PL2021440
Summit Creek 1st Plat - Public Water
Engineering Plan Review
Engineering Plan Review
Void
11/10/2021
291 INVESTORS LLC
APPLICATION EXPIRED - Mike Weisenborn 01/10/2024 9:20 AM
Locations
Contacts
291 INVESTORS LLC, Address:900 W 48TH ST  
CLAYTON PROPERTIES GROUP, INC, Address:10450 Holmes Rd Suite 100, Phone:(816) 246-6700  
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review Approved with Conditions 02/10/2022 01/28/2022
Sue Pyles, P.E.
Engineering Review Approved with Conditions 01/19/2022 01/14/2022
Sue Pyles, P.E.
Engineering Review Corrections 01/07/2022 01/07/2022
Sue Pyles, P.E.
Corrective Action Required
01/06/2022

Sheet C.500: Informational – The “Utility Companies” contact list is duplicated on this sheet.
Corrective Action Required
01/07/2022

Sheet C.503: Please revise the storm sewer shown crossing the water line at Sta. 7+73, it doesn’t match the storm sewer plan and doesn’t meet minimum separation requirements as shown.
Corrective Action Required
01/07/2022

Sheet C.505: Show the Line 2 connection information in the Line 4 Profile view.
Corrective Action Required
01/11/2022

Water Line 4 between Sta. 8+00 - Sta. 9+00 (approximately) does not meet horizontal separation requirements with the storm sewer line. Please revise.
Corrective Action Required
01/11/2022

Water lines crossing storm or sanitary lines should cross as close to 90 degrees as possible. If the crossing angle is less than 45 degrees, please use restrained joint pipe until there is 10 feet of separation. There appear to be many crossings that will require restrained joint pipe. Please revise the pipe or verify it is not needed for each crossing.
Engineering Review Corrections 12/10/2021 12/10/2021
Sue Pyles, P.E.
Corrective Action Required
12/10/2021

Please submit an Engineer’s Estimate of Probable Construction Costs and a copy of the MDNR permit.
Corrective Action Required
12/10/2021

SHEET C.500 – There is a typo on the FEMA panel no. Please reference panel 29095C0551G.
Corrective Action Required
12/10/2021

SHEETS C.502 – C.505 – Please remove the storm elevations, shown where it crosses the water, from the plan view.
Corrective Action Required
12/10/2021

SHEET C.502 – C.505 – It appears that there are some locations where the water and storm lines do not meet minimum vertical separation. Please reconcile by either lowering the storm or water line.
Hearings

There are no hearings for this planning application.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your Planning Application