Review Type |
Outcome |
Est. Completion Date |
Completed |
Sprinkler Plan Review
|
Released for Construction
|
|
02/03/2011
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Received February 3, 2011.
|
|
IFGC - Inspection, testing and maintenance - alarm and extinguishing systems 901.6
Corrective Action Required
2006 IFC 901.6- Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Not required fire protection systems and equipment shall be inspected, tested and maintained or removed.
Action required: The existing system shall have documentation of a current annual inspection. Verified at inspection
|
|
Misc
Corrective Action Required
The scale shown on the drawing does not appear to be the same as the drawing.
|
|
Misc
Corrective Action Required
Confirm there is adequate coverage along the north side of the open office.
Action required: Add additional head(s) to maintain coverage.
|
|
|
Alarm Plan Review
|
Released for Construction
|
|
02/03/2011
|
|
Jim Eden
|
|
Construction documents for fire alarm systems
Corrective Action Required
2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations.
Information provided January 31, 2011
|
|
Installation acceptance testing
Corrective Action Required
2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action required: Call (816) 969-1300 to schedule a test.
|
|
Misc
Corrective Action Required
Smoke detection is required over the new FACP by NFPA 72.
Action required: Provide smoke detection over the FACP. Verified at inspection.
|
|
Misc
Corrective Action Required
The new panel shall be connected to, and communicate with the existing FACP. Any alarm in the building shall activate both systems. Reseting one panel shall reset both panels.
Action required: System operation will be verified at testing.
|
|
|
Internal Plan Review (Res)
|
Approved
|
|
12/10/2010
|
|
Mike Weisenborn
|
|
|
Building Plan Review
|
Approved
|
12/10/2010
|
12/10/2010
|
|
Mike Weisenborn
|
|
Misc
Corrective Action Required
A License Tax application completed by the contractor must be submitted to the City of Lee's Summit, Codes Administration Department, and any applicable License Tax paid prior to issuing a building permit.
Action required - The general contractor shall complete a license tax application and submit it prior to permit issuance. The calculated license tax shall be paid either prior to permit issuance or it may be deferred to payment prior to receiving any type of occupancy.
|
|
|
License Tax Codes
|
Approved
|
12/10/2010
|
12/10/2010
|
|
Mike Weisenborn
|
|
|
Zoning Review
|
Approved
|
12/10/2010
|
12/10/2010
|
|
Mike Weisenborn
|
|
|
Historical Preservation Review
|
Approved
|
12/10/2010
|
12/10/2010
|
|
Mike Weisenborn
|
|
|
Fire Plan Review
|
Approved
|
12/10/2010
|
12/09/2010
|
|
Jim Eden
|
|
Construction documents - Fire protection systems
Corrective Action Required
Fire Department- 2006 IFC 901.2- Construction documents. The fire code official shall have the authority to require construction documents and calculations for all fire protection systems and to require permits be issued for the installation, rehabilitation or modification of any fire protection system. Construction documents for fire protection systems shall be submitted for review and approval prior to system installation.
Action required: Provide shop drawings for any alteration of the sprinkler system needed to maintain adequate coverage per NFPA 13.
|
|
Construction documents for fire alarm systems
Corrective Action Required
Fire Department- 2006 IFC 907.1.1- Construction documents. Construction documents for fire alarm systems shall be submitted for review and approval prior to system installation. Construction documents shall include, but not be limited to, all of the following: 1. .A floor plan which indicates the use of all rooms. 2. Locations of alarm-initiating and notification appliances. 3. Alarm control and trouble signaling equipment. 4. Annunciation. 5. Power connection. 6. Battery calculations. 7. Conductor type and sizes. 8. Voltage drop calculations. 9. Manufacturers, model numbers and listing information for equipment, devices and materials. 10. Details of ceiling height and construction. 11. The interface of fire safety control functions.
Action required: Provide a layout plan of notification appliances in the space.
|
|
Installation acceptance testing
Corrective Action Required
Fire Department- 2006 IFC 901.5- Installation acceptance testing. Fire detection and alarm systems, fire-extinguishing systems, fire hydrant systems, fire standpipe systems, fire pump systems, private fire service mains and all other fire protection systems and appurtenances thereto shall be subject to acceptance tests as contained in the installation standards and as approved by the fire code official. The fire code official shall be notified before any required acceptance testing. The fire code official shall be notified 48 hours before any required acceptance test.
Action required: Call (816) 969-1300 to schedule an alarm test. The test shall be completed when it does not interupt other tenants in the building.
|
|
Address numbers required
Corrective Action Required
Fire Department- 2006 IFC 505.1- Address numbers. New and existing buildings shall have approved address numbers, building numbers or approved building identification placed in a position that is plainly legible and visible from the street or road fronting the property. These numbers shall contrast with their background. In Multi-tenant commercial building where tenants have multiple entrances located on different sides of the building , each door shall be addressed. Address numbers shall be Arabic numerals or alphabet letters. Numbers shall be a minimum of 4 inches (102 mm) high with a minimum stroke width of 0.5 inch (12.7 mm).
Action required: All exterior doors and doors from common vestibules to the space shall be addressed . Verified at inspection.
|
|
Portable fire extinguishers - general
Corrective Action Required
Fire Department- 2006 IFC 906.2 - General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
Action required: Provide a minimum of one 2A:10B C fire extinguisher in the space. Verified at inspection.
|
|
Knox box required
Corrective Action Required
Fire Department- 2006 IFC 506.1- Where required. Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type and shall contain keys to gain necessary access as required by the fire code official.
Action required: Provide a key for the Knox Box for access to the GAP. Completed at inspection.
|
|
Misc
Corrective Action Required
The construction type is listed as Type I. This needs to be corrected to Type VB.
|
|
Misc
Corrective Action Required
Fire Department- IFC 008.1.3.4 Access-controlled egress doors.
The entrance doors in a means of egress in buildings with an occupancy in Group A, B, E, M, R-1 or R-2 and entrance doors to tenant spaces in occupancies in Groups A, B, E, M, R-1 and R-2 are permitted to be equipped with an approved entrance and egress access control system which shall be installed in accordance with all of the following criteria:
1. A sensor shall be provided on the egress side arranged to detect an occupant approaching the doors. The doors shall be arranged to unlock by a signal from or loss of power to the sensor.
2. Loss of power to that part of the access control system which locks the doors shall automatically unlock the doors.
3. The doors shall be arranged to unlock from a manual unlocking device located 40 inches to 48 inches (1016 mm to 1219 mm) vertically above the floor and within 5 feet (1524 mm) of the secured doors. Ready access shall be provided to the manual unlocking device and the device shall be clearly identified by a sign that reads “PUSH TO EXIT.” When operated, the manual unlocking device shall result in direct interruption of power to the lock—independent of the access control system electronics—and the doors shall remain unlocked for a minimum of 30 seconds.
4. Activation of the building fire alarm system, if provided, shall automatically unlock the doors, and the doors shall remain unlocked until the fire alarm system has been reset.
5. Activation of the building automatic sprinkler or fire detection system, if provided, shall automatically unlock the doors. The doors shall remain unlocked until the fire alarm system has been reset.
6. Entrance doors in buildings with an occupancy in Group A, B, E or M shall not be secured from the egress side during periods that the building is open to the general public.
Action required: Access controlled doors shall be installed and operate as listed above. Provide a detail for installation. Verified at inspection.
|
|
|