PL2019237
HAWTHORN RIDGE 2ND PLAT - SANITARY SEWER PLANS
Engineering Plan Review
Engineering Plan Review
Approved
07/15/2019
CMH PARKS INC
Locations
Contacts
CMH PARKS INC, Address:5000 CLAYTON RD  
CLAYTON PROPERTIES GROUP INC, Address:120 SE 30TH ST  
OLSSON ASSOCIATES, Address:1301 BURLINGTON, SUITE 100, Phone:(816) 361-1171  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 04/28/2021 04/14/2021
Gene Williams, P.E.
Engineering Review Corrections 03/25/2021 03/25/2021
Gene Williams, P.E.
Engineering Review Approved with Conditions 09/06/2019 09/06/2019
Gene Williams, P.E.
Engineering Review Corrections 08/28/2019 08/28/2019
Gene Williams, P.E.
Corrective Action Required
08/28/2019

Changes were made in accordance with comment #3 of the previous comment letter (i.e., concerning the direct connection of several sanitary sewer laterals to manholes); however, the location of the laterals is not in compliance with the Design and Construction Manual. The City requires a minimum of 4 feet distance, as measured from the outside of the manhole, and the beginning of the wye (i.e., not the centerline of the wye).
Corrective Action Required
08/28/2019

Please be aware that the distance between laterals along the line is a minimum of 4 feet, as measured from centerline of the wye, to centerline of the next wye. It appears all of the wyes along the line segments comply with this requirement. This comment is being provided for future reference only.
Engineering Review Corrections 07/29/2019 07/29/2019
Gene Williams, P.E.
Corrective Action Required
07/29/2019

Please review Sheet C213 and ensure that the wye connections are not less than 4.0 feet, as measured from the centerline of the wye connection, and each adjacent wye centerline. There are numerous instances where this rule is violated.
Corrective Action Required
07/29/2019

Sheet C213: Please provide a note stating these connections are wye connections. There have been instances in the past where these connections have been made using tees, which is not allowed.
Corrective Action Required
07/29/2019

Sheet C213 and Sheet C202: There are at least four (4) instances where sanitary sewer laterals are shown connecting directly to manholes. This is not allowed. A minimum of 4.0 feet is required between the outside of the manhole wall, and the beginning of the lateral (i.e., not the centerline in this instance).
Corrective Action Required
07/29/2019

Sheet C202: The run between manhole 4-3 and 4-2 is greater than 400 feet. Although technically allowed under the Design and Construction Manual, Water Utilities prefers these runs to not exceed 400 feet.
Corrective Action Required
07/29/2019

Please label the existing City manhole 1-1 as #56-208.
Hearings

There are no hearings for this planning application.

Documents & Images
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home