Review Type |
Outcome |
Est. Completion Date |
Completed |
Fire Review
|
Complete
|
02/01/2011
|
01/27/2011
|
|
Jim Eden
|
|
Code Statement
Corrective Action Required
Fire Department-All building and life safety issues shall comply with the 2006 International Fire Code and local amendments as adopted by the City of Lee’s Summit.
|
|
|
Planning Review
|
Corrections
|
02/01/2011
|
01/25/2011
|
|
Hector Soto Jr.
|
|
|
Traffic Review
|
No Comments
|
02/01/2011
|
01/25/2011
|
|
Michael Park
|
|
|
Engineering Review
|
No Comments
|
02/01/2011
|
01/18/2011
|
|
David Lohe
|
|
|
Planning Review
|
Corrections
|
01/03/2011
|
01/03/2011
|
|
Hector Soto Jr.
|
|
Planning Correction
Corrective Action Required
PROPERTY LINE SETBACKS. The tower is required to be set back at least a distance equal to the tower height (149'). The proposed tower is set back 57', 49' and 28' from the north, east and southwest property lines, respectively. A written request for a modification to this requirement shall be submitted.
|
|
Planning Correction
Corrective Action Required
SEPARATION DISTANCES. Towers shall be separated by at least a distance equal to 4x the tower height (596') from any single- or two-family residences. The proposed tower is located approximately 400' away from the nearest single-family residences, which are located to the southwest on the opposite side of US 50 Hwy. A written request for a modification to this requirement shall be submitted.
|
|
Planning Correction
Corrective Action Required
FENCING. Security fencing around the tower site is required to incorporate an anti-climbing device. The plans show no indication of any anti-climbing device.
|
|
Planning Correction
Corrective Action Required
LANDSCAPING. Evergreen trees shall be a minimum 8' in height at the time of planting. Deciduous trees, including ornamentals, shall be a minimum 3" caliper at the time of planting.
|
|
Planning Correction
Corrective Action Required
TOWER APPEARANCE. Towers shall be painted a neutral color. There is no indication of any proposed color for the tower.
|
|
Planning Correction
Corrective Action Required
SUPPLEMENTAL TECHNICAL STUDIES. Contact Mehran Nazari with AdGen Telecom Group, the City's telecommunications consultant, at 703-757-6757 ext. 701. A copy of the site plan, grading plan, landscape plan and tower elevation will be submitted to the consultant for review. The consultant will make a determination regarding what additional technical information will be required for the review of this application.
|
|
Planning Correction
Corrective Action Required
COLOR PHOTOS. Color photo simulations from several angles showing the proposed site of the tower with a photo-realistic representation of the proposed tower as it would appear viewed from the closest residential property and from adjacent roadways.
|
|
Planning Correction
Corrective Action Required
LIABILITY INSURANCE. For your information, proof of general liability insurance for claims from injury or death and property damage in an amount approved by the the City, but not less than $2,000,000.00 per occurrence for personal injury and $2,000,000.00 per occurrence for property damage with the City listed as an additional insured shall be required prior to the issuance of any building permit.
|
|
Planning Correction
Corrective Action Required
A turnaround is requested at the end of the driveway so vehicles will not have to back out onto Blue Parkway.
|
|
Planning Correction
Corrective Action Required
No curbing is shown on the driveway - staff supports a modification to the curbing requirement.
|
|
|
Engineering Review
|
Corrections
|
01/03/2011
|
01/03/2011
|
|
David Lohe
|
|
Corrective Action Required
The UDO requires curbs on driveways and parking areas. Public Works would support a condition to waive the requirements since concentrating the stormwater would probably be more detrimental than allowing sheet flow on this site.
|
|
|
Traffic Review
|
No Comments
|
01/03/2011
|
12/22/2010
|
|
Michael Park
|
|
|
Fire Review
|
Complete
|
01/03/2011
|
12/21/2010
|
|
Jim Eden
|
|
Corrective Action Required
Fire Department- All building and life safety issues shall comply with the 2006 International Fire Code and local amendments as adopted by the City of Lee’s Summit.
|
|
|