Permit Application Status

PRCOM20100231


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRCOM20100231
Building Permit - Commercial
Certificate of Occupancy
RED SUMMIT FAIR LLC
NEW TENANT FINISH
Tenant finish
12/01/2010
12/30/2010
06/11/2011
03/25/2011
Locations
Contacts
ANS CONSTRUCTION, Address:29 W 14TH AVENUE, Phone:(816) 231-2288  
SCHARHAG ARCHITECTS, Address:310 ARMOUR RD #202, Phone:(816) 221-9297  
KMZC PLUMBING, Address:301 W WEA, Phone:(913) 238-2583  
ATLAS MECHANICAL SERVICES INC, Address:26015 RA HWY, Phone:(913) 708-4695  
ELECTRICAL EXPRESS, Address:4225 E 53RD ST, Phone:(816) 739-9379  
KMZC PLUMBING, Address:301 W WEA, Phone:(913) 238-2583  
RED SUMMIT FAIR LLC, Address:1 E WASHINGTON ST STE 300  
Reviews
Review Type Outcome Est. Completion Date Completed
Sprinkler Plan Review Released for Construction 03/08/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
03/08/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Plans received on March 8, 2011.
Installation acceptance testing
Corrective Action Required
03/08/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule a flow and alarm test. Testing shall be completed before regular tenant business hours.
Misc
Corrective Action Required
03/08/2011

The sprinkler control valve and flow switch shall be properly marked to indicate the area they serve. Verified at inspection.
Alarm Plan Review Released for Construction 03/08/2011
Jim Eden
Construction documents - Fire protection systems
Corrective Action Required
03/08/2011

2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Installation acceptance testing
Corrective Action Required
03/08/2011

2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test. Call (816) 969-1300 to schedule a test. Tests shall be completed before or after regular tenant business hours.
Misc
Corrective Action Required
03/08/2011

2006 IFC 907.12 Duct smoke detectors. Duct smoke detectors shall be connected to the building’s fire alarm control panel when a fire alarm system is provided. Activation of a duct smoke detector shall initiate a visible and audible supervisory signal at a constantly attended location. Duct smoke detectors shall not be used as a substitute for required open area detection. Duct alarms shall be supervisory signals only without activation of interior horn/strobes. Verified at inspection.
Building Plan Review Rejected 12/13/2010 12/29/2010
Codes Admin
Misc
Corrective Action Required
12/13/2010

The occupant load used for this project is based on office area. It is the Codes Administration Departments practice to calculate the occupant load of any type of salon at 2 people per station. In this instance, since there are 24 stations and a wax room. The occupant load is 50. Action required - Make needed corrections to the occupant load.
Misc
Corrective Action Required
12/13/2010

The plans indicate that the rear wall of the space is a rated assembly but information on how the assembly is to be protected at penetrations has not been provided. Action required - Provide additional information for penetrations of the assembly.
Misc
Corrective Action Required
12/13/2010

The plans do not indicate what type of hardware will be installed on specific doors. Action required - Add additional information to the plans. Include the type of hardware to be installed and if closers are included.
Plumb - Separate facilities
Corrective Action Required
12/13/2010

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - As this is a B Occupancy with an occupant load of 50, separate men's and women's restrooms area required. Make needed corrections.
Misc
Corrective Action Required
12/13/2010

A plumbing riser diagram for the waste and vent has not been provided. Action required - Provide additional information.
Misc
Corrective Action Required
12/13/2010

A water distribution detail has not been provided. Action required - Provide additional information.
Plumb - Backflow general 608.3
Corrective Action Required
12/13/2010

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Specifications for the pedi chairs have not been provided. Show how this requirement will be met.
Misc
Corrective Action Required
12/13/2010

An electrical panel schedule has not been provided. Action required - Provide an electrical panel schedule.
Misc
Corrective Action Required
12/13/2010

Per footnote b of Table 403.3 of the 2006 IMC, mechanical exhaust required the recirculation of air from such spaces as permitted by Section 403.2.1 is prohibited (see Section 403.2.1, Items 1 and 3). Action required - Air in nail salons can not be recirculated. Return air can only be pulled from rooms that are separated by an assembly. Make needed corrections.
Misc
Corrective Action Required
12/13/2010

2006 IMC Table 403.3 footnote i - The required exhaust system shall capture the contaminants and odors at their source. Action required - It is the Codes Administration Departments practice to require the exhaust openings for nail stations at the table height of each station. Exhaust openings for pedi chairs are to be located within 12 inches of the floor and can be located in the walls behind the chairs. Make needed corrections.
Misc
Corrective Action Required
12/13/2010

The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff. Action required - This comment is for information purposes and will be verified on inspection.
Mech - Clothes dryers exhaust general
Corrective Action Required
12/13/2010

2006 IMC 504.1 - Installation. Clothes dryers shall be exhausted in accordance with the manufacturers instructions. Dryer exhaust systems shall be independent of all other systems and shall convey the moisture and any products of combustion to the outside of the building. Exception: This section shall not apply to listed and labeled condensing (ductless) clothes dryers. Action required - Information on the dryer vent is not indicated on the plans. Make needed corrections.
Bldg - Glazing - Human impact loads
Corrective Action Required
12/13/2010

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Provide additional information on the storefront system.
Internal Plan Review (Res) Approved 12/29/2010
Tracy Deister
Fire Plan Review Approved 01/03/2011 12/27/2010
Brian Austerman
Portable fire extinguishers - general
Corrective Action Required
12/22/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher at a conspicuous location. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
12/22/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for sprinkler alteration.
Construction documents for fire alarm systems
Corrective Action Required
12/22/2010

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for alarm system alteration.
Address numbers required
Corrective Action Required
12/22/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Verified at inspection.
Unlawful to occupancy
Corrective Action Required
12/22/2010

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved. For information only.
Building Plan Review Approved 01/03/2011 12/27/2010
Tracy Deister
Misc
Resolved
12/29/2010

The occupant load used for this project is based on office area. It is the Codes Administration Departments practice to calculate the occupant load of any type of salon at 2 people per station. In this instance, since there are 24 stations and a wax room. The occupant load is 50. Action required - Make needed corrections to the occupant load.
Misc
Resolved
12/29/2010

The plans indicate that the rear wall of the space is a rated assembly but information on how the assembly is to be protected at penetrations has not been provided. Action required - Provide additional information for penetrations of the assembly.
Misc
Resolved
12/29/2010

The plans do not indicate what type of hardware will be installed on specific doors. Action required - Add additional information to the plans. Include the type of hardware to be installed and if closers are included.
Plumb - Separate facilities
Resolved
12/29/2010

2006 IPC 403.2 - Separate facilities. Where plumbing fixtures are required, separate facilities shall be provided for each sex. (See code for possible exceptions.) Action required - As this is a B Occupancy with an occupant load of 50, separate men's and women's restrooms area required. Make needed corrections.
Misc
Resolved
12/29/2010

A plumbing riser diagram for the waste and vent has not been provided. Action required - Provide additional information.
Misc
Resolved
12/29/2010

A water distribution detail has not been provided. Action required - Provide additional information.
Plumb - Backflow general 608.3
Resolved
12/29/2010

2006 IPC 608.3 - Devices, appurtenances, appliances and apparatus. All devices, appurtenances, appliances and apparatus intended to serve some special function, such as sterilization, distillation, processing, cooling, or storage of ice or foods, and that connect to the water supply system, shall be provided with protection against backflow and contamination of the water supply system. Water pumps, filters, softeners, tanks and all other appliances and devices that handle or treat potable water shall be protected against contamination. Action required - Specifications for the pedi chairs have not been provided. Show how this requirement will be met.
Misc
Resolved
12/29/2010

An electrical panel schedule has not been provided. Action required - Provide an electrical panel schedule.
Misc
Resolved
12/29/2010

Per footnote b of Table 403.3 of the 2006 IMC, mechanical exhaust required the recirculation of air from such spaces as permitted by Section 403.2.1 is prohibited (see Section 403.2.1, Items 1 and 3). Action required - Air in nail salons can not be recirculated. Return air can only be pulled from rooms that are separated by an assembly. Make needed corrections.
Misc
Resolved
12/29/2010

2006 IMC Table 403.3 footnote i - The required exhaust system shall capture the contaminants and odors at their source. Action required - It is the Codes Administration Departments practice to require the exhaust openings for nail stations at the table height of each station. Exhaust openings for pedi chairs are to be located within 12 inches of the floor and can be located in the walls behind the chairs. Make needed corrections.
Misc
Carried Forward
12/29/2010

The bottom chord braces at the rtu(s) shall be welded once the units have been installed. This will need to be verified by the city inspection staff. Action required - This comment is for information purposes and will be verified on inspection.
Mech - Clothes dryers exhaust general
Resolved
12/29/2010

2006 IMC 504.1 - Installation. Clothes dryers shall be exhausted in accordance with the manufacturers instructions. Dryer exhaust systems shall be independent of all other systems and shall convey the moisture and any products of combustion to the outside of the building. Exception: This section shall not apply to listed and labeled condensing (ductless) clothes dryers. Action required - Information on the dryer vent is not indicated on the plans. Make needed corrections.
Bldg - Glazing - Human impact loads
Resolved
12/29/2010

2006 IBC 2406.1 - Human impact loads. Individual glazed areas, including glass mirrors, in hazardous locations as defined in Section 2406.3 shall comply with Sections 2406.1 through 2406.1.4. Action required - Provide additional information on the storefront system.
All comments have been addressed and are shown on the revised plans dated 12-21-2010.
Internal Plan Review (Res) Rejected 12/13/2010 12/13/2010
Mike Weisenborn
Fire Plan Review Rejected 12/13/2010 12/13/2010
Mike Weisenborn
Portable fire extinguishers - general
Corrective Action Required
12/09/2010

Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Action required: Provide a minimum of one 2A:10B:C fire extinguisher at a conspicuous location. Verified at inspection.
Construction documents - Fire protection systems
Corrective Action Required
12/09/2010

Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation. Action required: Provide shop drawings for sprinkler alteration.
Construction documents for fire alarm systems
Corrective Action Required
12/09/2010

Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions. Action required: Provide shop drawings for alarm system alteration.
Address numbers required
Corrective Action Required
12/09/2010

Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). Verified at inspection.
Unlawful to occupancy
Corrective Action Required
12/09/2010

Fire Department- 2006 IFC 901.5.1- Occupancy. It shall be unlawful to occupy any portion of a building or structure until the required fire detection, alarm and suppression systems have been tested and approved. For information only.
License Tax Codes Approved 12/13/2010 12/13/2010
Mike Weisenborn
Zoning Review Approved 12/13/2010 12/13/2010
Mike Weisenborn
This zoning was approved on a previous application.
Historical Preservation Review Approved 12/13/2010 12/06/2010
Mike Weisenborn
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Tenent Finish $136.28 $136.28 Paid 12/30/2010
8331507-Sewer Connection Fee $690.00 $690.00 Paid 12/30/2010
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
In-wall Inspection Not Ready 1/19/2011 at 12:00 AM 01/19/2011
Misc
Corrective Action Required
01/19/2011
AREAS OF WALL COVERED BEFORE INSPECTION
Underslab Plumbing Inspection - Commercial Not Ready 1/20/2011 at 12:00 AM 01/19/2011
Misc
Corrective Action Required
01/19/2011
PLUMBING PIPE NOT EXPOSED FOR INSPECTION
Underslab Electrical Inspection - Commercial Passed 1/20/2011 at 12:00 AM 01/20/2011
Underslab Plumbing Inspection - Commercial Failed 1/20/2011 at 12:00 AM 01/20/2011
Misc
Corrective Action Required
01/19/2011
-PROVIDE FLOOR DRAINS PER PLAN -WET-VENTING SHALL BE LIMITED TO BATH GROUP ONLY. ALL THE OTHER DRAINAGE SHALL CONNECT DOWNSTREAM OF THE WET-VENTED BATH GROUPS (ANYTHING FIXTURE/TRAP NOT WITHIN A BATH ROOM IS NOT WITHIN A BATH GROUP); OR INDIVIDUALLY VENT EACH FIXTURE -COMPLETE DRAINAGE CONNECTION TO STACK IN HALLWAY
Underslab Plumbing Inspection - Commercial Passed 1/21/2011 at 12:00 AM 01/21/2011
Misc
Resolved
01/21/2011
-PROVIDE FLOOR DRAINS PER PLAN -WET-VENTING SHALL BE LIMITED TO BATH GROUP ONLY. ALL THE OTHER DRAINAGE SHALL CONNECT DOWNSTREAM OF THE WET-VENTED BATH GROUPS (ANYTHING FIXTURE/TRAP NOT WITHIN A BATH ROOM IS NOT WITHIN A BATH GROUP); OR INDIVIDUALLY VENT EACH FIXTURE
In-wall Inspection Failed 1/21/2011 at 12:00 AM 01/21/2011
Misc
Corrective Action Required
01/19/2011
AREAS OF WALL COVERED BEFORE INSPECTION *DO NOT COVER WALL UNTIL APPROVED
P308 PIPING SUPPORT
Corrective Action Required
01/21/2011
SUPPORT PVC (2" OR SMALLER) AT MID-HEIGHT
Misc
Corrective Action Required
01/21/2011
INSTALL BLOCKINGS IN BATH ROOMS FOR GRAP BARS, INCLUDING THE 18" VERTICAL GRAP BAR. VERTICAL GRAP BAR SHALL BE INSTALLED 39-41" FROM BACK WALL AND 39-41" ABOVE FLOOR
E330 Metal-Clad Cable: Type MC
Corrective Action Required
01/21/2011
SECURELY FASTEN MC CABLE WITHIN 12" OF BOX AT EXPOSED WALL ON THE OTHER SIDE OF TENANT
In-wall Inspection Passed 1/25/2011 at 12:00 AM 01/25/2011
Misc
Resolved
01/25/2011
AREAS OF WALL COVERED BEFORE INSPECTION *DO NOT COVER WALL UNTIL APPROVED
P308 PIPING SUPPORT
Resolved
01/25/2011
SUPPORT PVC (2" OR SMALLER) AT MID-HEIGHT
Misc
Resolved
01/25/2011
INSTALL BLOCKINGS IN BATH ROOMS FOR GRAP BARS, INCLUDING THE 18" VERTICAL GRAP BAR. VERTICAL GRAP BAR SHALL BE INSTALLED 39-41" FROM BACK WALL AND 39-41" ABOVE FLOOR
E330 Metal-Clad Cable: Type MC
Resolved
01/25/2011
SECURELY FASTEN MC CABLE WITHIN 12" OF BOX AT EXPOSED WALL ON THE OTHER SIDE OF TENANT
Electrical Service Inspection Passed 1/28/2011 at 12:00 AM 01/28/2011
Above Ceiling Inspection Not Ready 2/25/2011 at 12:00 AM 02/25/2011
Misc
Corrective Action Required
02/25/2011
IDENTITY OF PERMIT HOLDER NOT SAME AS PARTY ACTING AS SUCH. NOT READY FOR INSPECTION.
Gas Service Inspection - Commercial Not Ready 2/25/2011 at 12:00 AM 02/25/2011
Misc
Corrective Action Required
02/25/2011
IDENTITY OF PERMIT HOLDER NOT SAME AS PARTY ACTING AS SUCH. NOT READY FOR INSPECTION.
Gas Piping Inspection - Commercial Failed 3/2/2011 at 12:00 AM 03/02/2011
Misc
Corrective Action Required
03/02/2011
SUPPORT ROOFTOP GAS PIPING NEAR ALL JOINTS AND CHANGES OF DIRECTION
Misc
Corrective Action Required
03/02/2011
ATTACH SLIP SHEET TO BOTTOM OF ALL WOOD BLOCKING FOR ROOFTOP PIPING (SCREW TO SIDE OF BLOCK -- NOT BOTTOM)
Misc
Corrective Action Required
03/02/2011
DIRT LEG CAP NOT REMOVABLE
Misc
Corrective Action Required
03/02/2011
PIPE CLAMPS OVER-SIZE AT 3/4" PIPING
Misc
Corrective Action Required
03/02/2011
ROOFTOP GAS PIPING NOT PAINTED
Gas Service Inspection - Commercial Failed 3/2/2011 at 12:00 AM 03/02/2011
Misc
Resolved
03/02/2011
IDENTITY OF PERMIT HOLDER NOT SAME AS PARTY ACTING AS SUCH. NOT READY FOR INSPECTION.
Misc
Corrective Action Required
03/02/2011
CORRECT ALL PIPING ISSUES
Misc
Partial Correction
03/02/2011
GAS PIPING PRESSURE TEST LOST 2 PSI DURING MONITORING PERIOD
Above Ceiling Inspection Not Ready 3/2/2011 at 12:00 AM 03/02/2011
Misc
Resolved
03/02/2011
IDENTITY OF PERMIT HOLDER NOT SAME AS PARTY ACTING AS SUCH. NOT READY FOR INSPECTION.
Misc
Corrective Action Required
03/02/2011
NO CEILING TILE TO BE PLACED PRIOR TO ABOVE-CEILING INSPECTION EXCEPT THOSE FEW WHERE DEVICES ARE MOUNTED.
Gas Piping Inspection - Commercial Passed 3/8/2011 at 12:00 AM 03/08/2011
Misc
Resolved
03/08/2011
SUPPORT ROOFTOP GAS PIPING NEAR ALL JOINTS AND CHANGES OF DIRECTION
Misc
Resolved
03/08/2011
ATTACH SLIP SHEET TO BOTTOM OF ALL WOOD BLOCKING FOR ROOFTOP PIPING (SCREW TO SIDE OF BLOCK -- NOT BOTTOM)
Misc
Resolved
03/08/2011
DIRT LEG CAP NOT REMOVABLE
Misc
Resolved
03/08/2011
PIPE CLAMPS OVER-SIZE AT 3/4" PIPING
Misc
Resolved
03/08/2011
ROOFTOP GAS PIPING NOT PAINTED
Gas Service Inspection - Commercial Passed 3/8/2011 at 12:00 AM 03/08/2011
Misc
Corrective Action Required
03/02/2011
CORRECT ALL PIPING ISSUES
Above Ceiling Inspection Partial 3/14/2011 3/14/2011 at 12:00 AM 03/14/2011
Misc
Resolved
03/14/2011
NO CEILING TILE TO BE PLACED PRIOR TO ABOVE-CEILING INSPECTION EXCEPT THOSE FEW WHERE DEVICES ARE MOUNTED.
Misc
Corrective Action Required
03/14/2011
OK TO COVER CEILING GRID AND ABOVE-CEILING SYSTEMS EXCEPT ABOVE THREE HANGING SOFFITS. A/E LETTER REQUIRED CERTIFYING ADAQUACY OF SUPPORT OF HANGING SOFFITS.
Sprinkler - Flow Test Passed 3/16/2011 at 12:00 AM 03/16/2011
Occupancy Inspection - Codes Commercial Not Ready 3/16/2011 at 12:00 AM 03/16/2011
Misc
Corrective Action Required
03/16/2011
READINESS FOR FINAL INSPECTION: FINAL INSPECTION POINTS DISCUSSED IN THE PAST NOT READY FOR INSPECTION
Occupancy Inspection - Fire Temporary C of O 3/16/2011 at 12:00 AM 03/16/2011
FD505.1 Address Numbers
Corrective Action Required
03/16/2011
New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In multi-tenant commercial buildings where tenants have multiple entrances located on different sisdes of the building, each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). 6" MINIMUM WHITE NUMBERS FOR THE FRONT, 4" MINIMUM BLACK NUMBERS FOR THE REAR DOOR
Misc
Corrective Action Required
03/16/2011
LABEL THE SPRINKLER SYSTEM VALVES WITH THE SUITE ADDRESS OF 930-P, FLOW ALARM AND THE TAMPER SWITCH.
FD906.1 Where Required- Fire Extinguishers
Corrective Action Required
03/16/2011
Portable fire extinguishers shall be installed in the following locations.1. In new and existing Group A, B, E, F, H, I , M, R-1, R-2, R-4 and S occupancies.Exception: In new and existing Group A, B and E occupancies equipped throughout with quick- response sprinklers, portable fire extinguishers shall be required only in locations specified in Items 2 through 6.2. Within 30 feet (9144 mm) of commercial cooking equipment.3. In areas where flammable or combustible liquids are stored, used or dispensed.4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 1415.1.5. Where required by the sections indicated in Table 906.1.6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. -------------------------------------- Portable fire extinguishers shall be installed in the following locations.1. In new and existing Group A, B, E, F, H, I , M, R-1, R-2, R-4 and S occupancies.Exception: In new and existing Group A, B and E occupancies equipped throughout with quick- response sprinklers, portable fire extinguishers shall be required only in locations specified in Items 2 through 6.2. Within 30 feet (9144 mm) of commercial cooking equipment.3. In areas where flammable or combustible liquids are stored, used or dispensed.4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 1415.1.5. Where required by the sections indicated in Table 906.1.6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. PROVIDE 1 MINIMUM SIZE 2A-10BC EXTINGUISHER, MOUNT ON THE WALL CLOSE TO AN EXIT WITH THE TOP NO HIGHER THAN 60" OFF THE FLOOR.
FD1004.3 Posting of occupant load.
Corrective Action Required
03/16/2011
Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST AN OCCUPANY LOAD OF 50 TOWARDS THE FRONT OF THE STORE.
Above Ceiling Inspection Passed 3/16/2011 at 12:00 AM 03/16/2011
Misc
Resolved
03/16/2011
OK TO COVER CEILING GRID AND ABOVE-CEILING SYSTEMS EXCEPT ABOVE THREE HANGING SOFFITS. A/E LETTER REQUIRED CERTIFYING ADAQUACY OF SUPPORT OF HANGING SOFFITS.
Alarm Test Passed 3/16/2011 at 12:00 AM 03/17/2011
Occupancy Inspection - Codes Commercial Temporary C of O 3/18/2011 at 12:00 AM 03/18/2011
Misc
Resolved
03/18/2011
READINESS FOR FINAL INSPECTION: FINAL INSPECTION POINTS DISCUSSED IN THE PAST NOT READY FOR INSPECTION
Misc
Corrective Action Required
03/18/2011
PROVIDE CERTIFIED REPORT OF AIR FLOW AT EXHAUST GRILLES
Misc
Corrective Action Required
03/18/2011
RE-PRINT LEGIBLE ELECTRICAL PANEL SCHEDULE
Occupancy Inspection - Fire Passed 3/18/2011 at 12:00 AM 03/18/2011
FD505.1 Address Numbers
Corrective Action Required
03/18/2011
New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In multi-tenant commercial buildings where tenants have multiple entrances located on different sisdes of the building, each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm). 6" MINIMUM WHITE NUMBERS FOR THE FRONT, 4" MINIMUM BLACK NUMBERS FOR THE REAR DOOR
Misc
Corrective Action Required
03/18/2011
LABEL THE SPRINKLER SYSTEM VALVES WITH THE SUITE ADDRESS OF 930-P, FLOW ALARM AND THE TAMPER SWITCH.
FD906.1 Where Required- Fire Extinguishers
Corrective Action Required
03/18/2011
Portable fire extinguishers shall be installed in the following locations.1. In new and existing Group A, B, E, F, H, I , M, R-1, R-2, R-4 and S occupancies.Exception: In new and existing Group A, B and E occupancies equipped throughout with quick- response sprinklers, portable fire extinguishers shall be required only in locations specified in Items 2 through 6.2. Within 30 feet (9144 mm) of commercial cooking equipment.3. In areas where flammable or combustible liquids are stored, used or dispensed.4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 1415.1.5. Where required by the sections indicated in Table 906.1.6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. -------------------------------------- Portable fire extinguishers shall be installed in the following locations.1. In new and existing Group A, B, E, F, H, I , M, R-1, R-2, R-4 and S occupancies.Exception: In new and existing Group A, B and E occupancies equipped throughout with quick- response sprinklers, portable fire extinguishers shall be required only in locations specified in Items 2 through 6.2. Within 30 feet (9144 mm) of commercial cooking equipment.3. In areas where flammable or combustible liquids are stored, used or dispensed.4. On each floor of structures under construction, except Group R-3 occupancies, in accordance with Section 1415.1.5. Where required by the sections indicated in Table 906.1.6. Special-hazard areas, including but not limited to laboratories, computer rooms and generator rooms, where required by the fire code official. PROVIDE 1 MINIMUM SIZE 2A-10BC EXTINGUISHER, MOUNT ON THE WALL CLOSE TO AN EXIT WITH THE TOP NO HIGHER THAN 60" OFF THE FLOOR.
FD1004.3 Posting of occupant load.
Corrective Action Required
03/18/2011
Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. POST AN OCCUPANY LOAD OF 50 TOWARDS THE FRONT OF THE STORE.
Occupancy Inspection - Codes Commercial Partial 3/22/2011 at 12:00 AM 03/22/2011
Misc
Corrective Action Required
03/18/2011
PROVIDE CERTIFIED REPORT OF AIR FLOW AT EXHAUST GRILLES
Misc
Corrective Action Required
03/18/2011
RE-PRINT LEGIBLE ELECTRICAL PANEL SCHEDULE
Occupancy Inspection - Codes Commercial Full C of O 3/25/2011 at 12:00 AM 03/25/2011
Misc
Resolved
03/25/2011
PROVIDE CERTIFIED REPORT OF AIR FLOW AT EXHAUST GRILLES
Misc
Resolved
03/25/2011
RE-PRINT LEGIBLE ELECTRICAL PANEL SCHEDULE
Documents & Images
Date Uploaded File Type Document Name
12/13/2010 Letter Plan Review Conditions
12/29/2010 Letter Plan Review Conditions
12/30/2010 Letter Building Permit
01/19/2011 Letter Inspection Summary
01/20/2011 Letter Inspection Summary
01/21/2011 Letter Inspection Summary
01/25/2011 Letter Inspection Summary
01/28/2011 Letter Inspection Summary
02/25/2011 Letter Building Permit
03/02/2011 Letter Inspection Summary
03/08/2011 Letter Inspection Summary
03/08/2011 Letter Fire (Alarm) Plan Review Notice
03/14/2011 Letter Inspection Summary
03/17/2011 Letter 20110317132207369.pdf
03/18/2011 Letter Temporary Certificate of Occupancy
03/25/2011 Letter Field Certificate of Occupancy
03/28/2011 Letter Final Certificate of Occupancy
06/26/2013 Letter Fire (Sprinkler) Plan Review
06/27/2013 Letter Plan Review Conditions
06/27/2013 Letter Plan Review Conditions
06/27/2013 Letter Fire Loss Reduction Form
06/27/2013 Letter Fire Loss Reduction Form
06/27/2013 Letter Fire Loss Reduction Form
06/27/2013 Letter Fire Loss Reduction Form
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home