Planning Application Status

PL2019154




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2019154
PERGOLA PARK 4TH PLAT - WATERLINE
Engineering Plan Review
Engineering Plan Review
Approved
04/19/2019
M-III LONGVIEW LLC
Locations
Contacts
M-III LONGVIEW LLC, Address:4220 SHAWNEE MISSION PARKWAY STE 200-B  
SCHLAGEL & ASSOCIATES, Address:14920 W 107TH ST, Phone:(913) 492-5158  
Reviews
Review Type Outcome Est. Completion Date Completed
Engineering Review No Comments 07/15/2019 07/09/2019
Sue Pyles, P.E.
Engineering Review Corrections 07/03/2019 06/27/2019
Sue Pyles, P.E.
Corrective Action Required
06/27/2019

Please revise all DIP to be Class 50 zinc coated interior and 401 super coat interior.
Corrective Action Required
06/27/2019

Please revise “dead end” to “temporary fire hydrant” in the label at Line 3 Sta. 1+90.75 in the Plan view for consistency with all other similar callouts.
Corrective Action Required
06/27/2019

Since the Line 2 stationing has been revised, the Profile view pipe length does not match. Revise accordingly.
Corrective Action Required
06/27/2019

Revise the size of pipe and pipe material shown in the Line 4 Profile view.
Corrective Action Required
06/27/2019

Verify that each connection to an existing water line is labeled in both Plan and Profile views.
Corrective Action Required
06/27/2019

Please review the Engineer’s Estimate of Probable Construction Costs submitted, it does not seem to completely match the information in the plan set. Revise accordingly.
Engineering Review Corrections 05/03/2019 05/08/2019
Sue Pyles, P.E.
Corrective Action Required
05/08/2019

Sheet 1: • Delete General Note 14, the City’s process has changed. • Utility Note 4 does not match what is shown in the plans. • Include Utility Contacts.
Corrective Action Required
05/08/2019

Sheet 3: • Label all fire hydrants in the Plan view. • Revise the compacted fill hatching to be shown more clearly in the Profile view. • Revise the label at Sta. 1+90.75 in the Line 3 Profile view, it is missing information. • Refer to removal of the same thing in Plan and Profile views at Line 3 Sta. 1+90.75. • DIP must be zinc coated. Please revise the Profile view label to reflect this requirement.
Corrective Action Required
05/08/2019

Sheet 4: • Revise the labels at Line 2 Sta. 6+39.55 and Line 4 Sta. 0+00 in the Profile views, they are missing information. • Label the Tee at Sta. 4+20.44 in the Line 2 Plan view. • Label the Tee and end Line 2 at Sta. 6+39.55 in the Line 2 Plan view. • The Line 2 Sta. 0+00 label is off the sheet. • Revise the label at Sta. 1+23.93 in the Line 4 Profile view to include connection to existing. • Include water line stationing in the Sta. 5+90.57 SE Mary Street label in the Line 4 Plan view.
Corrective Action Required
05/08/2019

Submit an Engineer’s Estimate of Probable Construction Costs.
Hearings

There are no hearings for this planning application.

Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home