PL2021442




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2021442
Summit Creek 1st Plat - Streets, Storm, Mass Grading
Engineering Plan Review
Engineering Plan Review
Void
11/10/2021
291 INVESTORS LLC
APPLICATION EXPIRED - Mike Weisenborn 01/10/2024 9:22 AM
Locations
Contacts
291 INVESTORS LLC, Address:900 W 48TH ST  
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review Corrections 03/18/2022 03/16/2022
Sue Pyles, P.E.
Corrective Action Required
03/16/2022

Please review the Engineer's Estimate quantities. Spot checks found many discrepencies between estimate and plans for storm sewer items. Review and revise as needed.
Traffic Review No Comments 03/18/2022 03/15/2022
Brad Cooley, P.E., RSPI
Engineering Review Corrections 03/08/2022 03/08/2022
Sue Pyles, P.E.
Corrective Action Required
03/08/2022

There is no drop across CI 1-9 between Line 5 in and Line 1 out. A 0.5' drop is required. Please revise.
Corrective Action Required
03/08/2022

Comments on the Engineer's Estimate will be sent under separate cover.
Traffic Review No Comments 03/08/2022 03/07/2022
Brad Cooley, P.E., RSPI
Traffic Review No Comments 02/10/2022 03/01/2022
Mike Weisenborn
Engineering Review Corrections 02/10/2022 02/10/2022
Sue Pyles, P.E.
Corrective Action Required
02/10/2022

Paddock Drive: • Include the required grading for the Paddock Drive cul-de-sac. • Will fill be placed within the floodway or just the floodplain? • Show the removal of the temporary portion of the existing cul-de-sac. • Revise the Engineer’s Estimate to account for all of this cul-de-sac work, if not already included.
Corrective Action Required
02/10/2022

Sheet C.100: Remove the extraneous Storm Line 7 labels/leaders.
Corrective Action Required
02/10/2022

Sheet C.200: Please label the proposed contours just west of Building 33.
Corrective Action Required
02/10/2022

Sheet C.201: Please revise the structure elevations so none are in bold for clarity.
Corrective Action Required
02/10/2022

Sheets C.301 & C.302: The flowline elevation shown for the Line 5 connection to CI 1-9 is shown differently in the Line 1 and Line 5 Profiles. Please revise.
Corrective Action Required
02/10/2022

Sheet C.302: Include the existing water line crossing between CI 5-2 and FES 5-3 in Profile view.
Engineering Review Corrections 01/10/2022 01/10/2022
Sue Pyles, P.E.
Corrective Action Required
01/10/2022

Please include design of the permanent cul-de-sac and removal of the temporary portion of the existing cul-de-sac at the north end of Paddock Drive in this set of plans. Please note that a Floodplain Development Permit will be required if work is proposed within the floodplain. Both the floodplain and floodway shall be located by elevation for confirmation of their locations.
Corrective Action Required
01/10/2022

Based on the number and nature of comments, the next review will be a 10-day review.
Corrective Action Required
01/10/2022

Sheet C.001: • Please review the Site Improvement Notes, they don’t match the project. • Please use the same terminology throughout the plan set for the stormwater BMP in Tract C (Retention or detention).
Corrective Action Required
01/10/2022

Sheet C.100 (First One): • Please provide a legend to clarify the dashed lines and hatched area. Please make this revision to all of the plan sets on this project. • There are extra storm line labels/leaders in the NE section of the site. Please remove. • This sheet and the following sheet are both labeled C.100. Please revise.
Corrective Action Required
01/10/2022

Sheet C.200: • Swale information is provided, but no swales are shown on the Grading Plan. Please revise as needed. • Please label contours west of Building 32.
Corrective Action Required
01/10/2022

Sheet C.201: • Please label all top of structure elevations and include any 100-year WSE information applicable. Please note that additional review of the grading will be done once storm sewer structure elevations are shown. • Please remove the contours from this sheet.
Corrective Action Required
01/10/2022

Sheet C.202: Please revise the drainage area boundary line type for clarity.
Corrective Action Required
01/10/2022

Sheets C.203-C.207: • Please include underdrain at low points. • Please review Profile view label and revise overlapping text for clarity. • Why is Neosho Drive shown differently the first 300 feet in Profile view? • Please denote ADA route slope requirements at all stop conditions in Profile view.
Corrective Action Required
01/10/2022

Sheets C.301-C.307: • Please show all utility crossings in Profile view. • Storm Line 1 between CI 1-6 & 1-7 does not meet horizontal separation requirements with the water line. Please revise. • The Storm Line 5 FL In (W) is incorrect at CI 1-9 in Profile view. Please revise. • Please revise the compacted fill hatching in Profile views to something that provides more clarity. The hatching used covers up too much. • Many storm sewer structure tops are not shown meeting proposed grade. Please review all Profile views and revise as needed. • Please revise the alignment at FI 9-1 to make it a minimum 90 degree bend. • Please confirm that the storm sewer for the collector has been designed for the 2% event. • HDPE is not allowed under collector roadways. Please revise storm sewer as needed.
Traffic Review Corrections 01/10/2022 01/06/2022
Brad Cooley, P.E., RSPI
Corrective Action Required
01/05/2022

Sheet C.205 - Horizontal curves along Kirksville Dr. (Sta. 7+85, 9+15, & 11+60) are too tight (min. 200').
Corrective Action Required
01/05/2022

Sheet C.206 - Horizontal curve along Napoleon Dr. (Sta. 15+15) is too tight (min. 200').
Corrective Action Required
01/06/2022

Please provide a request for payment in lieu of construction for the sidewalk around the cul-de-sac on the south side of the property (Paddock Dr.).
Engineering Review Corrections 12/10/2021 12/10/2021
Sue Pyles, P.E.
Corrective Action Required
12/10/2021

Please submit an Engineer’s Estimate of Probable Construction Costs.
Corrective Action Required
12/10/2021

SHEET C.001 – Please provide updated items and quantities.
Corrective Action Required
12/10/2021

SHEETS C.203 – C.207 – At the bottom of the profiles, consider showing proposed ground elevations.
Corrective Action Required
12/10/2021

SHEET Exhibit – In reviewing the macro drainage report, Exhibit I shows additional useful information for the outlet structures and a detail for the trash guard. Please include that information on this sheet.
Corrective Action Required
12/10/2021

SHEET C.300 – It appears that the labels for storm line 11 are in reverse as compared to sheet C.306. It appears that they are also switched in the inlet/pipe calcs.
Corrective Action Required
12/10/2021

SHEETS C.301 – C.307 – Please show proposed water in the storm profiles.
Corrective Action Required
12/10/2021

SHEET C.302 – Looking at storm line 5, at roughly STA 2+00 the proposed grade just stops. Please show the proposed grade tying into existing ground.
Corrective Action Required
12/10/2021

SHEET C.302 – Looking at storm line 5, it appears that the flowline elevation at FES 5-1 is too low to work with the elevation of the existing outer road.
Corrective Action Required
12/10/2021

SHEET C.303 – Looking at storm line 6, please show the proposed grade tying into the top of FES 6-1.
Corrective Action Required
12/10/2021

SHEET C.304 – It appears that proposed grade does not meet up with the top of the proposed field inlets along the profile.
Corrective Action Required
12/10/2021

SHEET C.304 – Comparing the back, corner lot elevations shown on sheet C.201, for buildings 8, 7, 6, 5, and 4 to the top of structure elevations for the field inlets, it appears that the inlets are sitting too high. In particular, the throat of FI 7-3 is 972.50 as compared an elevation of 969.05 for the corner of the lot for building 7. Additionally, given the elevation of the pipe, it does not appear that the inlet top can be lowered enough to obtain positive drainage. Please be aware that it will be necessary to check all field inlets throughout the development and ensure that they are sitting low enough to accommodate positive drainage from the homes.
Traffic Review Corrections 12/03/2021 12/01/2021
Brad Cooley, P.E., RSPI
Corrective Action Required
12/01/2021

Please provide coordination and approval from the State for all work within the outer road R/W.
Corrective Action Required
12/01/2021

Please provide typical sections.
Corrective Action Required
12/01/2021

Sheet C.204 - Neosho Drive Sta. 0+78.97 - sag curve K-Value too low (Min. 37).
Corrective Action Required
12/01/2021

Please provide horizontal curve data.
Hearings

There are no hearings for this planning application.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your Planning Application