Planning Application Status

PL2017185




 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PL2017185
Manor at Stoney Creek 3rd Plat - Street, Stormwater, MDP, and ESC
Engineering Plan Review
Engineering Plan Review
Approved
09/01/2017
CMH PARKS INC
Locations
Address
4406 SW AMETHYST DR, LEES SUMMIT, MO 64082

Address
4402 SW AMETHYST DR, LEES SUMMIT, MO 64082

Address
4401 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4405 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4409 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4413 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4417 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4421 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4420 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4416 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4412 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4408 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4404 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4400 SW ALABASTER CIR, LEES SUMMIT, MO 64082

Address
4401 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4405 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4409 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4413 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4417 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4421 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4420 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4416 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4412 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4408 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4404 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Address
4400 SW TANZANITE CIR, LEES SUMMIT, MO 64082

Property
69700122800000000

Property
69700123900000000

Property
69700124000000000

Property
69700122600000000

Property
69700123800000000

Property
69700122900000000

Property
69700124100000000

Property
69700122500000000

Property
69700123000000000

Property
69700123700000000

Property
69700124200000000

Property
69700122400000000

Property
69700123100000000

Property
69700123600000000

Property
69700124300000000

Property
69700122300000000

Property
69700123200000000

Property
69700123500000000

Property
69700124400000000

Property
69700071300000000

Property
69700122100000000

Property
69700122200000000

Property
69700123300000000

Property
69700123400000000

Property
69700124500000000

Property
69700122700000000

Property
69700122000000000

Address
4407 SW AMETHYST DR, LEES SUMMIT, MO 64082

Contacts
ENGINEERING SOLUTIONS, Address:50 SE 30TH ST, Phone:(816) 623-9888  
CMH PARKS INC, Address:5000 CLAYTON RD  
CMH PARKS INC (David Price), Address:120 SE 30TH ST 64082, Phone:(816) 246-6700  
NOE HEATH & EMILY, Address:4407 SW AMETHYST DR  
FERGER JEFFREY C, Address:4402 SW AMETHYST DR  
ANNIS ALEXANDRA & GEOFFREY, Address:4406 SW AMETHYST DR  
CONWAY DEREK M & LACEY J, Address:4401 SW ALABASTER CIR  
PERCIVAL JERRY & ALICIA, Address:4405 SW ALABASTER CIR  
STATON ERIC, Address:4409 SW ALABASTER CIR  
HOUK NATHAN & EMILY, Address:4413 SW ALABASTER CIR  
STAUFFER GARY L & TINA, Address:4417 SW ALABASTER CIR  
BEAUCHAMP JAMES LARRY & PATRICIA ANN, Address:4421 SW ALABASTER CIR  
GINDLESBERGER ANDREW RILEY & VALERIE JEAN, Address:4400 SW ALABASTER CIR  
RICHARDS SCOTT & AMY, Address:4404 SW ALABASTER CIR  
GRIFFIN T DELIBERO 2013 IRREVOCABLE TRUST, Address:4408 SW ALABASTER CIR  
LARSEN CARL B & YONG NAN, Address:4412 SW ALABASTER CIR  
TRITTEN LESLIE, Address:4416 SW ALABASTER CIR  
MCFARLAND NICOLE R, Address:4420 SW ALABASTER CIR  
PRUETT ANDREA L & CASEY B, Address:4401 SW TANZANITE CIR  
FERGUSON MICHAEL & REGINA, Address:4405 SW TANZANITE CIR  
SMITH BRETT & KATHLEEN, Address:4409 SW TANZANITE CIR  
TAMAYO DANIEL A & JENNIFER H, Address:4413 SW TANZANITE CIR  
TOURE ALASSANE, Address:4417 SW TANZANITE CIR  
WALLACE DARREN, Address:4421 SW TANZANITE CIR  
ODONNELL THOMAS & CALLIE, Address:4400 SW TANZANITE CIR  
AGNEW WILLARD & MARGARET MARY, Address:4404 SW TANZANITE CIR  
LUECK SHAWN & DARCY, Address:4408 SW TANZANITE CIR  
VORIS JESSICA, Address:4412 SW TANZANITE CIR  
SHELTON RAIMONDA D, Address:4416 SW TANZANITE CIR  
GRANADOS ALEXANDER & DORIAN G, Address:4420 SW TANZANITE CIR  
Reviews
Review Type Outcome Est. Completion Date Completed
Record Drawings Review No Comments 11/08/2021 11/11/2021
Sue Pyles, P.E.
Engineering Review No Comments 06/04/2018 05/31/2018
Sue Pyles, P.E.
Engineering Review Corrections 05/21/2018 05/21/2018
Sue Pyles, P.E.
Corrective Action Required
05/21/2018

Existing conditions for this project have changed due to an adjacent project placing fill within the limits of this project. Please revise the appropriate drawings for this project to reflect the additional fill areas or the grading already completed.
Corrective Action Required
05/21/2018

The revised existing conditions now direct drainage toward adjacent lots. Add silt fence or other erosion control as applicable along the east and south boundaries where this project abuts adjacent residential lots.
Engineering Review No Comments 05/08/2018 05/08/2018
Sue Pyles, P.E.
DE C&O #05 As-Graded MDP
Corrective Action Required
05/08/2018

The As-graded Master Drainage Plan shall be submitted to and accepted by the City prior to the issuance of a Certificate of Substantial Completion and prior to the issuance of any building permits for the development.
DE C&O #06 Land Disturbance
Corrective Action Required
05/08/2018

A Land Disturbance Permit shall be obtained from the City if ground breaking will take place prior to the issuance of an infrastructure permit, building permit, or prior to the approval of the Final Development Plan / Engineering Plans.
DE Contact Field Eng. Inspector
Corrective Action Required
05/08/2018

Contact the Field Engineering Inspector at (816) 969-1200 at least 48 hours prior to the onset of construction.
DE Contact ROW Inspector
Corrective Action Required
05/08/2018

Prior to any activities within the right-of-way that are not directly associated with a specific infrastructure or building permit, a separate right-of-way permit may be required. Contact a Right-of-Way Inspector at (816) 969-1800 to obtain the required permit.
DE Engineers Estimate
Corrective Action Required
05/08/2018

The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Engineering Plan Review and Inspection Fee of $2,198.23 (which is based on 3% of the total infrastructure cost) must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit.
DE Future Repair Work
Corrective Action Required
05/08/2018

Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
Traffic Review No Comments 05/08/2018 05/08/2018
Michael Park
Engineering Review Corrections 04/19/2018 04/19/2018
Sue Pyles, P.E.
Corrective Action Required
04/19/2018

The previous submittal showed Line segment 3.4-M1.1 as 18” HDPE in the plan set and 24” in the storm sewer calculation tables, and this submittal shows the segment as 24” in the plan set and 18” in the storm sewer calculation tables. Please reconcile.
Corrective Action Required
04/19/2018

Please check and revise, as needed, the Engineer’s Estimate of probable Construction Costs as follows: • Verify quantities for items Paving – Geogrid and Inlet Protection. • Verify that the storm sewer pipe quantities are correct based on the previous comment regarding Line 1.
Traffic Review No Comments 04/19/2018 04/13/2018
Sue Pyles, P.E.
Traffic Review No Comments 03/28/2018 03/30/2018
Sue Pyles, P.E.
Engineering Review Corrections 03/28/2018 03/30/2018
Sue Pyles, P.E.
Corrective Action Required
03/29/2018

Sheet's C.050-052: Include inlet protection for existing field inlets prior to any land disturbance.
Corrective Action Required
03/29/2018

Sheet C.301: The top elevation for JB 1-2 does not match with the proposed grade in the Line 2 Profile view. Please revise.
Corrective Action Required
03/30/2018

ADA-accessible ramps are no longer required at cul-de-sacs. Please revise the plan set to show the sidewalks ending midway through lots 89 & 101. This revision will also be required on the Final Plat. The sidewalk will then terminate at the driveway on those lots and will be shown on the individual plot plans that are required for the building permits.
Corrective Action Required
03/30/2018

I reviewed the 10 year storm pipe table included in the plan set. I will send it under separate cover. Please revise, and extend the revisions to all other storm sewer calculation tables.
Corrective Action Required
03/30/2018

Engineer's Estimate of Probable Construction Costs: • Review and verify quantities for all items, especially pavement items and storm sewer pipe • Remove item for ADA Sidewalk Ramp • Verify that the formulas, as several values in the Cost/Item column do not match multiplying the Quantity by Unit Cost. If it is rounding errors, please make sure that the multiplication matches what is actually shown.
Engineering Review Corrections 02/22/2018 02/27/2018
Sue Pyles, P.E.
Corrective Action Required
02/27/2018

Sheet C.201: Verify MBOEs provided and revise as needed.
Corrective Action Required
02/27/2018

Sheet C.201: Include 100-yr WSE for all area inlets.
Corrective Action Required
02/27/2018

Sheet C.301: The sanitary crossing between CI 3-4 & CI 1-1 is incorrectly shown. Revise accordingly.
Corrective Action Required
02/27/2018

Sheets C.600-C.601: Include junction box and sidewalk standard details.
Corrective Action Required
02/27/2018

Sheet C.206 is not included with this submittal. Please include in the plan set.
Corrective Action Required
02/27/2018

Please review the storm sewer tables and revise as needed.
Corrective Action Required
02/27/2018

Please revise the Engineer’s Estimate of probable construction Costs to match the revised plans.
Corrective Action Required
02/27/2018

Further storm sewer review will be completed once the storm sewer tables are revised.
Traffic Review Corrections 02/22/2018 02/22/2018
Michael Park
Corrective Action Required
02/22/2018

The street name signs at the intersections of Tanzanite/Georgetown and Amethyst/Georgetown can be removed from the plans. The stop signs should remain. These street name signs are already proposed at the intersections in association with the Reserve at Stoney Creek 3rd Plat.
Informational
02/22/2018

There are no other design comments. Plan review (e.g. detail and completeness) to be completed by Develpoment Engineering.
Traffic Review Corrections 01/18/2018 01/18/2018
Michael Park
Corrective Action Required
01/18/2018

Generally, a full review of these plans was not completed. It has been determined the plans do not meet the minimum requirements in Section 5204.
Corrective Action Required
01/18/2018

Typical section should provide for 1.5% cross slope through sidewalk areas and 4:1 grading.
Corrective Action Required
01/18/2018

Missing horizontal alignment information.
Corrective Action Required
01/18/2018

Provide dimensions for deviations in typical section such as all curb return radii, PC/PT station/offset, cul-de-sac radius, etc.
Corrective Action Required
01/18/2018

Signing plan should coordinate with the adjacent plat engineering plans. Separate and identify stop signs and street name signs. Street name signs may or may not already be addressed in the adjacent plat (not necessary on both corners of the intersection).
Engineering Review Corrections 01/18/2018 01/18/2018
Sue Pyles, P.E.
Corrective Action Required
01/18/2018

Sheet C.001 • A 2% to 4% cross-slope is shown for the sidewalk within the right of way on the typical asphaltic concrete section. Please revise to comply with our standard of 1.5% cross-slope.
Corrective Action Required
01/18/2018

Sheet C.051 • Include a legend for inlet protection.
Corrective Action Required
01/18/2018

Sheets C.200-C.202 • Storm sewer calculations for this project must be included in this plan set. • DA D includes multiple inlets. Please correct this error and verify that the calculations correctly match. • MBOEs were not provided for any of the lots on the Master Drainage Plan. It would appear that several lots adjacent to field inlets in the sump condition would warrant an MBOE. Please provide MBOEs for these lots, and elevate the MBOE so they are a minimum of 2.0 feet above the 100 year water surface elevation. • Basement types (e.g., standard, daylight, walkout) were provided on the Master Drainage Plan for lots not a part of this project. Replace those lots with lots from this project.
Corrective Action Required
01/18/2018

Sheet C.206 • Please add a note specifying the use of KCMMB mix for sidewalks. • FYI – “Intersection” is misspelled in the Intersection/ADA Ramp Elevation title.
Corrective Action Required
01/18/2018

Sheet C.301 • The pipe lengths don’t match the stationing for Lines 1 and 2. • The field inlets are shown in a sump condition, with openings on all sides. However, the profile view shows the tops being flush with the ground. Please correct the profile view to reflect the grading around the field inlets to create a localized sump. • Include station equations at all structures where multiple lines connect. Include the Line Number in each station label. • Please reverse the CI 1-1 flowlines in the Line 1 Profile view to show the flowline out on the d/s side of the label and the flowlines in on the u/s side of the label. • Include the sanitary sewer crossing between CI 3-4 & 1-1 in the Line 1 Profile. • Include the waterline crossing between FI 2-2 & CI 3-3 in the Line 2 Profile. • FI 2-1 appears to be located directly over the proposed sanitary sewer. Please relocate the structure to gain the proper separation.
Corrective Action Required
01/18/2018

Sheets C.600 & C.601 are not included with this submittal. Please include all required standard details, including those for erosion control, in the plan set.
Corrective Action Required
01/18/2018

All references to the existing temporary cul-de-sac appear to have been removed. Please clearly indicate removal of the existing cul-de-sac.
Corrective Action Required
01/18/2018

Notes should be provided stating that all ADA-accessible ramps shall be constructed along with the subdivision improvements. Sidewalks, however, are not subject to this requirement.
Corrective Action Required
01/18/2018

A SWPPP will be required prior to approval of any land disturbance or prior to approval of the plans, whichever comes first.
Corrective Action Required
01/18/2018

Engineer’s Estimate of Probable Construction Costs • Verify the quantities for Sidewalk and ADA Sidewalk Ramp. The pipe quantities can’t be checked until the storm sewer information is corrected.
Engineering Review Corrections 09/25/2017 09/29/2017
Sue Pyles, P.E.
Corrective Action Required
09/29/2017

Sheet C001 • Please complete "Lots Thru" or remove from title block. • Revise the MoDot Base thickness for Option 2 in Street & Storm Sewers Note 1 and the Typical Section. • Revise the Standard Detail references in Street & Storm Sewers Note 4.
Corrective Action Required
09/29/2017

Sheet C050 • Please install silt fence to address drainage flowing north at the north part of the plat.
Corrective Action Required
09/29/2017

Sheet C100 • Remove the Sidewalk Construction Note, it does not apply to this project.
Corrective Action Required
09/29/2017

Sheet C200 • Include existing contours.
Corrective Action Required
09/29/2017

Sheet C201 • The first MBOE Note references a report not submitted and plan sheets not included in plan set. Please revise.
Corrective Action Required
09/29/2017

Sheet C202 • Include complete storm sewer calculations in the plan set. • DA 6 and DA D each include multiple inlets. Please revise. • A portion of this plat drains offsite. Please include and address in the Drainage Map and calculations.
Corrective Action Required
09/29/2017

Sheet C203 • Remove note to install temporary cul-de-sac.
Corrective Action Required
09/29/2017

Sheet C206 • General Comment Concerning the ADA-Accessible Ramps and ADA-Accessible Ways: The specific details of these features must include, at a minimum, the design details specified in Section 5304.8 of the Design and Construction Manual. Elevation call-outs, although required, are not sufficient. Other design details specified in this section are required, including slope call-outs which comply with the criteria listed in Table LS-5, and section views specified in 5304.8. • General Comment: All ADA-accessible ramps and ADA-accessible ways must have a specific detail associated with them. Please show the locations of these features, and provide a call-out on the plan view with a specific reference to the sheet number and detail number.
Corrective Action Required
09/29/2017

Sheet C301 • There is an extra curb inlet shown in the Plan view for line 1 that is not shown elsewhere in the plans. Please remove. • The Line 1 Profile view is missing information for Curb Inlet 1-1 and the FL(out) elevation for Curb Inlet 1-2. • Please revise the stationing for Curb Inlet 1-1 and include the pipe size upstream on Curb Inlet 2-3 in the Line 2 Profile view.
Corrective Action Required
09/29/2017

Sheets C600-601 Please replace the APWA storm sewer details with City of Lee’s Summit standard details.
Corrective Action Required
09/29/2017

General • Label temporary cul-de-sac to be removed throughout the plan set. • Clearly delineate between proposed, existing, and future construction throughout the plan set. • Be consistent in labeling. • Additional comments that haven’t been included with this review may be required based on revisions due to these comments and submission of missing information. • Please submit an Engineer’s Estimate of Probable Construction Costs. • Please submit the SWPPP. • Please submit Stormwater study. • Remove the “Phase 3, The Manor at Stoney Creek” label from Lots 69/70 throughout the plan set. • Please verify that these plans are coordinated with the plans for the adjacent project The Reserve at Stoney Creek 3rd Plat.
Traffic Review Corrections 09/25/2017 09/27/2017
Michael Park
Corrective Action Required
09/27/2017

Roadway profiles at intersections should be reviewed in consideration of the vertical grade interaction with roadway typical sections/cross slopes.
Corrective Action Required
09/27/2017

Intersection details need coordination with the improvement plans for Georgetown Dr.
Hearings

There are no hearings for this planning application.

Documents & Images
Date Uploaded File Type Document Name
09/29/2017 Letter DE-Comment Letter (Engineering Plans)
01/19/2018 Letter DE-Comment Letter (Engineering Plans)
02/14/2018 Plans C.204
02/14/2018 Plans C.205
02/14/2018 Plans C.300
02/14/2018 Plans C.301
02/14/2018 Plans C.302
02/14/2018 Plans C.303
02/14/2018 Plans C.600
02/14/2018 Plans C.601
02/14/2018 Plans C.602
02/14/2018 Plans C.001
02/14/2018 Plans C.050
02/14/2018 Plans C.051
02/14/2018 Plans C.052
02/14/2018 Plans C.100
02/14/2018 Plans C.200
02/14/2018 Plans C.201
02/14/2018 Plans C.202
02/14/2018 Plans C.203
02/27/2018 Letter DE-Comment Letter (Engineering Plans)
03/20/2018 Plans C.205
03/20/2018 Plans C.206
03/20/2018 Plans C.300
03/20/2018 Plans C.301
03/20/2018 Plans C.302
03/20/2018 Plans C.303
03/20/2018 Plans C.600
03/20/2018 Plans C.601
03/20/2018 Plans C.602
03/20/2018 Plans C.001
03/20/2018 Plans C.050
03/20/2018 Plans C.051
03/20/2018 Plans C.052
03/20/2018 Plans C.100
03/20/2018 Plans C.200
03/20/2018 Plans C.201
03/20/2018 Plans C.202
03/20/2018 Plans C.203
03/20/2018 Plans C.204
03/30/2018 Letter DE-Comment Letter (Engineering Plans)
04/12/2018 Plans C.300
04/12/2018 Plans C.301
04/12/2018 Plans C.302
04/12/2018 Plans C.303
04/12/2018 Plans C.600
04/12/2018 Plans C.601
04/12/2018 Plans C.602
04/12/2018 Plans C.001
04/12/2018 Plans C.050
04/12/2018 Plans C.051
04/12/2018 Plans C.052
04/12/2018 Plans C.100
04/12/2018 Plans C.200
04/12/2018 Plans C.201
04/12/2018 Plans C.202
04/12/2018 Plans C.203
04/12/2018 Plans C.204
04/12/2018 Plans C.205
04/19/2018 Letter DE-Comment Letter (Engineering Plans)
05/01/2018 Plans C.203
05/01/2018 Plans C.204
05/01/2018 Plans C.205
05/01/2018 Plans C.300
05/01/2018 Plans C.301
05/01/2018 Plans C.302
05/01/2018 Plans C.303
05/01/2018 Plans C.600
05/01/2018 Plans C.601
05/01/2018 Plans C.602
05/01/2018 Plans C.001
05/01/2018 Plans C.050
05/01/2018 Plans C.051
05/01/2018 Plans C.052
05/01/2018 Plans C.100
05/01/2018 Plans C.200
05/01/2018 Plans C.201
05/01/2018 Plans C.202
05/25/2018 Plans C.303
05/25/2018 Plans C.600
05/25/2018 Plans C.601
05/25/2018 Plans C.602
05/25/2018 Plans C.001
05/25/2018 Plans C.050
05/25/2018 Plans C.051
05/25/2018 Plans C.052
05/25/2018 Plans C.053
05/25/2018 Plans C.100
05/25/2018 Plans C.200
05/25/2018 Plans C.201
05/25/2018 Plans C.202
05/25/2018 Plans C.203
05/25/2018 Plans C.204
05/25/2018 Plans C.205
05/25/2018 Plans C.300
05/25/2018 Plans C.301
05/25/2018 Plans C.302
05/29/2018 Activity Document Fees PL2017185 The Manor at Stoney Creek 3rd Plat Street & Storm
05/29/2018 Activity Document Fees PL2017185 The Manor at Stoney Creek 3rd Plat Street & Storm
06/07/2018 Letter DE-Engineering Plans Approval Letter
10/26/2021 STREET AND STORM ASBUILTS 11-14-2019
11/11/2021 Email The Reserve and Manor 3rd Plat Record Drawings
11/30/2022 Accepted Record Drawings The Manor at Stoney Creek 3rd Street Storm AsBuilts Accepted RD
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New license, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home