Permit Application Status

PRCOM20110161


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20110161
Building Permit - Commercial
Certificate of Occupancy
DOUGLAS STATION SHOPPING CENTER LLC
CHANGE OF TENANT
Tenant finish
02/14/2011
02/28/2011
08/23/2011
03/28/2011
Locations
Contacts
DOUGLAS STATION SHOPPING CENTER LLC, Address:1725 NE RICE RD  
MARTIN GREGORY L, Address:212 SE TOPAZ CRT  
BUDDEMEYER CONSTRUCTION, Address:4223 FURLONG DR  
A-TEAM ELECTRIC, Address:7104 N HOMES, Phone:(816) 365-3670  
TRI-COUNTY PLUMBING LLC, Address:PO BOX 234, Phone:(816) 720-3222  
LS INVESTORS ONE LLC, Address:1220 WASHINGTON ST PO BOX 411299  
Reviews
Review Type Outcome Est. Completion Date Completed
Fire Plan Review Rejected 03/04/2011 03/02/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
03/01/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for sprinkler alterations. 03/01/2011- Sprinkler alateration plans are required.
Construction documents for fire alarm systems
Corrective Action Required
03/01/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings showing the location of new and relocated appliances. The drawings shop smoke detectors. Were these intended to de the remote LED/reset switches for the duct detectors?
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
03/01/2011

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing fire protection system shall have documentation of a current annual inspection. Verified at inspection.
Installation acceptance testing
Corrective Action Required
03/01/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. New and relocated appliances will be tested at inspection, preferrably before the regular business hours of the neighboring tenants.
Address numbers required
Corrective Action Required
03/01/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: All exterior doors shall be posted with the same address. Verified at inspection.
Portable fire extinguishers - general
Resolved
03/01/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide one additional 2A:10B:C fire extinguisher.
Misc
Corrective Action Required
03/01/2011

Correct occupant load calculations.
Fire Plan Review Rejected 02/22/2011 02/28/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
02/24/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for sprinkler alterations.
Construction documents for fire alarm systems
Corrective Action Required
02/24/2011

2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Provide shop drawings showing the location of new and relocated appliances. The drawings shop smoke detectors. Were these intended to de the remote LED/reset switches for the duct detectors?
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
02/24/2011

2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed. The existing fire protection system shall have documentation of a current annual inspection. Verified at inspection.
Installation acceptance testing
Corrective Action Required
02/24/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. New and relocated appliances will be tested at inspection, preferrably before the regular business hours of the neighboring tenants.
Address numbers required
Corrective Action Required
02/24/2011

2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: All exterior doors shall be posted with the same address. Verified at inspection.
Portable fire extinguishers - general
Corrective Action Required
02/24/2011

2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide one additional 2A:10B:C fire extinguisher.
Internal Plan Review (Res) Approved 02/28/2011
Mike Weisenborn
Building Plan Review Approved 03/04/2011 02/28/2011
Mike Weisenborn
Misc
Resolved
02/28/2011

The construction type provided on Sheet C-1 is Type I-B which is incorrect. The actual construction type of the building is Type V-B. Action required - Make needed corrections. Corrections have been made.
Bldg - Occupant load calculations - Areas without fixed seats
Resolved
02/28/2011

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - Provide the calculated occupant load with the Code Data and Design Loads. Occupant loads have been provided but where incorrect. Changed the multiplier for retail from 60 to 30.
Misc
Resolved
02/28/2011

All plans submitted for review on or after July 9, 2007 shall be designed to the requirements of the 2006 International Building Code, 2006 International Mechanical Code, 2006 International Plumbing Code, 2006 International Fuel Gas Code, 2006 International Fire Code, 2005 National Electric Code and the ANSI A117.1-2003 as amended and adopted by the City of Lee's Summit. Action required - Please add the additional required codes to the Applicable Codes section. Information has been added.
Misc
Resolved
02/28/2011

The plans show that wall type 4A is a firewall. There are no required fire-rated assemblies in this project. If the intent is to build a fire-resistive assembly the listing of the assembly needs to be provided. If the rated assembly is not intended to be constructred than the notation on the detail needs to be removed. Action required - Make needed corrections. The indication has been removed.
Bldg - Doors - Size of doors
Resolved
02/28/2011

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - Make needed corrections to the door to the window display area, office and fitting rooms. Corrections have been made.
Misc
Resolved
02/28/2011

As we discussed when the plans were submitted for review, the new men's restroom will be required to meet the current requirements for clearances. Action required - Make needed corrections. Corrections have made.
Misc
Resolved
02/28/2011

As we discussed when the plans were submitted for review, the accessible restroom will be required to meet the ANSI A117.1 requirements for an accessible restroom. Action required - Make needed corrections.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
02/25/2011

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Provide details showing compliance with the requirements for an accessible counter. To be verified on inspection.
Misc
Corrective Action Required
02/25/2011

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - Add the additional 18" vertical grab bar. The required vertical grab bar has been added to the plans but it is shown on the back wall. The vertical grab bar is required on the side wall of the toilet. Made notes on the plans.
Misc
Resolved
02/28/2011

2005 NEC 210.62 Show windows. At least one receptacle outlet shall be installed directly above a show window for each 3.7 linear m (12 linear ft) or major fraction thereof of show window area measured horizontally at its maximum width. Action required - Make corrections as needed.
Internal Plan Review (Res) Rejected 02/22/2011 02/24/2011
Mike Weisenborn
Building Plan Review Rejected 02/22/2011 02/18/2011
Mike Weisenborn
Misc
Corrective Action Required
02/18/2011

The construction type provided on Sheet C-1 is Type I-B which is incorrect. The actual construction type of the building is Type V-B. Action required - Make needed corrections.
Bldg - Occupant load calculations - Areas without fixed seats
Corrective Action Required
02/18/2011

2006 IBC 1004.1.1 - Areas without fixed seating. The number of occupants shall be computed at the rate of one occupant per unit of area as prescribed in Table 1004.1.1. For areas with out fixed seating, the occupant load shall not be less than that number determined by dividing the floor area under consideration by the occupant per unit of area factor assigned to the occupancy as set forth in Table 1004.1.1. Where an intended use is not listed in Table 1004.1.1, the building official shall establish a use based on a listed use that most nearly resembles the intended use. Action required - Provide the calculated occupant load with the Code Data and Design Loads.
Misc
Corrective Action Required
02/18/2011

All plans submitted for review on or after July 9, 2007 shall be designed to the requirements of the 2006 International Building Code, 2006 International Mechanical Code, 2006 International Plumbing Code, 2006 International Fuel Gas Code, 2006 International Fire Code, 2005 National Electric Code and the ANSI A117.1-2003 as amended and adopted by the City of Lee's Summit. Action required - Please add the additional required codes to the Applicable Codes section.
Misc
Corrective Action Required
02/18/2011

The plans show that wall type 4A is a firewall. There are no required fire-rated assemblies in this project. If the intent is to build a fire-resistive assembly the listing of the assembly needs to be provided. If the rated assembly is not intended to be constructred than the notation on the detail needs to be removed. Action required - Make needed corrections.
Bldg - Doors - Size of doors
Corrective Action Required
02/18/2011

2006 IBC 1008.1.1 - Size of doors. The minimum width of each door opening shall be sufficient for the occupant load thereof and shall provide a clear width of not less than 32 inches. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Where this section requires a minimum clear width of 32 inches and a door opening includes two door leaves without a mullion, one leaf shall provide a clear width of 32 inches. The maximum width of a swinging door leaf shall be 48 inches nominal. Means of egress doors in Group I-2 occupancy used for the movement of beds shall provide a clear width not less than 41.5 inches. The height of doors shall not be less than 80 inches. Action required - Make needed corrections to the door to the window display area, office and fitting rooms.
Misc
Corrective Action Required
02/18/2011

As we discussed when the plans were submitted for review, the new men's restroom will be required to meet the current requirements for clearances. Action required - Make needed corrections.
Misc
Corrective Action Required
02/18/2011

As we discussed when the plans were submitted for review, the accessible restroom will be required to meet the ANSI A117.1 requirements for an accessible restroom. Action required - Make needed corrections.
Bldg - Accessibility - Point of sale and service counters 1109.12.3
Corrective Action Required
02/18/2011

2006 IBC 1109.12.3 - Point of sale and service counters. Where counters are provided for sales or distribution of goods or services, at least one of each type provided shall be accessible. Where such counters are dispersed throughout the building or facility, accessible counters shall also be dispersed. Action required - Provide details showing compliance with the requirements for an accessible counter.
Misc
Corrective Action Required
02/18/2011

ICC/ANSI A117.1 2003 604.5.1 - Fixed sidewall grab bars. Fixed sidewall grab bars shall be 42 inches minimum in length, located 12 inches maximum from the rear wall and extending 54 inches minimum from the rear wall. In addition, a vertical grab bar 18 inches minimum in length shall be mounted with the bottom of the bar located between 39 inches and 41 inches above the floor, and with the center line of the bar located between 39 inches and 41 inches from the rear wall. Action required - Add the additional 18" vertical grab bar.
Misc
Corrective Action Required
02/18/2011

2005 NEC 210.62 Show windows. At least one receptacle outlet shall be installed directly above a show window for each 3.7 linear m (12 linear ft) or major fraction thereof of show window area measured horizontally at its maximum width. Action required - Make corrections as needed.
License Tax Codes Approved 02/22/2011 02/18/2011
Mike Weisenborn
Historical Preservation Review Approved 02/22/2011 02/15/2011
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Change of Tenant $81.70 $81.70 Paid 02/28/2011
8331507-Sewer Connection Fee $60.00 $60.00 Paid 02/28/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Commercial Not Ready 3/4/2011 3/4/2011 at 12:00 AM 03/04/2011
Misc
Resolved
03/04/2011
PERMIT DRAWINGS NOT FOUND AT JOBSITE.
Underslab Plumbing Inspection - Commercial Passed 3/7/2011 3/7/2011 at 12:00 AM 03/07/2011
In-wall Inspection Failed 3/10/2011 at 12:00 AM 03/10/2011
Misc
Corrective Action Required
03/10/2011
PVC AND COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING NOT PROTECTED BY SHIELD PLATES AT OPEN PORTIONS OF WALL
Misc
Corrective Action Required
03/10/2011
COPPER PIPING NOT PROTECTED FROM STEEL STUD EDGE AT ONE OR MORE LOCATION.
Misc
Corrective Action Required
03/10/2011
MC ELECTRICAL CABLE NOT SECURED WITHIN 12" OF ENTRY TO SOME BOXES
Misc
Corrective Action Required
03/10/2011
STUD AT MEN'S RR S.E. NOT REINFORCED TO COMPENSATE FOR REMOVED SECTION OF FLANGE
Misc
Corrective Action Required
03/10/2011
CLEANOUT AT MAIN PLUMBING STACK MUST BE USABLE; REINFORCE STUD IF PORTION OF FLANGE MUST BE REMOVED. INSTALL ACCESS PANEL BEFORE FINAL INSPECTION.
Misc
Corrective Action Required
03/10/2011
CLARIFICATION REQUIRED ON WALL TYPE "4A" DESIGNATED AS "FIREWALL"
In-wall Inspection Partial 3/14/2011 3/11/2011 at 12:00 AM 03/11/2011
Misc
Resolved
03/11/2011
PVC AND COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING NOT PROTECTED BY SHIELD PLATES AT OPEN PORTIONS OF WALL
Misc
Resolved
03/11/2011
COPPER PIPING NOT PROTECTED FROM STEEL STUD EDGE AT ONE OR MORE LOCATION.
Misc
Resolved
03/11/2011
MC ELECTRICAL CABLE NOT SECURED WITHIN 12" OF ENTRY TO SOME BOXES
Misc
Resolved
03/11/2011
STUD AT MEN'S RR S.E. NOT REINFORCED TO COMPENSATE FOR REMOVED SECTION OF FLANGE
Misc
Resolved
03/11/2011
CLEANOUT AT MAIN PLUMBING STACK MUST BE USABLE; REINFORCE STUD IF PORTION OF FLANGE MUST BE REMOVED. INSTALL ACCESS PANEL BEFORE FINAL INSPECTION.
Misc
Corrective Action Required
03/11/2011
CLARIFICATION REQUIRED ON WALL TYPE "4A" DESIGNATED AS "FIREWALL"
Misc
Resolved
03/11/2011
PROPERTY LOCKED; NO ACCESS FOR INSPECTION.
In-wall Inspection Partial 3/11/2011 3/11/2011 at 12:00 AM 03/11/2011
Misc
Resolved
03/11/2011
PVC AND COPPER PLUMBING PIPE LESS THAN 1-1/2" FROM FACE OF FRAMING NOT PROTECTED BY SHIELD PLATES AT OPEN PORTIONS OF WALL
Misc
Resolved
03/11/2011
COPPER PIPING NOT PROTECTED FROM STEEL STUD EDGE AT ONE OR MORE LOCATION.
Misc
Resolved
03/11/2011
MC ELECTRICAL CABLE NOT SECURED WITHIN 12" OF ENTRY TO SOME BOXES
Misc
Resolved
03/11/2011
STUD AT MEN'S RR S.E. NOT REINFORCED TO COMPENSATE FOR REMOVED SECTION OF FLANGE
Misc
Resolved
03/11/2011
CLEANOUT AT MAIN PLUMBING STACK MUST BE USABLE; REINFORCE STUD IF PORTION OF FLANGE MUST BE REMOVED. INSTALL ACCESS PANEL BEFORE FINAL INSPECTION.
Misc
Corrective Action Required
03/10/2011
CLARIFICATION REQUIRED ON WALL TYPE "4A" DESIGNATED AS "FIREWALL"
Misc
Resolved
03/11/2011
PROPERTY LOCKED; NO ACCESS FOR INSPECTION.
Occupancy Inspection - Codes Commercial Failed 3/25/2011 at 12:00 AM 03/25/2011
Misc
Corrective Action Required
03/25/2011
ADDRESS LABELING OF ELECTRICAL SERVICE PANELS -- DESIGNATE WHICH METER SERVES EACH PANEL
Misc
Corrective Action Required
03/25/2011
LABELING OF ELECTRICAL CIRCUITS AT SERVICE PANELS: NEC 408.4; IRC E36O6.2. EACH BREAKER MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Corrective Action Required
03/25/2011
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRIES: APPLY PERMANENT TAGS TO LOAD SIDE ENTRY PIPE (NOT ON METER).
Misc
Corrective Action Required
03/25/2011
SOME ELECTRICAL RECEPTACLES AT REAR WALL NOT SECURED SOLID TO BOX -- TIGHTEN
Misc
Corrective Action Required
03/25/2011
WALL BASE NOT INSTALLED AT SOUTH RESTROOM
Misc
Corrective Action Required
03/25/2011
NORTH RESTROOM LACKS HANDICAPPED-ACCESSIBLE SIGN
Misc
Corrective Action Required
03/25/2011
WATER CLOSETS NOT SEALED TO FLOOR SURFACE
Misc
Corrective Action Required
03/25/2011
AFFIX "NO SMOKING" SIGN AT EACH ENTRANCE TO BE UTILIZED BY PUBLIC
Occupancy Inspection - Fire Temporary C of O 3/25/2011 at 12:00 AM 03/25/2011
Misc
Corrective Action Required
03/25/2011
post the designated address on the front and fear doors of 1170, 4" min. in a contrasting color
Misc
Corrective Action Required
03/25/2011
mount 2A-10BC fire extinguisher close to an exit with the top of theextinguisher no higher than 60" off floor.
Misc
Corrective Action Required
03/25/2011
replace the painted sprinkler head located above the middle front entry door.
Misc
Corrective Action Required
03/25/2011
cover the open j-box located above the storeage room door at the rear of the store.
Alarm Test Passed 3/24/2011 at 12:00 AM 03/25/2011
Occupancy Inspection - Codes Commercial Full C of O 3/28/2011 at 12:00 AM 03/28/2011
Misc
Resolved
03/28/2011
ADDRESS LABELING OF ELECTRICAL SERVICE PANELS -- DESIGNATE WHICH METER SERVES EACH PANEL
Misc
Resolved
03/28/2011
LABELING OF ELECTRICAL CIRCUITS AT SERVICE PANELS: NEC 408.4; IRC E36O6.2. EACH BREAKER MUST BE LABELED. MUST BE LEGIBLE; SPECIFIC. IF PANEL SCHEDULE IS USED NUMBER POSITIONS ON PANEL FRONT PER SCHEDULE. NO DITTO MARKS OR CONTINUATION SYMBOLS EXCEPT @ MULTIPLE POLE BREAKERS. LABEL UNUSED BREAKERS "SPARE"
Misc
Resolved
03/28/2011
ADDRESS IDENTIFICATION OF GAS SERVICE ENTRIES: APPLY PERMANENT TAGS TO LOAD SIDE ENTRY PIPE (NOT ON METER).
Misc
Resolved
03/28/2011
SOME ELECTRICAL RECEPTACLES AT REAR WALL NOT SECURED SOLID TO BOX -- TIGHTEN
Misc
Resolved
03/28/2011
WALL BASE NOT INSTALLED AT SOUTH RESTROOM
Misc
Resolved
03/28/2011
NORTH RESTROOM LACKS HANDICAPPED-ACCESSIBLE SIGN
Misc
Resolved
03/28/2011
WATER CLOSETS NOT SEALED TO FLOOR SURFACE
Misc
Resolved
03/28/2011
AFFIX "NO SMOKING" SIGN AT EACH ENTRANCE TO BE UTILIZED BY PUBLIC
In-wall Inspection Passed 3/28/2011 at 12:00 AM 03/28/2011
Misc
Corrective Action Required
03/11/2011
CLARIFICATION REQUIRED ON WALL TYPE "4A" DESIGNATED AS "FIREWALL"
Occupancy Inspection - Fire Passed 3/28/2011 at 12:00 AM 03/28/2011
Misc
Corrective Action Required
03/25/2011
post the designated address on the front and fear doors of 1170, 4" min. in a contrasting color
Misc
Corrective Action Required
03/25/2011
mount 2A-10BC fire extinguisher close to an exit with the top of theextinguisher no higher than 60" off floor.
Misc
Corrective Action Required
03/25/2011
replace the painted sprinkler head located above the middle front entry door.
Misc
Corrective Action Required
03/25/2011
cover the open j-box located above the storeage room door at the rear of the store.
Documents & Images
Date Uploaded File Type Document Name
02/24/2011 Letter Plan Review Conditions
02/28/2011 Letter Building Permit
03/07/2011 Letter Inspection Summary
03/10/2011 Letter Inspection Summary
03/11/2011 Letter Inspection Summary
03/11/2011 Letter Inspection Summary
03/25/2011 Letter Inspection Summary
03/25/2011 Letter Inspection Summary
03/28/2011 Letter Field Certificate of Occupancy
03/28/2011 Letter Fire Loss Reduction Form
03/29/2011 Letter Final Certificate of Occupancy
06/27/2013 Letter Fire Loss Reduction Form
07/02/2013 Letter Plan Review Conditions
07/02/2013 Letter Plan Review Conditions
07/28/2015 Activity Document DOC072815-001
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home