Required
10/11/2011
DO NOT COVER SOUTH WEST ROOM / PENDING GAS LINE APPROVAL AND FIRE PENETRATION.
Gas Service Inspection - Commercial Passed 10/19/2011 at 12:00 AM 10/19/2011
Rated Assembly Inspection Passed 10/19/2011
Misc
Resolved
10/19/2011
INSPECTION REQUIRED FOR 2HR WALL OPENING AT STAIRS- CHECK DOORS AND SEAL WHEN INSTALLED
Above Ceiling Inspection Passed 10/19/2011
Misc
Resolved
10/19/2011
DO NOT COVER SOUTH WEST ROOM / PENDING GAS LINE APPROVAL AND FIRE PENETRATION.
Occupancy Inspection - Codes Commercial Failed 10/19/2011 10/19/2011 at 12:00 AM 10/19/2011
Misc
Corrective Action Required
10/19/2011
1. INSTAL SIDE GRAB BAR AT MAX 12" FROM REAR WALL. 2. INSTALL LOAD SIGNS AS PER F.D. 3. INSTAL WHEEL CHAIR LIFT- BLOCK OPENING FROM FLOOR TO 42". FOR TCO. 4. LABEL MAIN GAS METER (1499) 5. EXIT SIGNS AS PER F.D. LOCATION. OK FOR TCO WHEN #1,3 ARE COMPLETE.
Occupancy Inspection - Fire Temporary C of O 10/19/2011 at 12:00 AM 10/19/2011
Misc
Corrective Action Required
10/19/2011
(1) post occupant load of 152 in multi-purpose room (2) install additonal exit signage for the rear door leading to hallway from the multi-purpose room and in the main corridor off of the restrooms behind the multi-purpose room. (3) label the FDC to indicate sprinkler system services 1499 only.
Alarm Test Passed 10/19/2011 at 12:00 AM 10/19/2011
Occupancy Inspection - Fire Passed 10/20/2011
Misc
Corrective Action Required
10/19/2011
(1) post occupant load of 152 in multi-purpose room (2) install additonal exit signage for the rear door leading to hallway from the multi-purpose room and in the main corridor off of the restrooms behind the multi-purpose room. (3) label the FDC to indicate sprinkler system services 1499 only.
Misc
Corrective Action Required
10/20/2011
10/20/11: ALL PREVIOUS VIOLATIONS HAVE BEEN CORRECTED
Occupancy Inspection - Codes Commercial Temporary C of O 10/21/2011 10/21/2011 at 12:00 AM 10/21/2011
Misc
Corrective Action Required
10/19/2011
PROVIDE STATE INSPECTION ON WHEEL CHAIR LIFT WHEN INSTALLED. TCO APPROVED TO 11-15-11
Occupancy Inspection - Codes Commercial Full C of O 01/26/2012
Misc
Resolved
01/26/2012
PROVIDE STATE INSPECTION ON WHEEL CHAIR LIFT WHEN INSTALLED. TCO APPROVED TO 11-15-11
Documents & Images
Date Uploaded File Type Document Name
06/29/2011 Letter Plan Review Conditions
07/25/2011 Letter Building Permit
07/25/2011 Letter Plan Review Conditions
08/02/2011 Letter Inspection Summary
08/30/2011 Letter Inspection Summary
08/31/2011 Letter Inspection Summary
09/01/2011 Letter Inspection Summary
09/06/2011 Letter Inspection Summary
09/12/2011 Letter Inspection Summary
09/20/2011 Letter Inspection Summary
09/22/2011 Letter Inspection Summary
09/28/2011 Letter Inspection Summary
09/30/2011 Letter Inspection Summary
10/04/2011 Letter Inspection Summary
10/06/2011 Letter Inspection Summary
10/06/2011 Letter Inspection Summary
10/06/2011 Letter Inspection Summary
10/12/2011 Letter Inspection Summary
10/14/2011 Letter Inspection Summary
10/19/2011 Letter Inspection Summary
10/19/2011 Letter Fire Loss Reduction Form
10/20/2011 Letter Fire Loss Reduction Form
10/21/2011 Letter Temporary Certificate of Occupancy
11/30/2011 Activity Document 20111130101751253.pdf
11/30/2011 Activity Document 20111130101801218.pdf
12/27/2011 Letter 10-Day Notice of Violation
12/29/2011 Receipt Certified Receipt
01/26/2012 Letter Field Certificate of Occupancy
01/27/2012 Letter Final Certificate of Occupancy
01/27/2012 Letter 20120127090945219.pdf
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire (Alarm) Plan Review Notice
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home