Summary
PRRES20254012
Building Permit - Residential
Final Completion
SMITH STEPHEN R
ALTERATION SINGLE FAMILY
NEW ROOF MOUNTED SOLAR SYSTEM W/ BACK UP GENERATOR / 6.96 kw
09/18/2025
10/01/2025
03/30/2026
12/16/2025
Locations
Contacts
Solar Scapes KC LLC, Address:409 SW Nelson Dr  
LISSETTE@SOLARSCAPESKC.COM  
SMITH STEPHEN R, Address:504 NE WENONGA PL  
INTEGRITY PLUMBING SERVICES LLC, Address:405 SW Nelson Dr., Phone:(816) 803-9032  
Reviews
Review Type Outcome Est. Completion Date Completed
Residential Plan Review Approved 10/03/2025 10/01/2025
Brandon Kalwei
Fire Department Solar Review Approved with Conditions 09/30/2025 09/30/2025
Jim Eden
Miscellaneous Correction
Informational
09/30/2025

Provide ESS, generator, and Photovoltaic labeling. Verified at inspection.
Miscellaneous Correction
Resolved
09/30/2025

2024 IFC- 1207.11 ESS in Group R-3 and R-4 occupancies. ESS in Group R-3 and R-4 occupancies shall be in accordance with Sections 1207.11.1 through 1207.11.9. Exceptions: 1.ESS listed and labeled in accordance with UL 9540 and marked “For use in residential dwelling units,” where installed in accordance with the manufacturer’s instructions and NFPA 70. 2.ESS rated less than 1 kWh (3.6 megajoules). Confirm battery units are labeled per Exception #1.
Misc
Informational
09/30/2025

[A] 102.9 Matters not provided for. Requirements that are essential for the public safety of an existing or proposed activity, building or structure, or for the safety of the occupants thereof, that are not specifically provided for by this code, shall be determined by the fire code official. Whereas the 2024 IFC provides better guidance for an emerging technology., the applicable sections for ESS of 2024 IFC will serve as the code for this project.
Fire Department Solar Review Rejected 09/22/2025 09/18/2025
Jim Eden
Miscellaneous Correction
Corrective Action Required
09/18/2025

Provide ESS, generator, and Photovoltaic labeling. Verified at inspection.
Miscellaneous Correction
Corrective Action Required
09/18/2025

2024 IFC- 1207.11 ESS in Group R-3 and R-4 occupancies. ESS in Group R-3 and R-4 occupancies shall be in accordance with Sections 1207.11.1 through 1207.11.9. Exceptions: 1.ESS listed and labeled in accordance with UL 9540 and marked “For use in residential dwelling units,” where installed in accordance with the manufacturer’s instructions and NFPA 70. 2.ESS rated less than 1 kWh (3.6 megajoules). Confirm battery units are labeled per Exception #1.
Misc
Corrective Action Required
09/18/2025

[A] 102.9 Matters not provided for. Requirements that are essential for the public safety of an existing or proposed activity, building or structure, or for the safety of the occupants thereof, that are not specifically provided for by this code, shall be determined by the fire code official. Whereas the 2024 IFC provides better guidance for an emerging technology., the applicable sections for ESS of 2024 IFC will serve as the code for this project.
Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for Add/Alter Single Family $60.00 $60.00 Paid 10/01/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Gas Piping Inspection - Residential Passed 11/26/2025 11/26/2025
Final Inspection - Residential Failed 11/26/2025 11/26/2025 11/26/2025
Misc
Corrective Action Required
11/26/2025
Not ready. Complete all electrical, isolate all equipment grounding conductors from the neutral conductors, secure all wiring within 12" of enclosures, paint gas piping, etc.
Electrical Service Inspection Passed 11/26/2025 11/26/2025 11/26/2025
Final Inspection - Residential Passed 12/16/2025 12/16/2025 12/16/2025
Misc
Resolved
12/16/2025
Not ready. Complete all electrical, isolate all equipment grounding conductors from the neutral conductors, secure all wiring within 12" of enclosures, paint gas piping, etc.
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your permit