Review Type |
Outcome |
Est. Completion Date |
Completed |
Planning Review
|
No Comments
|
09/01/2016
|
09/06/2016
|
|
Hector Soto Jr.
|
|
|
Engineering Review
|
No Comments
|
09/01/2016
|
09/01/2016
|
|
Gene Williams, P.E.
|
|
DE Engineers Estimate
Corrective Action Required
The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Public Works Review and Inspection Fee of $4,182.71 (which is based on 3% of the total infrastructure cost plus a water test inspection fee) must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit from the Codes Administration Department.
|
|
DE Contact Field Eng. Inspector
Corrective Action Required
Contact Public Works Inspections at (816) 969-1800 at least 48 hours prior to the onset of construction.
|
|
DE Contact ROW Inspector
Corrective Action Required
Contact a Right-of-Way Inspector at (816) 969-1800 prior to any land disturbance within the right-of-way. These activities may require a permit.
|
|
DE Future Repair Work
Corrective Action Required
Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
|
|
PW Public Improvements TIFF CD's (DELETE)
Corrective Action Required
Any public improvements will require two (2) CD ROMs with the plans in TIFF format.
|
|
PW Submit Land Disturbance (DELETE)
Corrective Action Required
If ground breaking is desired prior to obtaining a building permit, please submit a Land Disturbance Permit application and the required attachments to the Erosion Control Specialist.
|
|
|
Fire Review
|
Corrections
|
09/01/2016
|
08/30/2016
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2012 International Fire Code .
|
|
Misc.
Corrective Action Required
Where will the sprinkler room be located?
|
|
|
Traffic Review
|
No Comments
|
09/01/2016
|
08/30/2016
|
|
Michael Park
|
|
|
Engineering Review
|
Approved with Conditions
|
11/04/2015
|
02/29/2016
|
|
Gene Williams, P.E.
|
|
DE Engineers Estimate
Corrective Action Required
The Engineer’s Estimate of Probable Construction Costs has been accepted for this project, and the Public Works Review and Inspection Fee of $4,182.71 (which is based on 3% of the total infrastructure cost plus a water test inspection fee) must be paid prior to the issuance of an infrastructure permit and/or the final processing of a building permit from the Codes Administration Department.
|
|
DE Contact Field Eng. Inspector
Corrective Action Required
Contact Public Works Inspections at (816) 969-1800 at least 48 hours prior to the onset of construction.
|
|
DE Contact ROW Inspector
Corrective Action Required
Contact a Right-of-Way Inspector at (816) 969-1800 prior to any land disturbance within the right-of-way. These activities may require a permit.
|
|
DE Future Repair Work
Corrective Action Required
Please be aware that any future repair work to public infrastructure (e.g., water main repair, sanitary sewer repair, storm sewer repair, etc.) within public easements will not necessarily include the repair of pavement, curbing, landscaping, or other private improvements which are located within the easement.
|
|
PW Public Improvements TIFF CD's (DELETE)
Corrective Action Required
Any public improvements will require two (2) CD ROMs with the plans in TIFF format.
|
|
PW Submit Land Disturbance (DELETE)
Corrective Action Required
If ground breaking is desired prior to obtaining a building permit, please submit a Land Disturbance Permit application and the required attachments to the Erosion Control Specialist.
|
|
|
Planning Review
|
Approved with Conditions
|
12/17/2015
|
12/17/2015
|
|
Hector Soto Jr.
|
|
Corrective Action Required
TRASH COMPACTOR SCREENING. Staff does not have the authority to approve the proposed temporary wood fence screening. The use of wood can only be approved by the City Council as part of a public hearing process, which requires submittal of a separate application and fee. However, staff does have the authority to administratively approve (i.e. no City Council approval required) any of the following types of temporary screening materials: vinyl fence, masonry wall, metal panel screen or fiber-cement panel screening. Please submit 3 copies of Sheet A303 only that reflect the revision of the screening material to one of the options that staff can administratively approve.
|
|
|
Engineering Review
|
Corrections
|
12/17/2015
|
12/17/2015
|
|
Gene Williams, P.E.
|
|
Corrective Action Required
Cost estimate needs revision as per email dated Dec. 17, 2015
|
|
Corrective Action Required
Awaiting permission from engineer to redline plans as per email dated Dec. 17th, 2015
|
|
|
Traffic Review
|
No Comments
|
12/17/2015
|
12/16/2015
|
|
Michael Park
|
|
|
Fire Review
|
Approved with Conditions
|
12/17/2015
|
12/15/2015
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2012 International Fire Code .
|
|
|
Engineering Review
|
Corrections
|
11/04/2015
|
11/04/2015
|
|
Gene Williams, P.E.
|
|
Corrective Action Required
Sheet C401: It is not clear where the sanitary and water service is being connected. Were the locations of the water and sanitary sewer field-verified? Our GIS records do not show the water or sanitary sewer service at this location.
|
|
Corrective Action Required
An automatic meter reading meter must be installed since the water line is private. Please show this on the plans after verifying the location.
|
|
Corrective Action Required
Why is ductile iron pipe being used for the fire line? The City would accept C900. Ductile iron pipe must be wrapped with poly, including all fittings.
|
|
Corrective Action Required
Please label the private streets, such as SW Midway Crossing in order to establish a reference.
|
|
Corrective Action Required
An erosion and sediment control plan appeared to be missing from the plans.
|
|
Corrective Action Required
An itemized and sealed Engineer's Estimate of Probable Construction Costs should accompany your final submittal drawings. The Engineering Plan Review and Inspection Fee is based on this estimate, and calculated at 3% of the total. Items to include in the estimate are: 1) water lines greater than 2" diameter, 2) water line fittings, tees, bends, thrust blocks, and valves and valve boxes, 3) sanitary sewer wye connection at the main, 3) storm pipes greater than 6" diameter, 4) storm inlets and storm drainage structures, 5) grading to establish proper drainage, 6) subgrade preparation, 7) aggregate sub-base for parking, 8) pavement, 9) curb and gutter, 10) erosion and sediment control measures and devices, and 11) final restoration, including seeding, sodding, fertilizer, mulch, and topsoil.
|
|
|
Planning Review
|
Corrections
|
11/04/2015
|
11/03/2015
|
|
Hector Soto Jr.
|
|
Corrective Action Required
KEYNOTES.
- The keynote on Civil Sheet C101 identifying the driveway for the trash compactor area is incorrect. It is labeled as the number 1 (proposed sidewalk), but should be the number 7 (proposed driveway entrance).
- The keynotes on Architectural Sheet A301 for the trash compactor enclosure are incorrect. The gate note should be called out as 5.7C, not 4.7C. The pattern on the gate should be called out as 5.7D, not 4.7C.
|
|
Corrective Action Required
TRASH COMPACTOR SCREENING. The trash compactor area on the south side of the building is shown to be screened from view along the east and south sides. The west side is left open. Staff understands that a future building expansion on the south side of the building will eventually provide screening along the west side. However, screening is required to be provided along the west side of the trash compactor area in the interim until such time as the building expansion is constructed. Staff will consider any temporary methods to achieve the necessary screening until the building expansion provides the intended permanent screening.
|
|
|
Traffic Review
|
No Comments
|
11/04/2015
|
10/29/2015
|
|
Michael Park
|
|
|
Fire Review
|
Corrections
|
11/04/2015
|
10/28/2015
|
|
Jim Eden
|
|
FDC
Corrective Action Required
IFC 903.3.7- Fire department connections. The location of fire department connections shall be approved by the fire code official. Connections shall be a 4 inch Storz type fitting and located within 100 feet of a fire hydrant, or as approved by the code official.
Action required: Shown the location of the fire department connection (FDC) on the building and a fire hydrant within 100 feet.
|
|
Knox Locks
Corrective Action Required
IFC 506.1 -Where access to or within a structure or an area is restricted because of secured openings or where immediate access is necessary for life-saving or fire-fighting purposes, the fire code official is authorized to require a key box to be installed in an approved location. The key box shall be of an approved type listed in accordance with UL 1037, and shall contain keys to gain necessary access as required by the fire code official.506.1.1 Locks.An approved lock shall be installed on gates or similar barriers when required by the fire code official.
Action required: A Knox box is required over the FDC. A box may be ordered online at Knoxbox.com.
|
|
Hydrants
Corrective Action Required
IFC 507.5.1- Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
Action required: Show the location of new or existing fire hydrants.
|
|
Code Statement
Corrective Action Required
All issues pertaining to life safety and property protection from the hazards of fire, explosion or dangerous conditions in new and existing buildings, structures and premises, and to the safety to fire fighters and emergency responders during emergency operations, shall be in accordance with the 2012 International Fire Code .
|
|
Misc.
The correct address for the building is 820 NW Blue Parkway.
|
|
|