| Review Type |
Outcome |
Est. Completion Date |
Completed |
|
Planning Review
|
Approved with Conditions
|
07/02/2013
|
07/03/2013
|
|
|
Chris Hughey
|
|
|
See attached PC Letter. CHRIS HUGHEY 07/03/2013 2:18 PM
|
|
Engineering Review
|
Approved with Conditions
|
07/02/2013
|
07/02/2013
|
|
|
Gene Williams, P.E.
|
|
|
Corrective Action Required
The existing 7.5 foot wide easement shown bisecting the property shall be vacated prior to approval of the Final Development Plan.
|
|
|
Corrective Action Required
The pavement section shall be revised to reflect a six (6) inch thick MoDOT Type 5 aggregate base rather than four (4) inches proposed.
|
|
|
Corrective Action Required
A Land Disturbance Permit shall be obtained if ground breaking will take place prior to the issuance of a building permit or prior to the approval of the Final Development Plan.
|
|
|
Corrective Action Required
Any cut and fill operations at the project site, which cause public water lines, public sanitary sewer lines, or public storm sewers to exceed their minimum or maximum depths of cover shall be mitigated by relocating the utility either horizontally or vertically to meet the specifications contained within the Design and Construction Manual.
|
|
|
|
|
Traffic Review
|
No Comments
|
07/02/2013
|
07/01/2013
|
|
|
Michael Park
|
|
|
|
|
Fire Review
|
Corrections
|
07/02/2013
|
06/26/2013
|
|
|
Jim Eden
|
|
|
Code Statement
Corrective Action Required
Fire Department- All building and life safety issues shall comply with the 2006 International Fire Code and local amendments as adopted by the City of Lee’s Summit.
|
|
|
Hydrants
Corrective Action Required
Fire Department- 508.5.1 Where required.
Where a portion of the facility or building hereafter constructed or moved into or within the jurisdiction is more than 300 feet from a hydrant on a fire apparatus access road, as measured by an approved route around the exterior of the facility or building, on-site fire hydrants and mains shall be provided where required by the fire code official.
Spacing shall also be in accordance with IFC C 105.1. Move the hydrant located on the south side parking lot island west to the center access lane.
ke
|
|
|
FDC's
Corrective Action Required
Fire Department- A fire hydrant shall be located within 100 feet of the fire department connection (FDC).
The fire department connection (FDC)and the location of the riser main are not shown on the drawings. Indicate the location of both and meet the 100' requirement.
|
|
|
Marking
Corrective Action Required
Fire Department- IFC 505.3 Where required by the fire code official, approved signs or other approved notices shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs or notices shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
|
|
|
Imposed Loads
Corrective Action Required
Fire Department- IFC 503.2.3 Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
|
|
|
|
|
Engineering Review
|
Corrections
|
05/31/2013
|
05/31/2013
|
|
|
Gene Williams, P.E.
|
|
|
Corrective Action Required
The "Micro Storm Water Drainage Study" dated May 17, 2013 does not appear to be based on current standards. Please see the Design and Construction Manual for acceptable flat-rate release standards and water quality standards under the default (comprehensive) strategy.
|
|
|
Corrective Action Required
It would appear that the volume of the detention basin will increase substantially after taking into account the new stormwater design standards.
|
|
|
Corrective Action Required
General Note: Most of the plans state "construction plans". Please keep in mind that the Preliminary Development Plan is a concept plan which may change depending on a review of the Final Development Plan.
|
|
|
Corrective Action Required
Sheet PDP 2: It appears that the proposed water meter is shown on private property and outside an existing easement. The water meter should be shown within right of way or an easement.
|
|
|
Corrective Action Required
Sheet PDP 2: It appears that a 4" water connection is shown on the west side of the proposed building. It is not clear why a domestic service line of this magnitude is required.
|
|
|
Corrective Action Required
General comment: Erosion and sediment control plan sheets were submitted, but comments on these sheets will not be presented during the Preliminary Development Plan phase.
|
|
|
Corrective Action Required
Sheet C.100: What is the purpose of the sediment basin? Is this a temporary measure to be installed during construction and later modified to become part of the detention basin? Is it part of the required water quality features? Is it acting as a sediment forebay?
|
|
|
Corrective Action Required
Sheet C.100: This sheet varies significantly from plan sheet PDP 2. This sheet is presented as a "Site Plan" but is missing the proposed fire line loop, sanitary sewer, etc. Is the purpose of this sheet to show existing conditions? If so, then please title it appropriately.
|
|
|
Corrective Action Required
Grading Plan Sheet C.200: Please be aware that any grading activities which exceed our minimum and/or maximum standards for depth of cover over City-owned utilities will require the applicant to either relocate the utility vertically or horizontally, or adjust the grading plan to achieve acceptable depth of cover.
|
|
|
Corrective Action Required
Storm Sewer Plan and Profile Sheets: There appears to be an inconsistent usage of symbols for stormwater. Some of the storm lines use "SW", while others show "STM", and others show "ST". Please use a consistent symbol and also include a legend.
|
|
|
Corrective Action Required
Sheet C.400: There appears to be inconsistent usage of symbols for stormwater. See previous comment.
|
|
|
Corrective Action Required
Sheet C.400: An additional backflow vault will be required for the new private fire hydrant located near the entrance from SW Persels Road.
|
|
|
Corrective Action Required
Sheet C.600: Asphaltic concrete typical section does not comply with the Unified Development Ordinance Article 12. Please review these requirements and update the typical section. All surfaces, including driving aisles and parking spaces not specified as fire access lanes, shall comply with these requirements. In lieu of these requirements, the applicant has the choice to use the Residential Street Standard for pavement construction shown on Table LS-2 of the Design and Construction Manual.
|
|
|
Corrective Action Required
Sheet C.600: All commercial entrances must be a minimum of 8" of KCMMB concrete mix to the right of way line.
|
|
|
Corrective Action Required
General comment: Easements appear to exist on the property, but there does not appear to be any indication of their existence. All easements, whether public or private, must be shown on the Preliminary Development Plan. It is likely that there will be conflicts with building placement, utility placement, etc. that cannot be foreseen at this time due to the lack of easements being shown on the Preliminary Development Plan.
|
|
|
|
|
Traffic Review
|
Corrections
|
05/31/2013
|
05/31/2013
|
|
|
Michael Park
|
|
|
Corrective Action Required
Since no services, education programs/school, daycare, etc. operate during the weekday, no impact analyses were conducted for the weekday peak traffic periods. If these types of activity were to occur on a weekday, additional traffic analysis and resulting improvement mitigations would be required.
|
|
|
Corrective Action Required
To comply with the Access Management Code and preserve traffic safety, the westerly driveway (existing) shall remain egress only as studied.
|
|
|
Corrective Action Required
Traffic Study - Street Network information should refer to Jefferson Street as a Commercial Collector, not a local street, and Persels Road as a Minor Arterial, not a collector, in accordance with street classifications by the City. Review and correct any Access Management Code conditions noted in the report as appropriate to reflect these changes in classification.
|
|
|
Corrective Action Required
Traffic Study - The trip generation used in the analysis for a 1000 seat Church (Existing) is 610 during the Sunday peak hour, but the actual traffic count for the 1000 seat Church experienced nearly 1000 trips during the Sunday peak hour. This difference, when factored to the anticipated growth associated with a 2000 seat Church may have a significant impact on the analyses. Since the difference in projected and measured volume is substantial, the study should provide some justification for the use of projected trip generation as opposed to real trip generation as the net difference in determining the development traffic impact. Either acknowledge the difference in trip generation and provide a good reason for the analyses as reported or modify/factor the intensity based on the relationship of real to projected numbers. Revise the intersection analyses as appropriate to reflect any change in trip generation.
|
|
|
Corrective Action Required
Traffic Study - Identify required improvements at the intersection of M-291 & Persels that would yield a LOS C or better to comply with the City's LOS Policy. Consider the planned improvements associated with the extension of Bailey Road to M-291 at Persels (under construction) in the analyses.
|
|
|
Corrective Action Required
Traffic Study - Complete an analysis scenario for the intersection of Persels and Jefferson Street that includes traffic signal control and lane configuration as planned by the City. This scenario may or may not result in an adequate LOS C or better for Existing Plus Site Develoment analyses.
|
|
|
Corrective Action Required
Traffic Study - A review of Jefferson Street from Oldham Pkwy to Persels should be completed in consideration of the City's Unimproved Road Policy. Trip generation from the development has been distributed along Jefferson Street and Jefferson Street from Oldham Pkw to Persels has a typical width of 18-20 feet more or less. Any non-residential development requires widening of unimproved roads, e.g. Jefferson, to the interim road standard defined as two 12-foot lanes with shoulder (and any driveway turn lanes in compliance with the Access Management Code) or to permanent curb and gutter roadway dependent on ADT.
|
|
|
Corrective Action Required
Traffic Study - The omission of left-turn lanes at Drives A, B, C, D, and E along Persels are justified in the report based on volume of left-turn traffic and conflcting volume. Additional justification relates to the width of Persels, which can accommodate a left turn movement while adjacent thru traffic passes. However, a left-turn lane for Drive F on Jefferson may need more consideration given the narrow width of Jefferson and the development/redevelopment potential that will increase traffic in the area. The left-turn lane on Jefferson is an Access Management Code condition for which an omission has yet to be adequately justified.
|
|
|
Corrective Action Required
Traffic Study - Note the intersections of Oldham and M-291 as well as Oldham and Jefferson have plans for relocation to accommodate future development or as part of redeveloment/development in the area. The study may assume any capacity improvements at these intersections associated with their relocation would accommodate the development impact.
|
|
|
Corrective Action Required
Traffic Study - Document the need or absense of need for left-turn and/or right-turn lane improvements at the intersection of Jefferson and Persels (particulary the southbound approach). Consider the planned improvements to this intersection by the City (signal and turn lanes for all but the southbound approach). At a minimum, a southbound left-turn lane should be provided on Jefferson at Persels.
|
|
|
Corrective Action Required
Traffic Study - The omission of right-turn lanes at Drives A, B, C, and D (Drive E already has a right-turn lane) along Persels are justified in the report based on volume of right-turn traffic and conflcting volume. Additional justification relates to the distribution of new engress trips and redistribution of existing engress traffic to Drives E and F as primary drives for the new development that consolidates attendence. However, a lright-turn lane for Drive F on Jefferson may need more consideration given the narrow width of Jefferson and the development/redevelopment potential that will increase traffic in the area. The right-turn lane on Jefferson is an Access Management Code condition for which an omission has yet to be adequately justified.
|
|
|
Corrective Action Required
Traffic Study - Review driveway throat length, driveway turn lanes, driveway sight distance, on-site traffic circulation, etc. in accordance with the Access Management Code. Acknowledge compliance with the code or provide recommendations for compliance or omission.
|
|
|
Corrective Action Required
Traffic Study - In addition to the LOS analyses and report, a vehicle queuing analysis, turn lane storage capacity and associated mitigation recommendations should be completed and reported for each study intersection.
|
|
|
|
|
Planning Review
|
Corrections
|
05/31/2013
|
05/31/2013
|
|
|
Chris Hughey
|
|
|
Legal Description
Corrective Action Required
Please submit an electronic copy of the legal description. Microsoft Word document or selectable text PDF are the preferred file formats. The legal description can be emailed to the planner's email address above.
|
|
|
Corrective Action Required
Minor Plat. A minor plat will be required to be submitted, approved and recorded at Jackson County to realign property lines consistent with the proposed development prior to approval of future building permits.
|
|
|
Corrective Action Required
Lighting - Sheet ES1.1. Will there be any under canopy light fixtures for the portion of the covered drive? If so, please submit manufacturer's specification sheets for these fixtures and add a note that all under canopy lighting shall be flush mounted.
|
|
|
Corrective Action Required
Lighting. All parking lot pole lighting that is adjacent to residential uses and/or districts shall have a maximum height of 15 feet and may extend up to 20 feet in height when more than 100 feet away from said residential use or district. Either all pole lights will need to meet the height restrictions set in Section 7.280.B of the Unified Development Ordinance (UDO) or submit a letter requesting a modification to the parking lot pole height limitations set in the UDO.
|
|
|
Corrective Action Required
Monument Sign. Provide a dimension from the monument sign to the property line. Please note Article 13 of the UDO states all monument signs shall be setback 10 feet from the property line.
|
|
|
Corrective Action Required
Signage general. Staff recommends showing general placement, size, and lighting methods for all wall mounted and monument signage. Signs that exceed the number of total signs, size, or have different lighting methods then what is permitted in Article 13 of the UDO can be approved by the Planning Commission and City Council as a part of this Preliminary Development Plan application if shown.
|
|
|
Corrective Action Required
Architecture. Architectural metal panels are a conditional material in the UDO which require Planning Commission and City Council approval. Please provide approximate percentage of coverage by the architectural metal panels for each elevation.
|
|
|
Corrective Action Required
Architecture. Show all ground mounted and/or roof mounted mechanical units. Please note all roof mounted mechanical units shall be screened equal to the height of the units by the building's parapet wall and all ground mounted mechanical units shall be screened equal to the height of the units by landscaping material or by decorative walls.
|
|
|
Corrective Action Required
Architecture (recommendation only). Staff would encourage the use of traditional stucco rather than EFIS or reduce EFIS to more of an incidental role rather than a primary facade material. Please note this is a recommendation only and not a requirement.
|
|
|
Corrective Action Required
Landscaping - High Impact Buffer. A high impact buffer will be required along the rear property lines of the adjacent Lots 6, 7 , & 8 of Clearview Acres and along the south/side property line of Lot 6 Clearview Acres, similar to the high impact buffer that was added along the west property line of the "Core Youth Building". Refer to Article 14 of the UDO for buffer requirements.
|
|
|
Corrective Action Required
Landscaping. Graphically show the existing plantings along SW Persels Rd between the 2 driveway entrances.
|
|
|
Corrective Action Required
Landscaping. Add a note to the landscaping plans stating all decidious trees shall have a minimum caliper of 3 inches, all evergreen trees shall have a minimum height of 8 feet, and all parking lot screening shrubs shall have a minimum height of 18 inches at the time of planting.
|
|
|
Corrective Action Required
Landscaping. There appears to be a conflict with the placement of the proposed mounument sign and adjacent landcaping shurbs and trees.
|
|
|
Corrective Action Required
Landscaping. The 20 foot parking lot setback along Jefferson St appears to scale out to approximately 17.5 feet. Please verify this dimension or possible 1:30 scale of drawing.
|
|
|
Corrective Action Required
Landscaping. Show the earthen berm along the southeast corner of the site on the landscaping plans. It appears there may be a gap between the 2.5 foot tall berm and shrubbery along Jefferson Street for parking lot screening methods.
|
|
|
Corrective Action Required
Landscaping. Correct the open space tree and shrub calculations and required numbers of planting materials. Open space calculations are based on the square footage of land excluding structures only. Refer to Section 14.090.B of the UDO.
|
|
|
Corrective Action Required
Accessible Parking Space Signage. Specify sign model #R7-8 and show mounting height of accessible parking signage as no higher than 5 feet above grade measured from the underside of the sign. Sheet C.600
|
|
|
Corrective Action Required
Sidewalk. Add a 5 foot dimension or label to the new sidewalk along Persels Rd.
|
|
|
Corrective Action Required
Parking. Provide the gross floor area of the largest assembly room or number of seats for the Core Building and this proposed building to verify there is enough shared parking available to serve both buildings. Refer to Table 12-1 of the UDO.
|
|
|
Corrective Action Required
Building square footage. List the proposed building square footage with and without the alternate addition on the site plan (sheet C.100).
|
|
|
Corrective Action Required
Trash enclosure. Provide a detail of the trash enclosure. Please note trash enclosure shall be constructed of masonry walls with a steel gate painted to be compatible with the color of the masonry walls and building it is to serve.
|
|
|
Corrective Action Required
Maximum building height. The maximum building height in R-1 (Single Family Residential) zoning district is 3 stories or 40 feet. Since 50 feet is shown on the building elevations please submit a letter requesting a modification to the maximum building height set in the UDO (refer to Table 5-4).
|
|
|
|
|
Fire Review
|
Corrections
|
05/31/2013
|
05/29/2013
|
|
|
Jim Eden
|
|
|
Code Statement
Corrective Action Required
Fire Department- All building and life safety issues shall comply with the 2006 International Fire Code and local amendments as adopted by the City of Lee’s Summit.
|
|
|
FDC's
Corrective Action Required
Fire Department- A fire hydrant shall be located within 100 feet of the fire department connection (FDC).
Show the location of the FDC.
|
|
|
Marking
Corrective Action Required
Fire Department- IFC 505.3 Where required by the fire code official, approved signs or other approved notices shall be provided for fire apparatus access roads to identify such roads or prohibit the obstruction thereof. Signs or notices shall be maintained in a clean and legible condition at all times and be replaced or repaired when necessary to provide adequate visibility.
D103.6.1 Roads 20 to 26 feet in width.
Fire apparatus access roads 20 to 26 feet wide (6096 to 7925 mm) shall be posted on both sides as a fire lane.
|
|
|
Fire Lanes
Corrective Action Required
Fire Department- D105.1 Where required.
Buildings or portions of buildings or facilities exceeding 30 feet (9144 mm) in height above the lowest level of fire department vehicle access shall be provided with approved fire apparatus access roads capable of accommodating fire department aerial apparatus. Overhead utility and power lines shall not be located within the aerial fire apparatus access roadway.
D105.2 Width.
Fire apparatus access roads shall have a minimum unobstructed width of 26 feet (7925 mm) in the immediate vicinity of any building or portion of building more than 30 feet (9144 mm) in height.
Confirm 26 feet of drivable surface for the fire lanes around the south and west sides of the building.
|
|
|
Imposed Loads
Corrective Action Required
Fire Department- IFC 503.2.3 Fire apparatus access roads shall be designed and maintained to support the imposed loads of fire apparatus and shall be surfaced so as to provide all-weather driving capabilities.
|
|
|
Hydrants
Corrective Action Required
Fire Department-C105.1 Hydrant spacing.
The average spacing between fire hydrants shall not exceed that listed in Table C105.1.
Exception: The fire chief is authorized to accept a deficiency of up to 10 percent where existing fire hydrants provide all or a portion of the required fire hydrant service.
Regardless of the average spacing, fire hydrants shall be located such that all points on streets and access roads adjacent to a building are within the distances listed in Table C105.1.
|
|
|
|