Review Type |
Outcome |
Est. Completion Date |
Completed |
Internal Plan Review (Res)
|
Approved
|
|
05/16/2011
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Approved
|
05/17/2011
|
05/16/2011
|
|
Mike Weisenborn
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Health Dept Review
For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required - Provide documentation of plan review approval from the Jackson County Health Department.
|
|
Bldg - Minimum number of exits
Corrective Action Required
2006 IBC 1019.1 - Minimum number of exits. All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by Table 1019.1 based on the occupant load of the story, except as modified in Section 1015.1 or 1019.2. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrived at grade or the public way.
Action required - As the occupant load of Dining Area "C" is greater than 50 two means of egress are required from the space. Make needed corrections.
Mike Weisenborn May 05, 2011 - The occupant load of this space has been changed to 50. Signage to be verified on inspection.
|
|
Misc
Corrective Action Required
The plans indicate that replacement of similar equipment and fixtures is the only work to be done in the kitchen area. This permit does not include any alterations to the plumbing, electrical or mechanical systems.
Action required - If any alterations to the existing plumbing, electrical or mechanical systems are required for new equipment, plans for the alterations shall be provided for review and approval prior to performing the work. This comment is for information purposes.
|
|
Misc
Corrective Action Required
All health and safety issues for backflow protection on the water system and indirect waste on the sanitary shall be maintained/installed as required by code.
Action required - This will be verified on inspection.
|
|
License contractors
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances.
Action required - The building permit must be issued to a general contractor with a minimum of a Class B license. All plumbing, electrical and mechanical work shall be performed by licensed contractors. This comment is for information purposes.
|
|
Project cost
The project cost, which is used to establish the permit fee, has not been provided.
Action required - Provide the project cost.
Mike Weisenborn May 16, 2011 - The project cost has been provided.
|
|
Planning - Signs
Corrective Action Required
Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirments.
Action required - This comment is for information purposes.
|
|
Misc
On Friday April 29th Mike Copeland, Manager of Inspections, meet with the contractor and architect to discuss issues on the project in relation to kitchen equipement.
Action required - Provide details on the plans of the required corrective action discussed durring the site visit.
Mike Weisenborn May 12, 2011 - Provided information.
|
|
|
Internal Plan Review (Res)
|
Rejected
|
|
05/12/2011
|
|
Mike Weisenborn
|
|
|
Internal Plan Review (Res)
|
Rejected
|
|
05/05/2011
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Rejected
|
05/02/2011
|
05/05/2011
|
|
Mike Weisenborn
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required - Provide documentation of plan review approval from the Jackson County Health Department.
|
|
Bldg - Minimum number of exits
Corrective Action Required
2006 IBC 1019.1 - Minimum number of exits. All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by Table 1019.1 based on the occupant load of the story, except as modified in Section 1015.1 or 1019.2. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrived at grade or the public way.
Action required - As the occupant load of Dining Area "C" is greater than 50 two means of egress are required from the space. Make needed corrections.
Mike Weisenborn May 05, 2011 - The occupant load of this space has been changed to 50. Signage to be verified on inspection.
|
|
Bldg - Accessibility - Point of sale and service counters 1109.12.3
2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Action required - Show how this requirement will be met for the Cashier Station.
Mike Weisenborn May 05, 2011 - Plans have been revised.
|
|
Misc
2006 IBC 1108.2.8.1 - Dining surfaces. Where dining surfaces for the consumption of food or drink are provided, at least 5 percent, but not less than one, of the seating and standing spaces at the dining surfaces shall be accessible and be distributed throughout the facility.
Action required - Show how this requirement will be met.
Mike Weisenborn May 05, 2011 - Information has been provided on the plans.
|
|
Plumb - Indirect waste for food handling fixtures
2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Action required - The new buffet tables shall be connected to the sanitary system by an indirect waste. Please add this to the note on the buffet tables on Sheet A2.
Mike Weisenborn May 05, 2011 - Notes have been added to the plans.
|
|
Bldg - Exit signage - Where required
2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Action required - Exit signage is required in Dining Area "C" as two means of egress are required from the space. Exit signage shall be visable from the Buffet Area. If the new cased opening block the visibility of the exit signage at the doors, additional signage shall be added.
Mike Weisenborn May 05, 2011 - The occupant load has been lowered so signage is not required.
|
|
Misc
Corrective Action Required
The plans indicate that replacement of similar equipment and fixtures is the only work to be done in the kitchen area. This permit does not include any alterations to the plumbing, electrical or mechanical systems.
Action required - If any alterations to the existing plumbing, electrical or mechanical systems are required for new equipment, plans for the alterations shall be provided for review and approval prior to performing the work. This comment is for information purposes.
|
|
Misc
Corrective Action Required
All health and safety issues for backflow protection on the water system and indirect waste on the sanitary shall be maintained/installed as required by code.
Action required - This will be verified on inspection.
|
|
License contractors
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances.
Action required - The building permit must be issued to a general contractor with a minimum of a Class B license. All plumbing, electrical and mechanical work shall be performed by licensed contractors. This comment is for information purposes.
|
|
Project cost
Corrective Action Required
The project cost, which is used to establish the permit fee, has not been provided.
Action required - Provide the project cost.
|
|
Planning - Signs
Corrective Action Required
Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirments.
|
|
Misc
Corrective Action Required
On Friday April 29th Mike Copeland, Manager of Inspections, meet with the contractor and architect to discuss issues on the project in relation to kitchen equipement.
Action required - Provide details on the plans of the required corrective action discussed durring the site visit.
|
|
|
Fire Plan Review
|
Approved
|
05/02/2011
|
05/02/2011
|
|
Brian Austerman
|
|
Misc
Corrective Action Required
015.1 Exit or exit access doorways required.
Two exits or exit access doorways from any space shall be provided where one of the following conditions exists:
1. The occupant load of the space exceeds the values in Table 1015.1.
2. The common path of egress travel exceeds the limitations of Section 1014.3.
3. Where required by Sections 1015.3, 1015.4 and 1015.5.
Exception: Group I-2 occupancies shall comply with Section 1014.2.2.
Action required: The occupant load of Dining Room C shall not exceed 49. Reduce the number of seating spaces in the room. RESUB SHOWS 50, NEEDS TO BE 49. VERIFIED AT INSPECTION
|
|
Posting of occupant load
Corrective Action Required
2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Rooms shall be posted along with the the posting of the total occupancy at the front door. Verified at inspection.
|
|
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Action required: The K class extinguisher shall be located at the manual pull station for the hood system with instructions for operation in english and the predominant language.
|
|
Misc
Corrective Action Required
904.11.6 Operations and maintenance.
Commercial cooking systems shall be operated and maintained in accordance with this section.
904.11.6.1 Ventilation system.
The ventilation system in connection with hoods shall be operated at the required rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used.
904.11.6.2 Grease extractors.
Where grease extractors are installed, they shall be operated when the commercial-type cooking equipment is used.
904.11.6.3 Cleaning.
Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
904.11.6.4 Extinguishing system service.
Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.
904.11.6.5 Fusible link and sprinkler head replacement.
Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer’s instructions.
Verified at inspection.
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required: Provide a minimum of 3 , 2A:10B:C fire extinguishers. Verified at inspection.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action required: The Fire Department shall witness a test of the hood system.
|
|
|
License Tax Codes
|
Approved
|
04/13/2011
|
04/13/2011
|
|
Mike Weisenborn
|
|
|
Internal Plan Review (Res)
|
Rejected
|
04/13/2011
|
04/12/2011
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Rejected
|
04/13/2011
|
04/12/2011
|
|
Mike Weisenborn
|
|
Health Dept Inspection
Corrective Action Required
For the Health Department inspection contact Chris Saxton with the Jackson County Public Works Department, Environmental Health Division at 816-881-4455. Health Department approval is required prior to receiving any type of Occupancy from the City of Lee's Summit.
Action required - This comment is for information purposes.
|
|
Health Dept Review
Corrective Action Required
For the Health Department review contact Chris Saxton with the Jackson County Public Works Department, Environmental Services Division, at 816-881-4455. Health Department approval is required prior to receiving any type of building permit from the City of Lee's Summit.
Action required - Provide documentation of plan review approval from the Jackson County Health Department.
|
|
Bldg - Minimum number of exits
Corrective Action Required
2006 IBC 1019.1 - Minimum number of exits. All rooms and spaces within each story shall be provided with and have access to the minimum number of approved independent exits required by Table 1019.1 based on the occupant load of the story, except as modified in Section 1015.1 or 1019.2. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories. The required number of exits from any story, basement or individual space shall be maintained until arrived at grade or the public way.
Action required - As the occupant load of Dining Area "C" is greater than 50 two means of egress are required from the space. Make needed corrections.
|
|
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed.
Action required - Show how this requirement will be met for the Cashier Station.
|
|
Misc
Corrective Action Required
2006 IBC 1108.2.8.1 - Dining surfaces. Where dining surfaces for the consumption of food or drink are provided, at least 5 percent, but not less than one, of the seating and standing spaces at the dining surfaces shall be accessible and be distributed throughout the facility.
Action required - Show how this requirement will be met.
|
|
Plumb - Indirect waste for food handling fixtures
Corrective Action Required
2006 IPC 802.1.1 - Food handling. Equipment and fixtures utilized for the storage, preparation and handling of food shall discharge through an indirect waste pipe by means of an air gap.
Action required - The new buffet tables shall be connected to the sanitary system by an indirect waste. Please add this to the note on the buffet tables on Sheet A2.
|
|
Bldg - Exit signage - Where required
Corrective Action Required
2006 IBC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in a corridor is more than 100 feet or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.
Action required - Exit signage is required in Dining Area "C" as two means of egress are required from the space. Exit signage shall be visable from the Buffet Area. If the new cased opening block the visibility of the exit signage at the doors, additional signage shall be added.
|
|
Misc
Corrective Action Required
The plans indicate that replacement of similar equipment and fixtures is the only work to be done in the kitchen area. This permit does not include any alterations to the plumbing, electrical or mechanical systems.
Action required - If any alterations to the existing plumbing, electrical or mechanical systems are required for new equipment, plans for the alterations shall be provided for review and approval prior to performing the work. This comment is for information purposes.
|
|
Misc
Corrective Action Required
All health and safety issues for backflow protection on the water system and indirect waste on the sanitary shall be maintained/installed as required by code.
Action required - This will be verified on inspection.
|
|
License contractors
Corrective Action Required
No person, other than a licensed contractor or employees of a licensed contractor, shall engage in electrical, plumbing or mechanical business, construction, installation or maintenance unless duly licensed in accordance with this section. Expert from Sec. 7-130, Lees Summit Code of Ordinances.
Action required - The building permit must be issued to a general contractor with a minimum of a Class B license. All plumbing, electrical and mechanical work shall be performed by licensed contractors. This comment is for information purposes.
|
|
Project cost
Corrective Action Required
The project cost, which is used to establish the permit fee, has not been provided.
Action required - Provide the project cost.
|
|
Planning - Signs
Corrective Action Required
Exterior signage is not included in the building permit review. Please contact the Planning and Development Department at (816) 969-1600 for application, review and permit requirments.
|
|
|
Fire Plan Review
|
Rejected
|
04/13/2011
|
04/11/2011
|
|
Jim Eden
|
|
Misc
Corrective Action Required
015.1 Exit or exit access doorways required.
Two exits or exit access doorways from any space shall be provided where one of the following conditions exists:
1. The occupant load of the space exceeds the values in Table 1015.1.
2. The common path of egress travel exceeds the limitations of Section 1014.3.
3. Where required by Sections 1015.3, 1015.4 and 1015.5.
Exception: Group I-2 occupancies shall comply with Section 1014.2.2.
Action required: The occupant load of Dining Room C shall not exceed 49. Reduce the number of seating spaces in the room.
|
|
Posting of occupant load
Corrective Action Required
2006 IFC 1004.3- Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
Action required: Rooms shall be posted along with the the posting of the total occupancy at the front door. Verified at inspection.
|
|
Portable fire extinguishers for commercial cooking equipment.
Corrective Action Required
2006 IFC 904.11.5- Portable fire extinguishers for commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher.
Action required: The K class extinguisher shall be located at the manual pull station for the hood system with instructions for operation in english and the predominant language.
|
|
Misc
Corrective Action Required
904.11.6 Operations and maintenance.
Commercial cooking systems shall be operated and maintained in accordance with this section.
904.11.6.1 Ventilation system.
The ventilation system in connection with hoods shall be operated at the required rate of air movement, and classified grease filters shall be in place when equipment under a kitchen grease hood is used.
904.11.6.2 Grease extractors.
Where grease extractors are installed, they shall be operated when the commercial-type cooking equipment is used.
904.11.6.3 Cleaning.
Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
904.11.6.4 Extinguishing system service.
Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.
904.11.6.5 Fusible link and sprinkler head replacement.
Fusible links and automatic sprinkler heads shall be replaced at least annually, and other protection devices shall be serviced or replaced in accordance with the manufacturer’s instructions.
Verified at inspection.
|
|
Portable fire extinguishers - general
Corrective Action Required
2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required: Provide a minimum of 3 , 2A:10B:C fire extinguishers. Verified at inspection.
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action required: The Fire Department shall witness a test of the hood system.
|
|
|
Historical Preservation Review
|
Approved
|
04/13/2011
|
04/01/2011
|
|
Mike Weisenborn
|
|
|