Planning Application Status

PL2021443




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2021443
Summit Creek 1st Plat - ESC
Engineering Plan Review
Engineering Plan Review
Void
11/10/2021
291 INVESTORS LLC
APPLICATION EXPIRED - Mike Weisenborn 01/10/2024 9:23 AM
Locations
Contacts
291 INVESTORS LLC, Address:900 W 48TH ST  
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review Approved with Conditions 01/18/2022 01/18/2022
Sue Pyles, P.E.
Engineering Review Corrections 01/07/2022 01/07/2022
Sue Pyles, P.E.
Corrective Action Required
01/07/2022

Why isn’t the proposed detention basin serving as a sediment basin? Please include as a BMP or provide explanation why it isn’t possible. Include the appropriate standard details, as well.
Corrective Action Required
01/07/2022

Please include the following, prominently highlighted: “NOTE: CONTRACTOR TO CONSTRUCT STORMWATER MANAGEMENT FACILITIES, SPECIFICALLY THOSE FEATURES RELATED TO DETENTION, PRIOR TO ANY LAND DISTURBANCE OF THE SITE AND PRIOR TO THE CONSTRUCTION OF ANY OTHER SITE DEVELOPMENT WORK AS NOT TO EFFECT DOWNSTREAM NEIGHBORS WITH UNDETAINED STORMWATER DISCHARGE.”
Corrective Action Required
01/07/2022

Please provide ESC for the cul-de-sac construction at the north end of Paddock Drive (see street/storm comments).
Corrective Action Required
01/07/2022

Please update the Summary of Quantity table and the Engineer’s Estimate based revisions made due to the comments above.
Engineering Review Corrections 12/10/2021 12/10/2021
Loic Nguinguiri, E.I.
Corrective Action Required
12/10/2021

Include the developer’s direct telephone number.
Corrective Action Required
12/10/2021

Revise Final Development Plan (FDP) to Erosion and Sediment Control (ESC) Plan within the headline. Make sure to also add “1st plat” to the title.
Corrective Action Required
12/10/2021

Show/label the FEMA 100-year floodplain boundary (zone AE) within the set of plans. Additional floodplain development permit may be required in order to perform grading work within the floodplain limits.
Corrective Action Required
12/10/2021

On the ESC phase 1 plan sheet, are the two (2) discontinuities along the northern silt fence barrier made on purpose? if not, please add.
Corrective Action Required
12/10/2021

Provide ESC protection to the field inlet located northeast of lot 249 along the southern border.
Corrective Action Required
12/10/2021

Label/show proposed grading contour elevations over the panoply of circular lines shown to the northeast within the project site.
Corrective Action Required
12/10/2021

Increase the font size of the grading contour elevations, labeled on the grading plan sheet, in order to improve and ease readability.
Corrective Action Required
12/10/2021

Please note that no review of the detention basin design is included with this review, and that grading was looked at for ESC purposes only.
Corrective Action Required
12/10/2021

Please make sure to obtain the appropriate permission or temporary construction easement to perform grading work outside of the property limits, as necessary.
Corrective Action Required
12/10/2021

Provide a SWPPP report and a Missouri DNR permit.
Corrective Action Required
12/10/2021

Please provide an Engineer’s Opinion of Probable Construction Cost (EOOPCC) sheet.
Hearings

There are no hearings for this planning application.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your Planning Application