PL2022246
THE VILLAS OF CHAPEL RIDGE 2ND PLAT, LOTS 43-74 AND TRACTS C-1 AND D-1 - PUBLIC WATER
Engineering Plan Review
Engineering Plan Review
Approved
06/27/2022
CHOYCE LLC
Locations
Contacts
CHOYCE LLC, Address:PO BOX 847  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review Approved with Conditions 03/04/2025 02/25/2025
Gene Williams, P.E.
Engineering Review Corrections 02/25/2025 02/24/2025
Gene Williams, P.E.
Corrective Action Required
02/24/2025

Unit costs are very low compared to other projects I have reviewed for pipe, valves, connection to existing, and fire hydrants. I can send an example from a project with 5 times the scope, and 8 inch C900 pipe in 2022 was estimated at $45 a foot at that time. In 2025 dollars, it would be even higher. None of the unit costs shown in your estimate appear realistic, and instead appear to be based on very old data. Correction required.
Engineering Review Corrections 02/21/2025 02/14/2025
Gene Williams, P.E.
Corrective Action Required
02/14/2025

Estimate appears to be identical to the one prepared 3 years ago. There has been approximately 20% inflation since that time. Correction required.
Engineering Review Approved with Conditions 02/19/2025 02/13/2025
Gene Williams, P.E.
Engineering Review Approved with Conditions 05/10/2023 05/09/2023
Gene Williams, P.E.
Engineering Review Corrections 03/27/2023 03/31/2023
Gene Williams, P.E.
Corrective Action Required
03/31/2023

Please refer to comment #2 in the previous applicant letter. Although you have shown a valve on the south side of Dick Howser, it is in the middle of a sidewalk with no justification for placing within a sidewalk. Please move the valve to the north within the greenspace between the sidewalk and Dick Howser Dr. For clarity purposes, it may be beneficial to remove the rectangular symbol around the water main, because this appears to be a casing carrier pipe which is not needed or desired by Water Utilities for water mains. Please revise.
Engineering Review Corrections 08/31/2022 08/31/2022
Gene Williams, P.E.
Corrective Action Required
08/31/2022

Sheet C.501 has been altered since the last submittal to include dashed circles. Please remove these circles, as they do not appear to serve any purpose.
Corrective Action Required
08/31/2022

Please refer to previous applicant letter. Details are provided for the connection to the existing 12 inch line on the north side of Dick Howser Dr., but we are now allowing 12 inch gate valves on 12 inch lines rather than butterfly valves. However, there is already an existing valve on the 12 inch leg near the connection point, so no additional valve is desired on the 12 inch line. We will require 1) one (1) 8 inch gate valve on the 8 inch line on the north side of Dick Howser, and 2) one (1) gate valve on the south side of Dick Howser Dr. This is required to isolate the line beneath the roadway in the event of repair. Please review and revise as appropriate.
Corrective Action Required
08/31/2022

Troon Dr. Fire Hydrant Relocation: Please refer to previous applicant letter comment #3. I requested you show the location of the relocated fire hydrant. The note states it will be made permanent, with no indication of where they are to be installed other than "2 feet behind the back of curb". This is not sufficient. Please show the location where this will be placed on the plan view. Please use bold linetype since this is a proposed feature. Please review and revise as appropriate.
Corrective Action Required
08/31/2022

Independence Ave. Fire Hydrant Relocation: Although the relocated fire hydrant has been notated, the location on the plan view is vague. It appears greyed-out, and would imply an existing feature. Please make this bold, and include a label showing in no uncertain terms this is the location of the relocated fire hydrant. Please revew and revise as appropriate.
Corrective Action Required
08/31/2022

Connection Point on Troon Dr. and Independence Ave: The linework is not accurate on the existing water main to the new water line connection points for both connections. The connection points appear to be connected to the fire hydrants to be relocated rather than the main. Please use standard drafting standards to show a clear indication of where the proposed line will be connected to the existing main. Please review and revise as appropriate.
Corrective Action Required
08/31/2022

The location of the existing valves on the existing 12 inch water line on the north side of Dick Howser Dr. are not accurate, and are also not shown on the water main itself. Please ensure the location of these existing valves are accurate and located on the line itself, and ensure there is adequate clearance between these valves and the new connection point. Please review, evlauate, and revise.
Corrective Action Required
08/31/2022

The note concerning shut-down of the water main implies the City shall be responsible for notification of residents. Please revise this note. In addition to what has already been shown on this note, please add the following: "Contractor shall be responsible for notification of affected water customers in accordance with the City of Lee's Summit Design and Construction Manual" or equivalent language.
Engineering Review Corrections 07/15/2022 07/15/2022
Gene Williams, P.E.
Corrective Action Required
07/15/2022

General Loyout sheet is missing the connection to the water main on the north side of Dick Howser Dr. Please show the general location of the connection point on the General Layout sheet.
Corrective Action Required
07/15/2022

Sheet C.503: The conection to the 12 inch water main on the north side of Dick Howser Dr. is not shown. All details concerning this connection shall be shown, and boring beneath Dick Howser Dr. shall be required. Please revise as appropriate.
Corrective Action Required
07/15/2022

Show the location where the existing fire hydrants will be relocated. The note says to make them permanent, with no corresponding notes or location showing where they are to be installed. Please revise as appropriate.
Corrective Action Required
07/15/2022

Informational Comment: Casing pipe for the connection beneath Dick Howser Dr. is not desired.
Corrective Action Required
07/15/2022

A trenching and backfill detail was missing. Please ensure the new standard of 12 inch aggregate over the top of pipe is shown on the detail.
Corrective Action Required
07/15/2022

Ensure a note is provided stating that a cut-in tee is required on the 12 inch connection point on the north side of Dick Howser Dr.
Corrective Action Required
07/15/2022

It appears an additional fire hydrant is warranted along Line 1. Please review and revise as appropriate.
Corrective Action Required
07/15/2022

It appeears a 45 degree bend fitting is required at station 0+00 on line 2.
Hearings

There are no hearings for this planning application.

Documents & Images
Date Uploaded File Type Document Name
06/27/2022 Plans VILLAS WATER
07/15/2022 Letter DE-Comment Letter (Engineering Plans)
08/17/2022 Letter Comment Letter WATER 8-12-2022
08/17/2022 Engineers Estimate COST ESTIMATE WATER 8-12-2022
08/17/2022 Plans WATER 8-17-2022
08/31/2022 Letter DE-Comment Letter (Engineering Plans)
03/13/2023 Plans WATER 20230303
03/13/2023 Letter Comment Letter WATER 3-7-23
03/31/2023 Letter DE-Comment Letter (Engineering Plans)
05/02/2023 Plans APPROVED PLANS
05/02/2023 Letter Comment Letter WATER 230418
05/09/2023 Email STKY APPROVAL MAY2023
05/15/2023 Activity Document MDNR Concurrence Letter - Water Villas
05/15/2023 Activity Document Villas of Chapel Ridge 2nd Plat - Water Model
05/18/2023 Activity Document WaterModelResultsMay2023
05/18/2023 Activity Document MDNR Concurrence Letter - Water Villas
01/17/2025 Email MDNR COMMENT WATER
01/31/2025 Email WRONG PLAN SET EMAIL_PL2022246
02/03/2025 Plans Water Line Plans_PL2022246
02/03/2025 Letter MDNR Letter_PL2022246
02/05/2025 Plans Revised Water Line Plans_PL2022246
02/13/2025 Plans Stamped Approved Plans FDP Water_PL2022246
02/14/2025 Engineers Estimate Engineering Cost Estimate_Rev1_PL2022246
02/14/2025 Email Approval Email with Conditions_PL2022246
02/14/2025 Letter DE-Comment Letter (Engineering Plans)
02/17/2025 Engineers Estimate Engineering Cost Estimate_Rev2_PL2022246
02/25/2025 Engineers Estimate Engineering Cost Estimate_Rev3_PL2022246
02/25/2025 Activity Document Engineering Fee Worksheet_PL2022246
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home