Permit Application Status

PRRES20245090


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20245090
Building Permit - Residential
Issued
NEW SINGLE FAMILY
NEW HOUSE - FINISHED AND UNFINISHED BASEMENT - COVERED AND UNCOVERED DECK
09/25/2024
10/12/2024
Locations
Contacts
TRUMARK HOMES, LLC, Address:PO BOX 728, Phone:(816) 564-5613  
MARK A YANCIK, Address:508 nw manor dr  
TRUMARKHOMES.MARK@GMAIL.COM  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
IMPACT ELECTRICAL SOLUTIONS LLC, Address:14 ANCHOR DRIVE, Phone:(816) 674-9345  
A BRIGHT PLUMBING LLC, Address:18107 E 18TH TER N, Phone:(816) 215-0730  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sanitary Sewer Development Fee $2,285.00 $2,285.00 Paid 10/12/2024
9110073-Right of Way Permit Fee $170.00 $170.00 Paid 10/12/2024
7232302-Residential License Tax Fee $2,045.44 $2,045.44 Paid 10/12/2024
8331401-Water Tap Fee $3,973.00 $3,973.00 Paid 10/12/2024
8350015-Water Meter Fee $748.03 $748.03 Paid 10/12/2024
9110078-Valuation Fee New Single Family $1,591.34 $1,591.34 Paid 10/12/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Plot Plan Inspection Pending
Occupancy Inspection - Codes Residential Pending
Miscellaneous Inspection Pending
Erosion Control Inspection Residential Pending
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
02/07/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Footing Inspection - Residential Passed 10/14/2024 10/14/2024
Misc
Informational
10/14/2024
- INSPECTION PERFORMED BY THIRD PARTY.
Erosion Control Inspection Residential Failed 10/14/2024 10/14/2024
Misc
Corrective Action Required
10/14/2024
POST ADDRESS
Sewer Service Inspection - R Passed 10/18/2024 10/18/2024 10/18/2024
Erosion Control Inspection Residential Partial 10/18/2024 10/18/2024
Misc
Corrective Action Required
10/14/2024
POST ADDRESS
Water Service Inspection - R Passed 10/21/2024 10/21/2024 10/21/2024
Underslab Plumbing Inspection - Residential Passed 10/30/2024 10/30/2024 10/30/2024
Erosion Control Inspection Residential Failed 11/1/2024 11/01/2024
Misc
Resolved
11/01/2024
POST ADDRESS
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
11/01/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. - REMOVE GRAVEL FROM STREET - REPAIR SILT FENCE AT FRONT OF LOT - POST ADDRESS
Erosion Control Inspection Residential Partial 11/5/2024 11/05/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
11/05/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. - REMOVE GRAVEL FROM STREET - REPAIR SILT FENCE AT FRONT OF LOT - POST ADDRESS
Misc
Corrective Action Required
11/05/2024
-Erosion control in place at time of inspecion
Erosion Control Inspection Residential Failed 12/13/2024 12/13/2024
Misc
Resolved
12/13/2024
-Erosion control in place at time of inspecion
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/13/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - REMOVE TRASH AND DEBRIS FROM LOT. - RESTORE SILT FENCE AT FRONT OF LOT.
Piers/Caissons Inspection - Residential Failed 12/13/2024 12/13/2024 12/13/2024
Misc
Corrective Action Required
12/13/2024
- LOOSE DEBRIS AND WOOD, TRASH IN ALL THREE PIERS DUG.
Piers/Caissons Inspection - Residential Passed 12/16/2024 12/16/2024 12/16/2024
Misc
Resolved
12/16/2024
- LOOSE DEBRIS AND WOOD, TRASH IN ALL THREE PIERS DUG.
All Rough Inspection - Residential Failed 12/19/2024 12/19/2024 12/19/2024
Misc
Corrective Action Required
12/19/2024
*** PORTAL FRAME INSPECTION *** - GARAGE PORTAL APPROVED - DECK ROOF APPROVED - CS-PF AT SLIDER NO STRAPS, SHEETING BREAKS NOT IN MIDDLE THIRD, NO NAIL PATTERN
All Rough Inspection - Residential Failed 2/3/2025 2/3/2025 02/03/2025
Misc
Resolved
02/03/2025
*** PORTAL FRAME INSPECTION *** - GARAGE PORTAL APPROVED - DECK ROOF APPROVED - CS-PF AT SLIDER NO STRAPS, SHEETING BREAKS NOT IN MIDDLE THIRD, NO NAIL PATTERN
Misc
Corrective Action Required
02/03/2025
- bottom of rafter has no bearing in bedroom 3 - 2 king studs required at each end of slider on main level for span of 9’ 2” as per R602.7.5 table - Missing nails in stud shoes at master bathroom - Anchor sill plate in basement at entry to hallway - Fire block top plate at exterior of basement with approved material ( 7/16 siding not approved) - Fire block fur out walls basement vertically with in 10’ with approved material
Electrical Service Inspection Passed 2/3/2025 2/3/2025 02/03/2025
Gas Service Inspection - Residential Passed 2/3/2025 2/3/2025 02/03/2025
Erosion Control Inspection Residential Failed 2/3/2025 02/03/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/13/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - REMOVE TRASH AND DEBRIS FROM LOT. - RESTORE SILT FENCE AT FRONT OF LOT.
Misc
Corrective Action Required
02/03/2025
- Restore gravel filter
All Rough Inspection - Residential Passed 2/7/2025 2/7/2025 02/07/2025
Misc
Resolved
02/07/2025
- bottom of rafter has no bearing in bedroom 3 - 2 king studs required at each end of slider on main level for span of 9’ 2” as per R602.7.5 table - Missing nails in stud shoes at master bathroom - Anchor sill plate in basement at entry to hallway - Fire block top plate at exterior of basement with approved material ( 7/16 siding not approved) - Fire block fur out walls basement vertically with in 10’ with approved material
Erosion Control Inspection Residential Failed 2/7/2025 02/07/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
02/07/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. - REMOVE TRASH AND DEBRIS FROM LOT. - RESTORE SILT FENCE AT FRONT OF LOT.
Misc
Resolved
02/07/2025
- Restore gravel filter
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
02/07/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Driveway Inspection Partial 3/12/2025 3/12/2025 03/12/2025
Misc
Informational
03/12/2025
3-12-25 DP. DW was formed, aggregate compacted. Approved to pour.
Driveway Inspection Passed 4/3/2025 4/3/2025 04/03/2025
Misc
Informational
03/12/2025
3-12-25 DP. DW was formed, aggregate compacted. Approved to pour. 4-3-25 DP. DW was poured, forms removed. Passed.
Documents & Images
Date Uploaded File Type Document Name
09/25/2024 HIGHLAND LOT 168 2775 SW 11th TERR PERMIT-EXCISE APP
09/25/2024 168 Highland Meadows Staked - Copy
09/25/2024 LOT 168 HIGHLAND 2775 SW 11 TH TERR
09/30/2024 Approved Plans APPROVED PLANS
09/30/2024 Plot Plan APPROVED PLOT PLAN
09/30/2024 Permit Codes Residential Plan Review
10/12/2024 Permit DS Building Permit
10/12/2024 Receipt Receipt for transaction:2024-008294
10/14/2024 M L Crose 2775 SW 11th Terr LSMO Highland Meadows Lot 168 Trumark Permit 2024-5090 Foundation Footing Inspection Report 10-14-24
10/14/2024 Letter INSPECTION SUMMARY
10/14/2024 Letter INSPECTION SUMMARY
10/18/2024 Letter INSPECTION SUMMARY
10/18/2024 Letter INSPECTION SUMMARY
10/21/2024 Letter INSPECTION SUMMARY
10/30/2024 Letter INSPECTION SUMMARY
11/01/2024 Letter INSPECTION SUMMARY
11/05/2024 Letter INSPECTION SUMMARY
12/13/2024 Letter INSPECTION SUMMARY
12/13/2024 Letter INSPECTION SUMMARY
12/16/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
02/03/2025 Letter INSPECTION SUMMARY
02/03/2025 Letter INSPECTION SUMMARY
02/03/2025 Letter INSPECTION SUMMARY
02/03/2025 Letter INSPECTION SUMMARY
02/07/2025 Letter INSPECTION SUMMARY
02/07/2025 Letter INSPECTION SUMMARY
03/12/2025 Letter INSPECTION SUMMARY
04/03/2025 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home