Summary
PRRES20246187
Building Permit - Residential
Issued
NEW SINGLE FAMILY
NEW HOUSE - ROOF TRUSSES - UNCOVERED DECK - FINISHED AND UNFINISHED BASEMENT - STOP WORK ORDER generated on 01/02/2025 12:00 AM by username 'Shawn Hoffman'. STOP WORK ORDER removed on 01/21/2025 12:00 AM by username 'Shawn Hoffman'.
11/27/2024
12/03/2024
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
BRUCER@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sanitary Sewer Development Fee $2,285.00 $2,285.00 Paid 12/03/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 12/03/2024
7232302-Residential License Tax Fee $1,022.72 $1,022.72 Paid 12/03/2024
8331401-Water Tap Fee $3,973.00 $3,973.00 Paid 12/03/2024
8350015-Water Meter Fee $748.03 $748.03 Paid 12/03/2024
9110078-Valuation Fee New Single Family $2,081.08 $2,081.08 Paid 12/03/2024
$0.00 $0.00 $0.00 N/A
$0.00 $0.00 $0.00 N/A
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Occupancy Inspection - Codes Residential Pending
Driveway Inspection Pending
Misc
Informational
04/24/2025
4-24-25 DP. DW was formed, aggregate compacted, approved to pour
Sidewalk Inspection Pending
Misc
Informational
04/24/2025
4-24-25 DP. SW on the right side facing house is formed, cross slopes in compliance, approved to pour. SW on the left side facing house is not formed up yet.
Erosion Control Inspection Residential Pending
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
05/15/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - Protect front of lot. - No pretection in back of lot.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/15/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Erosion Control Inspection Residential Failed 12/20/2024 12/20/2024
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/20/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - Post address -Protect street
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
01/02/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Footing Inspection - Residential Passed 12/20/2024 12/20/2024
Misc
Corrective Action Required
12/20/2024
Third party inspection
Erosion Control Inspection Residential Failed - Stop Work 1/2/2025 01/02/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/20/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - Post address -Protect street
Erosion Control Inspection Residential Partial 1/21/2025 1/21/2025 01/21/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
01/21/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - Post address -Protect street
Misc
Corrective Action Required
01/21/2025
Erosion cotrol in place at time of inspection
Erosion Control Inspection Residential Partial 1/22/2025 01/22/2025
Misc
Corrective Action Required
01/21/2025
Erosion cotrol in place at time of inspection
Water Service Inspection - R Partial 1/22/2025 01/22/2025
Misc
Corrective Action Required
01/22/2025
- PARTIAL, POLY 30' OUT OF FOUNDATION
Sewer Service Inspection - R Passed 1/22/2025 1/22/2025 01/22/2025
Underslab Plumbing Inspection - Residential Passed 1/23/2025 1/23/2025 01/23/2025
Erosion Control Inspection Residential Partial 1/23/2025 01/23/2025
Misc
Corrective Action Required
01/22/2025
Erosion cotrol in place at time of inspection
Water Service Inspection - R Passed 1/23/2025 1/23/2025 01/23/2025
Misc
Resolved
01/23/2025
- PARTIAL, POLY 30' OUT OF FOUNDATION
All Rough Inspection - Residential Failed 2/25/2025 2/25/2025 02/25/2025
Miscellaneous Correction
Informational
02/25/2025
Exterior garage PFH sheathing and front porch truss tie downs passed and are okay to cover This is a partial pass only
All Rough Inspection - Residential Failed 3/10/2025 3/10/2025 03/10/2025
Miscellaneous Correction
Informational
02/25/2025
Exterior garage PFH sheathing and front porch truss tie downs passed and are okay to cover This is a partial pass only
Misc
Corrective Action Required
03/10/2025
- In pantry, fire block soffit at HVAC chase and garage wall - Floor joist hangers missing nails in great room - Minimum of 3 studs on exterior corners, basement South corner - No gauge on Gas line for inspection
Erosion Control Inspection Residential Failed 3/10/2025 03/10/2025
Misc
Resolved
03/10/2025
Erosion cotrol in place at time of inspection
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
03/10/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - No pretection in back of lot.
Electrical Service Inspection Passed 3/10/2025 3/10/2025 03/10/2025
Gas Service Inspection - Residential Failed 3/10/2025 3/10/2025 03/10/2025
Misc
Corrective Action Required
03/10/2025
- No gauge or pressure test.
All Rough Inspection - Residential Passed 3/12/2025 3/12/2025 03/12/2025
Miscellaneous Correction
Resolved
03/12/2025
Exterior garage PFH sheathing and front porch truss tie downs passed and are okay to cover This is a partial pass only
Misc
Resolved
03/12/2025
- In pantry, fire block soffit at HVAC chase and garage wall - Floor joist hangers missing nails in great room - Minimum of 3 studs on exterior corners, basement South corner - No gauge on Gas line for inspection
Gas Service Inspection - Residential Passed 3/12/2025 3/12/2025 03/12/2025
Misc
Resolved
03/12/2025
- No gauge or pressure test.
Erosion Control Inspection Residential Failed 3/12/2025 03/12/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
03/10/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - No pretection in back of lot.
Driveway Inspection Partial 4/24/2025 4/24/2025 04/24/2025
Misc
Informational
04/24/2025
4-24-25 DP. DW was formed, aggregate compacted, approved to pour
Sidewalk Inspection Partial 4/24/2025 4/24/2025 04/24/2025
Misc
Informational
04/24/2025
4-24-25 DP. SW on the right side facing house is formed, cross slopes in compliance, approved to pour. SW on the left side facing house is not formed up yet.
Erosion Control Inspection Residential Failed 5/15/2025 05/15/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
03/12/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - Protect front of lot. - No pretection in back of lot.
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/15/2025
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Documents & Images
Date Uploaded File Type Document Name
11/27/2024 Application Form HM #182 - PERMIT APP
12/03/2024 Approved Plans APPROVED PLANS
12/03/2024 Plot Plan APPROVED PLOT PLAN
12/03/2024 Approved Plans APPROVED TRUSS LAYOUT
12/03/2024 Approved Plans APPROVED TRUSS PACKAGE
12/03/2024 Permit Codes Residential Plan Review
12/03/2024 Permit DS Building Permit
12/03/2024 Receipt Receipt for transaction:2024-009269
12/20/2024 2765 SW 11th St LSMO Footing Inspection 12-19-24
12/20/2024 Letter INSPECTION SUMMARY
12/20/2024 Letter INSPECTION SUMMARY
01/02/2025 Letter Stop Work Order
01/21/2025 Letter INSPECTION SUMMARY
01/22/2025 Letter INSPECTION SUMMARY
01/22/2025 Letter INSPECTION SUMMARY
01/22/2025 Letter INSPECTION SUMMARY
01/23/2025 Letter INSPECTION SUMMARY
01/23/2025 Letter INSPECTION SUMMARY
01/23/2025 Letter INSPECTION SUMMARY
02/25/2025 Letter INSPECTION SUMMARY
03/05/2025 HM #182 - PFH Strap Letter- Stamped
03/05/2025 182 Highland Meadows field issue- Connections- Stamped
03/10/2025 Letter INSPECTION SUMMARY
03/10/2025 Letter INSPECTION SUMMARY
03/10/2025 Letter INSPECTION SUMMARY
03/10/2025 Letter INSPECTION SUMMARY
03/12/2025 Letter INSPECTION SUMMARY
03/12/2025 Letter INSPECTION SUMMARY
03/12/2025 Letter INSPECTION SUMMARY
04/24/2025 Letter INSPECTION SUMMARY
04/24/2025 Letter INSPECTION SUMMARY
05/15/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home