Permit Application Status

PRCOM20111755


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20111755
Building Permit - Commercial
Certificate of Occupancy
CP DEER BROOK PLAZA LLC
CHANGE OF TENANT
TENANT FINISH FOR NEW RETAIL BEAUTY SUPPLY
05/17/2011
06/14/2011
11/23/2011
06/28/2011
Locations
Contacts
CP DEER BROOK PLAZA LLC, Address:3400 COLLEGE BLVD STE 195  
CMG CONSTRUCTION , Address:8336 NIEMAN RD, Phone:(913) 384-2284  
SECO INC, Address:7007 COLLEGE BLVD STE 265, Phone:(913) 428-3550  
AIR CARE HEATING & COOLING, Address:10332 W 79TH ST, Phone:(913) 362-5274  
R S PLUMBING, Address:1200 S MARKET ST, Phone:(816) 732-6897  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 06/14/2011
Mike Weisenborn
Fire Plan Review Approved 05/27/2011 06/14/2011
Jim Eden
Address numbers required
Corrective Action Required
06/14/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: The front and rear door shall be posted with the address. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
06/14/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Verified at inspection. Provide a minimum 2A:10B:C fire extinguisher.
Misc
Corrective Action Required
06/14/2011

1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Exceptions: 1. Exit signs are not required in rooms or areas that require only one exit or exit access. 2. Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the fire code official. 3. Exit signs are not required in occupancies in Group U and individual sleeping units or dwelling units in Group R-1, R-2 or R-3. 4. Exit signs are not required in sleeping areas in occupancies in Group I-3. 5. In occupancies in Groups A-4 and A-5, exit signs are not required on the seating side of vomitories or openings into seating areas where exit signs are provided in the concourse that are readily apparent from the vomitories. Egress lighting is provided to identify each vomitory or opening within the seating area in an emergency. Action required: Provide exit lights over the front door and door 100. The exit over the rear door to remain. Verified at inspection.
Misc
Corrective Action Required
06/14/2011

Misc
Corrective Action Required
06/14/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required: Provide emergency lighting. verified at inspection.
Misc
Corrective Action Required
06/14/2011

Mike with CMG construction called to discuss existing conditions and item from first review.
Internal Plan Review (Res) Rejected 05/27/2011 05/27/2011
Mike Weisenborn
Building Plan Review Approved 05/27/2011 05/27/2011
Mike Weisenborn
Misc
Corrective Action Required
05/27/2011

This permit does not include any plumbing, electrical or mechanical work as plans and specifications for such work have not been provided. Action required - This comment is for information purposes.
License Tax Codes Approved 05/27/2011 05/27/2011
Mike Weisenborn
Fire Plan Review Rejected 05/27/2011 05/18/2011
Jim Eden
Misc
Resolved
06/14/2011

1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Exceptions: 1. Private garages, office areas, factory and storage areas with an occupant load of 10 or less. 2. Group I-3 occupancies used as a place of detention. 3. Critical or intensive care patient rooms within suites of health care facilities. 4. Doors within or serving a single dwelling unit in Groups R-2 and R-3. 5. In other than Group H occupancies, revolving doors complying with Section 1008.1.3.1. 6. In other than Group H occupancies, horizontal sliding doors complying with Section 1008.1.3.3 are permitted in a means of egress. 7. Power-operated doors in accordance with Section 1008.1.3.2. 8. Doors serving a bathroom within an individual sleeping unit in Group R-1. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. Action required: The front door shall swing outward. Per Mike with CMG, the door swings outward.
Address numbers required
Corrective Action Required
05/18/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: The front and rear door shall be posted with the address. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
05/18/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Verified at inspection. Provide a minimum 2A:10B:C fire extinguisher.
Misc
Corrective Action Required
05/18/2011

1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Exceptions: 1. Exit signs are not required in rooms or areas that require only one exit or exit access. 2. Main exterior exit doors or gates that are obviously and clearly identifiable as exits need not have exit signs where approved by the fire code official. 3. Exit signs are not required in occupancies in Group U and individual sleeping units or dwelling units in Group R-1, R-2 or R-3. 4. Exit signs are not required in sleeping areas in occupancies in Group I-3. 5. In occupancies in Groups A-4 and A-5, exit signs are not required on the seating side of vomitories or openings into seating areas where exit signs are provided in the concourse that are readily apparent from the vomitories. Egress lighting is provided to identify each vomitory or opening within the seating area in an emergency. Action required: Provide exit lights over the front door and door 100. The exit over the rear door to remain. Verified at inspection.
Misc
Corrective Action Required
05/18/2011

Misc
Corrective Action Required
05/18/2011

1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. Action required: Provide emergency lighting. verified at inspection.
Construction documents - Fire protection systems
Resolved
06/14/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide Shop drawings for sprinkler system alteration. 6/14-Per the letter from Absolute Fire, work is limited to raising the heads only.
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $71.49 $71.49 Paid 06/14/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Above Ceiling Inspection Partial 6/20/2011 at 12:00 AM 06/20/2011
Misc
Corrective Action Required
06/20/2011
SUPPORT EMT CONDUIT NEAR MECHANICAL (MAX. SPAN WITHOUT SUPPORT IS 10 FT)
All Rough Inspection - Commercial Passed 6/20/2011 at 12:00 AM 06/20/2011
Above Ceiling Inspection Passed 6/22/2011 at 12:00 AM 06/22/2011
Misc
Resolved
06/22/2011
SUPPORT EMT CONDUIT NEAR MECHANICAL (MAX. SPAN WITHOUT SUPPORT IS 10 FT)
All Rough Inspection - Commercial Failed 6/22/2011 6/23/2011 at 12:00 AM 06/22/2011
Misc
Corrective Action Required
06/22/2011
PROTECT PLUMBING WITHIN 1.5" OF STUD SURFACE
All Rough Inspection - Commercial Passed 6/23/2011 at 12:00 AM 06/23/2011
Misc
Resolved
06/23/2011
PROTECT PLUMBING WITHIN 1.5" OF STUD SURFACE
Occupancy Inspection - Codes Commercial Full C of O 6/28/2011 at 12:00 AM 06/28/2011
Occupancy Inspection - Fire Passed 06/28/2011
Documents & Images
Date Uploaded File Type Document Name
05/27/2011 Letter Plan Review Conditions
06/14/2011 Letter Absolute Fire - Sally Alteration Letter.pdf
06/14/2011 Letter Building Permit
06/14/2011 Letter Plan Review Conditions
06/14/2011 Letter 20110614161048070.pdf
06/20/2011 Letter Inspection Summary
06/22/2011 Letter Inspection Summary
06/23/2011 Letter Inspection Summary
06/28/2011 Letter Field Certificate of Occupancy
06/28/2011 Letter Fire Loss Reduction Form
06/29/2011 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire Building Plan Review
06/21/2013 Letter Fire Building Plan Review
06/27/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home