| Review Type |
Outcome |
Est. Completion Date |
Completed |
|
Traffic Review
|
Corrections
|
03/06/2026
|
03/06/2026
|
|
|
Erin Ralovo
|
|
|
Corrective Action Required
The connection at Rosemary Court should be a standard intersection.
|
|
|
Corrective Action Required
A Right Turn lane on Colbern will be required. Access Management Code requires 250 FT of turn lane and a 150 FT of taper. With the restriction of the drive to the apartments Staff would consider a shorter taper.
|
|
|
|
|
Planning Review
|
Corrections
|
03/06/2026
|
03/06/2026
|
|
|
Adair Bright
|
|
|
Corrective Action Required
Provide a comment response letter.
|
|
|
Corrective Action Required
SHEET C0.0. Revise the Site Data table - building setbacks are determined by the approved PDP within PMIX.
|
|
|
Corrective Action Required
SHEET C0.1. Update based on minor plat comments.
|
|
|
Corrective Action Required
Sheet C1.0. The building setback to the north shall be dimensioned on the site plan.
|
|
|
Corrective Action Required
SHEET L100. If using the existing trees to meet the open yard landscaping requirements (UDO Sec. 8.790.B), refer to UDO Sec. 8.750.C for minimum planting size requirements.
|
|
|
Corrective Action Required
SHEET L100. Update the sheet to include the open yard requirements outlined in UDO Sec. 8.790.B.
|
|
|
Corrective Action Required
SHEET AS1.20. Just want to confirm, the sign is included because you are requesting to exceed the maximum quantity through the PDP, correct?
|
|
|
Corrective Action Required
SHEET A5.00. A material schedule shall be provided that also identifies material classes per UDO Sec. 8.060 and percentages of facade that those materials cover. The building is classified as a civic building and shall meet all design standards outlined in UDO Sec. 8.080.B.
|
|
|
Corrective Action Required
SHEET ES1.10. Manufacturer's specification sheets shall be submitted per UDO Sec. 2.310.4.r.
|
|
|
Corrective Action Required
MISCELLANEOUS. The floor plans can be removed.
|
|
|
Corrective Action Required
MISCELLANEOUS. If existing trees are being utilized to fulfill landscaping requirements, submit a separate plan sheet detailing the trees to remain and their caliper size.
|
|
|
|
|
Engineering Review
|
Corrections
|
03/06/2026
|
03/03/2026
|
|
|
Gene Williams, P.E.
|
|
|
Corrective Action Required
Grading is shown within the stream buffer on Sheet C3.0. No grading is allowed within a stream buffer easement unless a waiver is granted by the City Engineer.
|
|
|
|
|
Fire Review
|
Approved with Conditions
|
03/06/2026
|
02/23/2026
|
|
|
Jim Eden
|
|
|
Code Statement
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
|
|
|
Fire Lanes - Marking
Corrective Action Required
IFC 503.3 - Where required by the fire code official, approved signs or other approved notices or markings that include the words NO PARKING—FIRE LANE shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. The means by which fire lanes are designated shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
All accesses to the front and side of the building shall be posted Fire Lane-No Parking.
|
|
|
FDC
Corrective Action Required
IFC 903.3.7 - Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official.
Show the location of the FDC on the building.
|
|
|
|