STREETS OF WEST PRYOR- LOWENSTEIN PARK IMPROVEMENTS
Commercial Final Development Plan
Commercial Final Development Plan
Approved
06/21/2019
Locations
Contacts
DRAKE DEVELOPMENT, LLC, Address:7200 West 132nd Street; Suite 150  
KAW VALLEY ENGINEERING INC, Address:14700 W 114TH TERR, Phone:(913) 894-5150  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review Approved with Conditions 08/05/2019 08/12/2019
Sue Pyles, P.E.
DE C&O #11 Pavement Thickness
Corrective Action Required
07/30/2019

Private parking lots shall follow Article 8 of the Unified Development Ordinance for pavement thickness and base requirements.
DE Contact Field Eng. Inspector
Corrective Action Required
07/30/2019

Contact the Field Engineering Inspector at (816) 969-1200 at least 48 hours prior to the onset of construction.
DE Engineers Estimate
Corrective Action Required
07/30/2019

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee (which is calculated as 3% of the total infrastructure cost plus a water test inspection fee(s)), and the water tap and meter setup fee have been included. These must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit. $30,527.94
DE Future Repair Work
Corrective Action Required
07/30/2019

Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
Planning Review No Comments 08/05/2019 07/30/2019
Sue Pyles, P.E.
Engineering Review Corrections 07/24/2019 07/29/2019
Sue Pyles, P.E.
Corrective Action Required
07/29/2019

Revise the Heavy Duty Pavement typical section to meet the City's requirements.
Corrective Action Required
07/29/2019

Submit an Engineer's Estimate of Probable Construction Costs.
Planning Review Corrections 07/24/2019 07/23/2019
Jennifer Thompson
Corrective Action Required
07/23/2019

The pavement standards have not been met for the heavy duty asphalt. The 4-inch should be revised to 5-inch. Please refer to the UDO Article 8.620-for required thicknesses. See engineering comment for further requests.
Fire Review Approved with Conditions 07/24/2019 07/18/2019
Jim Eden
Code Statement
Informational
07/18/2019

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Building Codes Review No Comments 07/24/2019 07/18/2019
Joe Frogge
Traffic Review No Comments 07/24/2019 07/17/2019
Michael Park
Planning Review Corrections 07/08/2019 07/08/2019
Dawn Bell
Corrective Action Required
07/05/2019

Provide a note in the accessible sign detail referencing the R7-8 sign type. This sign has a white background and green border.
Corrective Action Required
07/05/2019

The pavement standards have not been met. Please refer to the UDO Article 8.620-for required thicknesses. In addition, two types of pavement details (vehicle parking areas and drives and fire lanes and truck access) are required and needs to be references within the plan.
Corrective Action Required
07/05/2019

Label the color of restrooms.
Corrective Action Required
07/05/2019

The landscaping sizes have not been met. Please revise the caliper sizes to 3 inches and the required minimum height of evergreen trees is 8 feet.
Traffic Review No Comments 07/08/2019 07/08/2019
Michael Park
Resolved
07/08/2019

Building Codes Review Corrections 07/08/2019 07/05/2019
Joe Frogge
Corrective Action Required
07/05/2019

Inadequate information to complete review. Provide the following: - All water and waste pipe materials. - Size of water meter.
Corrective Action Required
07/05/2019

2 water meters shown. Action required: Eliminate one of the meters.
Engineering Review Corrections 07/08/2019 07/05/2019
Sue Pyles, P.E.
Corrective Action Required
07/05/2019

C-6: Site and Utility Plan Terminate storm sewer line “X” from box 42A to a stub out in lieu of energy dissipation or rip rap outlet where P&R can continue drainage past play area.
Corrective Action Required
07/05/2019

A-1 Restroom plan, section, elevation, detail Install hose bib on exterior of restroom building for maintenance hook up Call outs for asphalt color and type (match existing facilities) Call outs for burnished block color (match existing facilities) Widen plumbing chase from 2’-0”to 2’8” Insulation type?
Engineering Review Corrections 07/08/2019 07/05/2019
Sue Pyles, P.E.
Corrective Action Required
07/05/2019

General: • A portion of the park improvements, located in the NW corner of the park, are shown as a part of the public street plans. Please include all park related items in this plan set and remove from any other sets. • Show and label easements throughout the plan set, including Landscape sheets.
Corrective Action Required
07/05/2019

Sheet C-5: It appears that the trees to remain are incorrectly labeled. Please revise.
Corrective Action Required
07/05/2019

Sheet C-6: Please clarify water service line alignment. See Building Codes review comments.
Corrective Action Required
07/05/2019

Sheet C-7: The scale shown, 1”=40’, is incorrect. It appears the scale is 1”=30’, please revise.
Corrective Action Required
07/05/2019

Sheet C-13: The Regular Duty Paving detail does not meet the requirements of UDO Section 8.620. Please revise the detail and do not refer to MoDOT requirements in the notes.
Corrective Action Required
07/05/2019

Sheet L 2.01: Only ornamental tree varieties may be located within public easements. Verify that requirement is being met.
Corrective Action Required
07/05/2019

Sheet’s C-5 & C-6: In addition to the label below the sheet number, please include “For Reference Only” in a central location on each sheet. It should be large enough to be noticed right away.
Fire Review Approved with Conditions 07/08/2019 07/02/2019
Jim Eden
Code Statement
Corrective Action Required
07/02/2019

All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2018 International Fire Code.
Fees
Paid Fees Amount Paid Owing Date Paid
9110077-Final Development Plan fee $1,000.00 $1,000.00 Paid 06/21/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Hearings
Title Location Date Time
Documents & Images
Date Uploaded File Type Document Name
06/21/2019 Receipt Receipt for transaction: 2019-003993
06/21/2019 Letter Routing Sheet - FDP
06/21/2019 7067-1PARK
07/08/2019 Letter Applicant Letter - FDP (DFDP)
07/17/2019 Letter Resubmittal Routing Sheet - FDP
07/18/2019 2019-07-16 PARK 1ST Submittal Comment Response Letter
07/18/2019 7067-1PARK
07/29/2019 Letter Resubmittal Routing Sheet - FDP
08/21/2019 Activity Document Fees PL2019217 Streets of West Pryor Lowenstein Park FDP0
02/16/2021 SWP Estimate Comments
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home