Review Type |
Outcome |
Est. Completion Date |
Completed |
Zoning Review
|
Approved
|
12/21/2010
|
01/24/2011
|
|
John Borns
|
|
|
Internal Plan Review (Res)
|
Approved
|
|
01/13/2011
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Approved
|
01/21/2011
|
01/13/2011
|
|
Mike Weisenborn
|
|
Misc
The plans do not provide any specifications for the electrical work.
Action required - Provide additional information on the electrical work.
|
|
Misc
Corrective Action Required
The plans indicate that the existing tenant demising wall is rated. The demising walls of this space are not rated.
Action required - This comment is for information purposes.
|
|
|
Fire Plan Review
|
Approved
|
12/21/2010
|
01/13/2011
|
|
Mike Weisenborn
|
|
Construction documents - Fire protection systems
Corrective Action Required
Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide shop drawings for sprinkler alterations.
|
|
Construction documents for fire alarm systems
Corrective Action Required
Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action required: Provide shop drawings for any additional appliances.
|
|
Portable fire extinguishers - general
Corrective Action Required
Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required: Provide a minimum of one 2A:10B:C fire extinguisher in a conspicuous location.
|
|
Address numbers required
Corrective Action Required
Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required: Confirm addressing is on both doors.
|
|
Misc
Corrective Action Required
Fire Department-Conditions from the white box finish confirmed at inspection, including exit and emergency lighting.
|
|
Approved, set to rejected for resubmittal. Mike
|
Sprinkler Plan Review
|
Released for Construction
|
|
12/30/2010
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Plans submitted 12/30/2010
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action required: Call (816) 969-1300 to schedule sprinkler and alarm tests.
|
|
Fire protection equipment identification
Corrective Action Required
2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible.
Action required: Sectional valves and controls shall be clearly marked to indicate the area they serve and accessible. Verified at inspection.
|
|
|
Internal Plan Review (Res)
|
Rejected
|
12/21/2010
|
12/20/2010
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Rejected
|
12/21/2010
|
12/16/2010
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
The plans do not provide any specifications for the electrical work.
Action required - Provide additional information on the electrical work.
|
|
Misc
Corrective Action Required
The plans indicate that the existing tenant demising wall is rated.
Action required - I don't believe the existing demising wall is rated. If it is all penetrations will have to be protected. Provide additional information.
|
|
|
License Tax Codes
|
Approved
|
12/21/2010
|
12/16/2010
|
|
Mike Weisenborn
|
|
|
Historical Preservation Review
|
Approved
|
12/21/2010
|
12/09/2010
|
|
Mike Weisenborn
|
|
|