Summary
PRCOM20110449
Building Permit - Commercial
Certificate of Occupancy
LEES SUMMIT 29197 L L C
CHANGE OF TENANT
CHANGE OF TENANT. SPACE WAS PREVIOUSLY USED AS A BUFFET
04/01/2011
05/17/2011
11/08/2011
10/03/2011
Locations
Contacts
LEES SUMMIT 29197 L L C, Address:605 W 47TH ST 100  
CORNERSTONE ARCHITECTS LLC, Address:8117 ROBERTS RD  
MONUMENT EXTERIOR DESIGNS INC, Address:3808 N 99TH ST, Phone:(816) 914-3917  
MONUMENT EXTERIOR DESIGNS INC, Address:3808 N 99TH ST, Phone:(816) 914-3917  
MONUMENT EXTERIOR DESIGNS INC, Address:3808 N 99TH ST, Phone:(816) 914-3917  
MONUMENT EXTERIOR DESIGNS INC, Address:3808 N 99TH ST, Phone:(816) 914-3917  
Reviews
Review Type Outcome Est. Completion Date Completed
Internal Plan Review (Res) Approved 05/16/2011
Mike Weisenborn
Building Plan Review Approved 05/17/2011 05/16/2011
Mike Weisenborn
Health Dept Inspection
Corrective Action Required
05/12/2011

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required - This comment is for information purposes.
Health Dept Review
Resolved
05/16/2011

For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required - Provide documentation of plan review approval from the Jackson County Health Department.
Bldg - Minimum number of exits
Corrective Action Required
05/12/2011

2006 IBC 1019.1 - Minimum number of exits. All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by Table 1019.1 based on the occupant load of the story, except as modified in Section 1015.1 or 1019.2. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrived at grade or the public way. Action required - As the occupant load of Dining Area "C" is greater than 50 two means of egress are required from the space. Make needed corrections. Mike Weisenborn May 05, 2011 - The occupant load of this space has been changed to 50. Signage to be verified on inspection.
Misc
Corrective Action Required
05/12/2011

The plans indicate that replacement of similar equipment and fixtures is the only work to be done in the kitchen area. This permit does not include any alterations to the plumbing, electrical or mechanical systems. Action required - If any alterations to the existing plumbing, electrical or mechanical systems are required for new equipment, plans for the alterations shall be provided for review and approval prior to performing the work. This comment is for information purposes.
Misc
Corrective Action Required
05/12/2011

All health and safety issues for backflow protection on the water system and indirect waste on the sanitary shall be maintained/installed as required by code. Action required - This will be verified on inspection.
License contractors
Corrective Action Required
05/12/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - The building permit must be issued to a general contractor with a minimum of a Class B license. All plumbing, electrical and mechanical work shall be performed by licensed contractors. This comment is for information purposes.
Project cost
Resolved
05/16/2011

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the project cost. Mike Weisenborn May 16, 2011 - The project cost has been provided.
Planning - Signs
Corrective Action Required
05/12/2011

Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirments. Action required - This comment is for information purposes.
Misc
Resolved
05/12/2011

On Friday April 29th Mike Copeland, Manager of Inspections, meet with the contractor and architect to discuss issues on the project in relation to kitchen equipement. Action required - Provide details on the plans of the required corrective action discussed durring the site visit. Mike Weisenborn May 12, 2011 - Provided information.
Internal Plan Review (Res) Rejected 05/12/2011
Mike Weisenborn
Internal Plan Review (Res) Rejected 05/05/2011
Mike Weisenborn
Building Plan Review Rejected 05/02/2011 05/05/2011
Mike Weisenborn
Health Dept Inspection
Corrective Action Required
04/26/2011

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required - This comment is for information purposes.
Health Dept Review
Corrective Action Required
04/26/2011

For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required - Provide documentation of plan review approval from the Jackson County Health Department.
Bldg - Minimum number of exits
Corrective Action Required
04/26/2011

2006 IBC 1019.1 - Minimum number of exits. All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by Table 1019.1 based on the occupant load of the story, except as modified in Section 1015.1 or 1019.2. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrived at grade or the public way. Action required - As the occupant load of Dining Area "C" is greater than 50 two means of egress are required from the space. Make needed corrections. Mike Weisenborn May 05, 2011 - The occupant load of this space has been changed to 50. Signage to be verified on inspection.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Resolved
05/05/2011

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met for the Cashier Station. Mike Weisenborn May 05, 2011 - Plans have been revised.
Misc
Resolved
05/05/2011

2006 IBC 1108.2.8.1 - Dining surfaces. Where dining surfaces for the consumption of food or drink are provided, at least 5 percent, but not less than one, of the seating and standing spaces at the dining surfaces shall be accessible and be distributed throughout the facility. Action required - Show how this requirement will be met. Mike Weisenborn May 05, 2011 - Information has been provided on the plans.
Plumb - Indirect waste for food handling fixtures
Resolved
05/05/2011

2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap. Action required - The new buffet tables shall be connected to the sanitary system by an indirect waste. Please add this to the note on the buffet tables on Sheet A2. Mike Weisenborn May 05, 2011 - Notes have been added to the plans.
Bldg - Exit signage - Where required
Resolved
05/05/2011

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - Exit signage is required in Dining Area "C" as two means of egress are required from the space. Exit signage shall be visable from the Buffet Area. If the new cased opening block the visibility of the exit signage at the doors, additional signage shall be added. Mike Weisenborn May 05, 2011 - The occupant load has been lowered so signage is not required.
Misc
Corrective Action Required
04/26/2011

The plans indicate that replacement of similar equipment and fixtures is the only work to be done in the kitchen area. This permit does not include any alterations to the plumbing, electrical or mechanical systems. Action required - If any alterations to the existing plumbing, electrical or mechanical systems are required for new equipment, plans for the alterations shall be provided for review and approval prior to performing the work. This comment is for information purposes.
Misc
Corrective Action Required
04/26/2011

All health and safety issues for backflow protection on the water system and indirect waste on the sanitary shall be maintained/installed as required by code. Action required - This will be verified on inspection.
License contractors
Corrective Action Required
04/26/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - The building permit must be issued to a general contractor with a minimum of a Class B license. All plumbing, electrical and mechanical work shall be performed by licensed contractors. This comment is for information purposes.
Project cost
Corrective Action Required
04/26/2011

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the project cost.
Planning - Signs
Corrective Action Required
04/26/2011

Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirments.
Misc
Corrective Action Required
05/05/2011

On Friday April 29th Mike Copeland, Manager of Inspections, meet with the contractor and architect to discuss issues on the project in relation to kitchen equipement. Action required - Provide details on the plans of the required corrective action discussed durring the site visit.
Fire Plan Review Approved 05/02/2011 05/02/2011
Brian Austerman
Misc
Corrective Action Required
04/26/2011

015.1 Exit or exit access doorways required. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: 1. The occupant load of the space exceeds the values in Table 1015.1. 2. The common path of egress travel exceeds the limitations of Section 1014.3. 3. Where required by Sections 1015.3, 1015.4 and 1015.5. Exception: Group I-2 occupancies shall comply with Section 1014.2.2. Action required: The occupant load of Dining Room C shall not exceed 49. Reduce the number of seating spaces in the room. RESUB SHOWS 50, NEEDS TO BE 49. VERIFIED AT INSPECTION
Posting of occupant load
Corrective Action Required
04/26/2011

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Rooms shall be posted along with the the posting of the total occupancy at the front door. Verified at inspection.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
04/26/2011

2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action required: The K class extinguisher shall be located at the manual pull station for the hood system with instructions for operation in english and the predominant language.
Misc
Corrective Action Required
04/26/2011

904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. 904.11.6.1 Ventilation system. The ventilation system in connection with hoods shall be operated at the required rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used. 904.11.6.2 Grease extractors. Where grease extractors are installed, they shall be operated when the commercial-type cooking equipment is used. 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. 904.11.6.5 Fusible link and sprinkler head replacement. Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer’s instructions. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
04/26/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of 3 , 2A:10B:C fire extinguishers. Verified at inspection.
Installation acceptance testing
Corrective Action Required
04/26/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: The Fire Department shall witness a test of the hood system.
License Tax Codes Approved 04/13/2011 04/13/2011
Mike Weisenborn
Internal Plan Review (Res) Rejected 04/13/2011 04/12/2011
Mike Weisenborn
Building Plan Review Rejected 04/13/2011 04/12/2011
Mike Weisenborn
Health Dept Inspection
Corrective Action Required
04/12/2011

For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit. Action required - This comment is for information purposes.
Health Dept Review
Corrective Action Required
04/12/2011

For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit. Action required - Provide documentation of plan review approval from the Jackson County Health Department.
Bldg - Minimum number of exits
Corrective Action Required
04/12/2011

2006 IBC 1019.1 - Minimum number of exits. All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by Table 1019.1 based on the occupant load of the story, except as modified in Section 1015.1 or 1019.2. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrived at grade or the public way. Action required - As the occupant load of Dining Area "C" is greater than 50 two means of egress are required from the space. Make needed corrections.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
04/12/2011

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Show how this requirement will be met for the Cashier Station.
Misc
Corrective Action Required
04/12/2011

2006 IBC 1108.2.8.1 - Dining surfaces. Where dining surfaces for the consumption of food or drink are provided, at least 5 percent, but not less than one, of the seating and standing spaces at the dining surfaces shall be accessible and be distributed throughout the facility. Action required - Show how this requirement will be met.
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
04/12/2011

2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap. Action required - The new buffet tables shall be connected to the sanitary system by an indirect waste. Please add this to the note on the buffet tables on Sheet A2.
Bldg - Exit signage - Where required
Corrective Action Required
04/12/2011

2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign. Action required - Exit signage is required in Dining Area "C" as two means of egress are required from the space. Exit signage shall be visable from the Buffet Area. If the new cased opening block the visibility of the exit signage at the doors, additional signage shall be added.
Misc
Corrective Action Required
04/12/2011

The plans indicate that replacement of similar equipment and fixtures is the only work to be done in the kitchen area. This permit does not include any alterations to the plumbing, electrical or mechanical systems. Action required - If any alterations to the existing plumbing, electrical or mechanical systems are required for new equipment, plans for the alterations shall be provided for review and approval prior to performing the work. This comment is for information purposes.
Misc
Corrective Action Required
04/12/2011

All health and safety issues for backflow protection on the water system and indirect waste on the sanitary shall be maintained/installed as required by code. Action required - This will be verified on inspection.
License contractors
Corrective Action Required
04/12/2011

No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances. Action required - The building permit must be issued to a general contractor with a minimum of a Class B license. All plumbing, electrical and mechanical work shall be performed by licensed contractors. This comment is for information purposes.
Project cost
Corrective Action Required
04/12/2011

The project cost, which is used to establish the permit fee, has not been provided. Action required - Provide the project cost.
Planning - Signs
Corrective Action Required
04/12/2011

Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirments.
Fire Plan Review Rejected 04/13/2011 04/11/2011
Jim Eden
Misc
Corrective Action Required
04/08/2011

015.1 Exit or exit access doorways required. Two exits or exit access doorways from any space shall be provided where one of the following conditions exists: 1. The occupant load of the space exceeds the values in Table 1015.1. 2. The common path of egress travel exceeds the limitations of Section 1014.3. 3. Where required by Sections 1015.3, 1015.4 and 1015.5. Exception: Group I-2 occupancies shall comply with Section 1014.2.2. Action required: The occupant load of Dining Room C shall not exceed 49. Reduce the number of seating spaces in the room.
Posting of occupant load
Corrective Action Required
04/08/2011

2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Action required: Rooms shall be posted along with the the posting of the total occupancy at the front door. Verified at inspection.
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
04/08/2011

2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. Action required: The K class extinguisher shall be located at the manual pull station for the hood system with instructions for operation in english and the predominant language.
Misc
Corrective Action Required
04/08/2011

904.11.6 Operations and maintenance. Commercial cooking systems shall be operated and maintained in accordance with this section. 904.11.6.1 Ventilation system. The ventilation system in connection with hoods shall be operated at the required rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used. 904.11.6.2 Grease extractors. Where grease extractors are installed, they shall be operated when the commercial-type cooking equipment is used. 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. 904.11.6.5 Fusible link and sprinkler head replacement. Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer’s instructions. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
04/08/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of 3 , 2A:10B:C fire extinguishers. Verified at inspection.
Installation acceptance testing
Corrective Action Required
04/11/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: The Fire Department shall witness a test of the hood system.
Historical Preservation Review Approved 04/13/2011 04/01/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Change of Tenant $102.13 $102.13 Paid 05/17/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 5/24/2011 at 12:00 AM 05/24/2011
Misc
Corrective Action Required
05/24/2011
- NO ACCESS - CALL FOR REINSPECTION
Underslab Plumbing Inspection - Commercial Passed 5/25/2011 at 12:00 AM 05/25/2011
Misc
Corrective Action Required
05/24/2011
- NO ACCESS - CALL FOR REINSPECTION
Underslab Electrical Inspection - Commercial Passed 05/25/2011
Rated Assembly Inspection Passed 6/6/2011 6/6/2011 at 12:00 AM 06/06/2011
Rough Electrical Inspection - Residential Passed 6/6/2011 6/6/2011 at 12:00 AM 06/06/2011
Hood/Duct Inspection Passed 8/30/2011 at 9:00 AM 08/30/2011
Occupancy Inspection - Codes Commercial Failed 9/23/2011 at 12:00 AM 09/23/2011
Misc
Corrective Action Required
09/23/2011
1. PROVIDE OPEN FRONT TOILET SEATS. 2. REMOVE DEAD BOLT LOCKS FROM EXIT DOORS 3. PROVIDE BACKFLOW ON SODA MACHINE 4. PROVIDE BACKFLOW ON ICE MACHINE 5. SUBMIT BACK FLOW TEST TO WATER DEPARTMENT. 6. MOVE TOILET PAPER CONTAINER FROM BLOCKING VERTICAL GRAB BARS IN RESTROOM. 7. PROVIDE HEALTH DEPARTMENT APPROVAL PRYOR TO OCCUPANCY PENDING FIRE DEPARTMENT APPROVAL
Occupancy Inspection - Fire Not Ready 9/23/2011 at 12:00 AM 09/23/2011
Misc
Corrective Action Required
09/23/2011
(1) ansul supression line needs to be plugged where a nozzel had been removed (2) seal all penatrations in the hood system (3) remove the dead blots and passage hardware from the west dining room exit door and the east kitchen exit door
Occupancy Inspection - Fire Passed 09/29/2011
Misc
Corrective Action Required
09/23/2011
(1) ansul supression line needs to be plugged where a nozzel had been removed (2) seal all penatrations in the hood system (3) remove the dead blots and passage hardware from the west dining room exit door and the east kitchen exit door
Occupancy Inspection - Codes Commercial Full C of O 10/3/2011 at 12:00 AM 10/03/2011
Misc
Resolved
10/03/2011
1. PROVIDE OPEN FRONT TOILET SEATS. 2. REMOVE DEAD BOLT LOCKS FROM EXIT DOORS 3. PROVIDE BACKFLOW ON SODA MACHINE 4. PROVIDE BACKFLOW ON ICE MACHINE 5. SUBMIT BACK FLOW TEST TO WATER DEPARTMENT. 6. MOVE TOILET PAPER CONTAINER FROM BLOCKING VERTICAL GRAB BARS IN RESTROOM. 7. PROVIDE HEALTH DEPARTMENT APPROVAL PRYOR TO OCCUPANCY PENDING FIRE DEPARTMENT APPROVAL
Documents & Images
Date Uploaded File Type Document Name
04/12/2011 Letter Plan Review Conditions
05/05/2011 Letter Plan Review Conditions
05/12/2011 Letter Plan Review Conditions
05/17/2011 Letter Plan Review Conditions
05/17/2011 Letter Building Permit
05/24/2011 Letter Inspection Summary
05/25/2011 Letter Inspection Summary
06/06/2011 Letter Inspection Summary
09/23/2011 Letter Inspection Summary
09/23/2011 Letter Fire Loss Reduction Form
09/29/2011 Letter Fire Loss Reduction Form
10/03/2011 Letter Field Certificate of Occupancy
10/03/2011 Letter Field Certificate of Occupancy
10/04/2011 Letter Final Certificate of Occupancy
06/21/2013 Letter Fire Building Plan Review
06/25/2013 Letter Fire Building Plan Review
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents