Permit Application Status

PRCOM20100267


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20100267
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
TENANT FINISH FOR WOMEN'S AND KIDS CLOTHING
12/09/2010
01/18/2011
06/18/2011
02/04/2011
Locations
Contacts
GUIDING LIGHT ELECTRIC INC, Address:706 HAMBLEN RD, Phone:(816) 361-5150  
HAMMERLY CONSTRUCTION COMPANY LLC, Address:2505 NE INDIAN POINTE  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Zoning Review Approved 12/21/2010 01/24/2011
John Borns
Internal Plan Review (Res) Approved 01/13/2011
Mike Weisenborn
Building Plan Review Approved 01/21/2011 01/13/2011
Mike Weisenborn
Misc
Resolved
01/13/2011

The plans do not provide any specifications for the electrical work. Action required - Provide additional information on the electrical work.
Misc
Corrective Action Required
01/13/2011

The plans indicate that the existing tenant demising wall is rated. The demising walls of this space are not rated. Action required - This comment is for information purposes.
Fire Plan Review Approved 12/21/2010 01/13/2011
Mike Weisenborn
Construction documents - Fire protection systems
Corrective Action Required
12/10/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for sprinkler alterations.
Construction documents for fire alarm systems
Corrective Action Required
12/10/2010

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for any additional appliances.
Portable fire extinguishers - general
Corrective Action Required
12/10/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher in a conspicuous location.
Address numbers required
Corrective Action Required
12/10/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Action required: Confirm addressing is on both doors.
Misc
Corrective Action Required
12/10/2010

Fire Department-Conditions from the white box finish confirmed at inspection, including exit and emergency lighting.
Approved, set to rejected for resubmittal. Mike
Sprinkler Plan Review Released for Construction 12/30/2010
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
12/30/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans submitted 12/30/2010
Installation acceptance testing
Corrective Action Required
12/30/2010

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Action required: Call (816) 969-1300 to schedule sprinkler and alarm tests.
Fire protection equipment identification
Corrective Action Required
12/30/2010

2006 IFC 510.1- Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. Action required: Sectional valves and controls shall be clearly marked to indicate the area they serve and accessible. Verified at inspection.
Internal Plan Review (Res) Rejected 12/21/2010 12/20/2010
Mike Weisenborn
Building Plan Review Rejected 12/21/2010 12/16/2010
Mike Weisenborn
Misc
Corrective Action Required
12/16/2010

The plans do not provide any specifications for the electrical work. Action required - Provide additional information on the electrical work.
Misc
Corrective Action Required
12/16/2010

The plans indicate that the existing tenant demising wall is rated. Action required - I don't believe the existing demising wall is rated. If it is all penetrations will have to be protected. Provide additional information.
License Tax Codes Approved 12/21/2010 12/16/2010
Mike Weisenborn
Historical Preservation Review Approved 12/21/2010 12/09/2010
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $35.17 $35.17 Paid 01/18/2011
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Alarm Test Passed 1/21/2011 at 12:00 AM 01/21/2011
Sprinkler - Flow Test Passed 1/21/2011 at 12:00 AM 01/21/2011
Corrective Action Required
01/21/2011
Sprinkler - Flow Test Passed 01/21/2011
Alarm Test Passed 01/21/2011
Occupancy Inspection - Fire Passed 01/24/2011
Corrective Action Required
01/24/2011
Occupancy Inspection - Codes Commercial Temporary C of O 1/24/2011 at 12:00 AM 01/24/2011
Misc
Corrective Action Required
01/24/2011
ACCESSIBLE COMMERCIAL RESTROOM REQUIRES: 1) NON-ABSORBENT FINISH ON RESTROOM WALL, BASE, AND FLOOR (CRACK MUST BE FILLED) 2) ADA/ANSI ACCESSIBLE SIGN
Occupancy Inspection - Codes Commercial Not Ready 2/1/2011 at 12:00 AM 02/01/2011
Misc
Corrective Action Required
01/24/2011
ACCESSIBLE COMMERCIAL RESTROOM REQUIRES: 1) NON-ABSORBENT FINISH ON RESTROOM WALL, BASE, AND FLOOR (CRACK MUST BE FILLED) 2) ADA/ANSI ACCESSIBLE SIGN
Occupancy Inspection - Codes Commercial Not Ready 2/3/2011 at 12:00 AM 02/03/2011
Misc
Corrective Action Required
02/01/2011
ACCESSIBLE COMMERCIAL RESTROOM REQUIRES: 1) NON-ABSORBENT FINISH ON RESTROOM WALL, BASE, AND FLOOR (CRACK MUST BE FILLED) 2) ADA/ANSI ACCESSIBLE SIGN
Occupancy Inspection - Codes Commercial Full C of O 2/4/2011 at 12:00 AM 02/04/2011
Misc
Resolved
02/04/2011
ACCESSIBLE COMMERCIAL RESTROOM REQUIRES: 1) NON-ABSORBENT FINISH ON RESTROOM WALL, BASE, AND FLOOR (CRACK MUST BE FILLED) 2) ADA/ANSI ACCESSIBLE SIGN
Documents & Images
Date Uploaded File Type Document Name
12/20/2010 Letter Plan Review Conditions
12/30/2010 Letter Fire (Sprinkler) Plan Review
01/18/2011 Letter Plan Review Conditions
01/18/2011 Letter Plan Review Conditions
01/18/2011 Letter Building Permit
01/21/2011 Letter Fire Loss Reduction Form
01/24/2011 Letter Fire Loss Reduction Form
01/24/2011 Letter Temporary Certificate of Occupancy
02/01/2011 Letter Inspection Summary
02/03/2011 Letter Inspection Summary
02/04/2011 Letter Field Certificate of Occupancy
02/07/2011 Letter Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home