Summary
PL2022374
Lee's Summit North High School - Robotics Facility
Commercial Final Development Plan
Commercial Final Development Plan
Approved
10/21/2022
REORGANIZED SCHOOL DIST NO 7
New 7,100 square foot robotics facility
Locations
Contacts
REORGANIZED SCHOOL DIST NO 7, Address:600 SE MILLER  
MULTISTUDIO, Address:4200 PENNSYLVANIA AVE  
KAW VALLEY ENGINEERING INC, Address:14700 W 114TH TERR, Phone:(913) 894-5150  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review Approved with Conditions 12/02/2022 12/02/2022
Gene Williams, P.E.
DE Engineers Estimate
Corrective Action Required
12/02/2022

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)). These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $4,252.13
DE Contact Field Eng. Inspector
Corrective Action Required
12/02/2022

Prior to the commencement of any construction activities, the Contractor shall contact Field Engineering Inspections at (816) 969-1200 to coordinate a preconstruction meeting / conference with the assigned Field Engineering Inspector.
Corrective Action Required
12/02/2022

Review of the waiver is currently under review by the City Engineer. It is anticipated the waiver shall be approved. If not, it may be possible that detention shall be requred or other measures for the new improvements. If this occurs, a revision to the Final Development Plan shall be required.
Building Codes Review No Comments 12/02/2022 12/01/2022
Joe Frogge
Miscellaneous Correction
Resolved
12/01/2022

Water service backflow to be inside building. 11/17/22 - still shown in yard on C500-B 11/23/22 - profile on C800-B still references exterior backflow and there is no information about meter.
Miscellaneous Correction
Resolved
12/01/2022

Specify size, type, and location of water meter. 11/17/22 - not found in plans 11/23/22 - Not found in plans
Traffic Review No Comments 12/02/2022 11/23/2022
Mike Weisenborn
Fire Review Approved with Conditions 12/02/2022 11/23/2022
Mike Weisenborn
Code Statement
Corrective Action Required
11/23/2022

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Knox Locks
Corrective Action Required
11/23/2022

IFC 506.1 - Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. 506.1.1 Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. A Knox padlock sall be provided on the gate if not already there.
Planning Review No Comments 12/02/2022 11/23/2022
Mike Weisenborn
Building Codes Review Corrections 11/18/2022 11/21/2022
Joe Frogge
Miscellaneous Correction
Resolved
11/17/2022

Sanitary connection at manhole not allowed.
Miscellaneous Correction
Corrective Action Required
11/11/2022

Water service backflow to be inside building. 11/17/22 - still shown in yard on C500-B
Miscellaneous Correction
Corrective Action Required
11/11/2022

Specify size, type, and location of water meter. 11/17/22 - not found in plans
Engineering Review Corrections 11/18/2022 11/18/2022
Gene Williams, P.E.
Corrective Action Required
11/17/2022

The Design Criteria Modification Request should be combined into one (1) single pdf file with: 1) the template form, 2) the summary discussion (sealed), and 3) exhibits. Please combine these into one (1) single pdf file.
Corrective Action Required
11/17/2022

The 6 inch fire line appears to be connected to a private water line. Does this private water main connect to the public 12 inch main along Douglas St. with a backflow vault and backflow assembly? If not, a backflow vault and backflow assembly may be required near the 12 inch main near Douglas St. Please review and revise the drawings as necessary, as it appears there is no backflow vault near the 12 inch public main near Douglas St. If required by Water Utilities, this backflow vault and backflow assembly should be located outside of right of way and outside any public easements. Please see the Design and Construction Manual for more specific requirements for fire lines and backflow vaults, or contact me for further discussion.
Corrective Action Required
11/17/2022

A 2 inch domestic service line is shown connecting to what appears to be a private water main. It also shows an in-line backflow vault and backflow preventor, which should be shown within the building and not outside the building. Backflow vaults installed outside a building are generally limited to private fire lines rather than domestic water service lines. Please show the location of the water meter, including sizing information, near the public water main along Douglas St. (i.e., the 12 inch line near Douglas St.). No backflow vault is desired or required for a domestic service line, so please eliminate the backflow vault from the domestic line. Please revise as appropriate.
Corrective Action Required
11/17/2022

A two (2) inch domestic water service line is shown, but it is questionable whether this size line is appropriate for the building shown. Are you intending on installing a 2 inch meter? It would appear a 5/8 inch meter would be sufficient in this instance, and it would appear a 2 inch line would not be required. Please review and revise as appropriate.
Corrective Action Required
11/17/2022

Please show the location of the water meter and the size of the water meter. It should be located near the public 12 inch line near Douglas St., and within right of way or an easement and in an area readily-accessible to Water Utilities staff. If no easement is located in the area of the water meter, a separately-recorded water line easement may be dedicated.
Corrective Action Required
11/17/2022

It appears a water meter already exists near the private fire hydrant. Is there a reason why an additional water meter is being proposed? It may be possible to install a tee after the existing water meter, and utilize the existing water meter to service the new building. Please evaluate and revise as appropriate.
Corrective Action Required
11/17/2022

There were references to W(R) on the plan sheets (i.e., Water Line "Record"). What does this term refer to? We are seeing no such water line in our records. Please evaluate and revise as appropriate.
Corrective Action Required
11/18/2022

Due to the apparent confusion regarding water lines and fire lines, please contact me for further information. Alternatively, please consult the Design and Construction Manual "Water Mains" for further information regarding fire lines, domestic service lines, backflow vaults and backflow assemblies, etc.
Corrective Action Required
11/18/2022

Please revise the cost estimate as appropriate after making the revisions to the plans.
Planning Review No Comments 11/18/2022 11/17/2022
Hector Soto Jr.
Traffic Review No Comments 11/18/2022 11/11/2022
Scott Ready
Fire Review Approved with Conditions 11/18/2022 11/11/2022
Scott Ready
Code Statement
Corrective Action Required
11/11/2022

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Knox Locks
Corrective Action Required
11/11/2022

IFC 506.1 - Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. 506.1.1 Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. A Knox padlock sall be provided on the gate if not already there.
Engineering Review Corrections 11/04/2022 11/04/2022
Gene Williams, P.E.
Corrective Action Required
11/04/2022

The waiver request is not a construction modification request, but rather, a design modification request. Please resubmit the correct form.
Corrective Action Required
11/04/2022

Please include the project number on the design modification form. It is project number PL2022374.
Corrective Action Required
11/04/2022

Please ensure the other waiver requests for Lee's Summit West High School and the main Lee's Summit High School include the correct form for the waiver. It is not a Construction Modification Request, but rather, a Design Criteria Modification Request. This form shall be sent separately.
Corrective Action Required
11/04/2022

The plan package included Lee's Summit West High School improvements. Please eliminate these from the application package, and only include those pertaining to Lee's Summit North High School.
Corrective Action Required
11/04/2022

Normally, a general overview sheet is included to show where the improvements are being proposed. I could not find such a general layout sheet. Please provide a general layout sheet of the campus.
Corrective Action Required
11/04/2022

No further review was conducted, pending receipt of a plan package that can be reviewed from the perspective of: 1) one project (i.e., Lee's Summit North High School), and 2) an overview sheet showing where the proposed building is located in relation to other buildings. At present, I cannot determine where the building addition is being proposed with certainty.
Traffic Review No Comments 11/04/2022 11/04/2022
Brad Cooley, P.E., RSPI
Fire Review Approved with Conditions 11/04/2022 11/02/2022
Jim Eden
Code Statement
Corrective Action Required
11/07/2022

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Knox Locks
Corrective Action Required
11/02/2022

IFC 506.1 - Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official. 506.1.1 Locks. An approved lock shall be installed on gates or similar barriers when required by the fire code official. A Knox padlock sall be provided on the gate if not already there.
Planning Review Corrections 11/04/2022 11/01/2022
Hector Soto Jr.
Corrective Action Required
11/01/2022

SITE DATA TABLE (Sheet C100-B). - Correct the listed property zoning from PO to R-1 (Single-family Residential). - Fill in the setback information for Front (30' per plat); Rear (30'); and side (30'). - Provide building square footage for the existing school; the proposed robotics building; and total (existing + proposed). - List the number of existing classrooms; the number of proposed classrooms (from the addition); and total classrooms (existing + proposed). - List the number of existing parking parking spaces and the number of required parking spaces. The number of required parking spaces for a high school is calculated at a rate of 6 spaces per total classrooms.
Corrective Action Required
11/01/2022

ROOF-TOP UNITS. In order to comply with City ordinances, all RTUs shall be fully screened from view by raising building parapet heights at least equal to the height of the units being screened.
Corrective Action Required
11/01/2022

EXTERIOR MATERIALS. Label the proposed exterior building material colors.
Corrective Action Required
11/01/2022

LIGHTING. Identify which light fixture(s) listed on the fixture schedule on Sheet E700 will be used on the building exterior. All exterior lighting fixtures shall comply with UDO Sections 8.220 and 8.260.
Building Codes Review Corrections 11/04/2022 10/26/2022
Joe Frogge
Miscellaneous Correction
Corrective Action Required
10/26/2022

Sanitary connection at manhole not allowed.
Miscellaneous Correction
Corrective Action Required
10/26/2022

Water service backflow to be inside building.
Miscellaneous Correction
Corrective Action Required
10/26/2022

Specify size, type, and location of water meter.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $725.00 $725.00 Paid 11/07/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
10/21/2022 Application Form Final Development Plan_LSN_Signed
10/21/2022 Plans 220909_LSW_LSN Bid Set_REDUX
10/21/2022 Engineer Report/Study 20220909 LSNHS Robotics Stormwater Compliance Letter (R0)
10/28/2022 Engineers Estimate LSNHS Robotics -EPEOPCC 20221027
11/04/2022 Letter Applicant Letter - FDP (DFDP)
11/04/2022 Letter Applicant Letter - FDP (DFDP)
11/07/2022 Receipt Receipt for transaction: 2022-008760
11/11/2022 Engineer Report/Study 22-5545 Lee's Summit North Robotics Addition Geotech Report
11/11/2022 Plans 221110 LSN Permit Set
11/11/2022 Letter Lee's Summit North FDP Responses
11/11/2022 Letter LSN DCM Design Waiver Request 11-08-2022
11/11/2022 Letter LSR7 Robotics - ASI 001-ISS 003 - LSN Narrative
11/21/2022 Letter Applicant Letter - FDP (DFDP)
11/23/2022 Letter 22-1123_Lee Summit North FDP Comments
11/23/2022 Plans 221110 LSN Permit Set
11/23/2022 Waiver/Modification Document 20221122 LSNHS Robotics Stormwater Compliance Letter (R1)
11/23/2022 Engineers Estimate LSNHS Robotics -EPEOPCC 20221122
11/28/2022 Plans 221128 LSN Permit Set
11/28/2022 Letter Lee Summit North FDP Comments_11282022
12/02/2022 Activity Document Copy of FeeWSLSHSNORTHRoboticsFDP0
12/02/2022 Waiver/Modification Document WAIVER REQUEST UNSIGNED
12/02/2022 Email EMAIL TO CITY ENGINEER DEC2022
12/02/2022 Letter Applicant Letter - FDP (DFDP)
12/02/2022 Approved Plans APPROVED LSN ROBOTICS CIVIL
12/13/2022 Waiver/Modification Document SIGNED WAIVER STORMWATER
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home