Permit Application Status

PRRES20245089


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20245089
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE. FINISHED/UNFINISHED BASEMENT. UNCOVERED DECK.
09/25/2024
10/09/2024
03/29/2025
06/13/2025
Locations
Contacts
TRUMARK HOMES, LLC, Address:PO BOX 728, Phone:(816) 564-5613  
MARK A YANCIK, Address:508 nw manor dr  
APEX HEATING & AIR CONDITIONING INC, Address:1202 NW EAGLE RIDGE BLVD, Phone:(816) 228-2739  
IMPACT ELECTRICAL SOLUTIONS LLC, Address:14 ANCHOR DRIVE, Phone:(816) 674-9345  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
TRUMARKHOMES.KYLE@GMAIL.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Water Tap Fee $3,973.00 $3,973.00 Paid 10/09/2024
Water Meter Fee $748.03 $748.03 Paid 10/09/2024
Sanitary Sewer Development Fee $2,285.00 $2,285.00 Paid 10/09/2024
Right of Way Permit Fee $85.00 $85.00 Paid 10/09/2024
Residential Excise Tax Fee $1,022.72 $1,022.72 Paid 10/09/2024
Valuation Fee New Single Family $1,644.07 $1,644.07 Paid 10/09/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 10/11/2024 10/11/2024 10/11/2024
Erosion Control Inspection Residential Failed 10/11/2024 10/11/2024 10/11/2024
Misc
Corrective Action Required
10/11/2024
- Repair silt fence - Post address
Sewer Service Inspection - R Passed 10/18/2024 10/18/2024
Water Service Inspection - R Passed 10/22/2024 10/22/2024 10/22/2024
Erosion Control Inspection Residential Partial 10/23/2024 10/23/2024
Misc
Corrective Action Required
10/11/2024
Erosion control in place at time of inspection
Underslab Plumbing Inspection - Residential Passed 10/23/2024 10/23/2024 10/23/2024
All Rough Inspection - Residential Failed 11/13/2024 11/13/2024 11/13/2024
Misc
Informational
11/13/2024
- portal frame and porch ok to cover
Erosion Control Inspection Residential Failed 12/13/2024 12/13/2024
Misc
Corrective Action Required
10/23/2024
Erosion control in place at time of inspection
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
12/13/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - RESTORE EROSION CONTROL AT FRONT OF LOT. - REMOVE GRAVEL AND DEBRIS FROM STREET
Piers/Caissons Inspection - Residential Passed 12/13/2024 12/13/2024 12/13/2024
Erosion Control Inspection Residential Failed 12/27/2024 12/27/2024
Misc
Resolved
12/27/2024
Erosion control in place at time of inspection
DCM2 ESC DEFICIENT INSTALLATION
Resolved
12/27/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - RESTORE EROSION CONTROL AT FRONT OF LOT. - REMOVE GRAVEL AND DEBRIS FROM STREET
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/27/2024
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. =Establish erosion control at front of lot.
All Rough Inspection - Residential Failed 12/27/2024 12/27/2024 12/27/2024
Misc
Informational
11/13/2024
- portal frame and porch ok to cover
Misc
Corrective Action Required
12/27/2024
INSPECTION DENIDE NO INSPECTION DONE - Erosion control out of compliance
All Rough Inspection - Residential Failed 1/2/2025 1/2/2025 01/02/2025
Misc
Resolved
01/02/2025
- portal frame and porch ok to cover
Misc
Resolved
01/02/2025
INSPECTION DENIDE NO INSPECTION DONE - Erosion control out of compliance
Misc
Corrective Action Required
01/02/2025
2786 sw 12 st - Add another stud under triple 2x10” at single bay return wall - Missing stud shoes at kitchen bearing wall - Protect wiring within 6’ of attic access - Add support under double 2x10” basement unfinished area back wall - Address floor joist over electrical panel with multiple holes closer than 2” -
Erosion Control Inspection Residential Partial 1/2/2025 01/02/2025
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
01/02/2025
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE. =Establish erosion control at front of lot.
Misc
Corrective Action Required
01/02/2025
- Erosion control in place at time of inspection
Electrical Service Inspection Passed 1/2/2025 1/2/2025 01/02/2025
Gas Service Inspection - Residential Passed 1/2/2025 1/2/2025 01/02/2025
All Rough Inspection - Residential Failed 1/7/2025 1/7/2025 01/07/2025
Misc
Corrective Action Required
01/02/2025
- Missing stud shoes at kitchen bearing wall Ok to insulate
All Rough Inspection - Residential Passed 1/10/2025 1/10/2025 01/10/2025
Misc
Resolved
01/10/2025
- Missing stud shoes at kitchen bearing wall Ok to insulate
Driveway Inspection Partial 3/10/2025 3/10/2025 03/10/2025
Misc
Informational
03/10/2025
3-10-25 DP. DW was formed, aggregate compacted. Approved to pour.
Driveway Inspection Passed 3/18/2025 3/18/2025 03/18/2025
Misc
Informational
03/10/2025
3-10-25 DP. DW was formed, aggregate compacted. Approved to pour. 3-18-25 DP. DW was poured, forms removed. Passed
Erosion Control Inspection Residential Failed 3/19/2025 03/19/2025
Misc
Resolved
03/19/2025
- Erosion control in place at time of inspection
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
03/19/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - POST ADDRESS - PERIMETER EROSION CONTROL NOT IN COMPLIANCE.
Erosion Control Inspection Residential Passed 5/29/2025 05/29/2025
DCM2 ESC DEFICIENT INSTALLATION
Resolved
05/29/2025
Occupancy Inspection - Codes Residential Failed 5/29/2025 05/29/2025
Miscellaneous Correction
Corrective Action Required
05/29/2025
-R317, Smart siding behind concrete at front stoop at agrage wall, to be 2" gap - Provide security screws at front door - Fire stop gaps above garage doors at ceiling
Plot Plan Inspection Passed 5/29/2025 05/29/2025
Occupancy Inspection - Codes Residential Full C of O 6/13/2025 6/13/2025 06/13/2025
Miscellaneous Correction
Resolved
06/13/2025
-R317, Smart siding behind concrete at front stoop at agrage wall, to be 2" gap - Provide security screws at front door - Fire stop gaps above garage doors at ceiling
Documents & Images
Date Uploaded File Type Document Name
09/25/2024 HIGHLAND LOT 145 CORRECT ADDRESS APP
09/30/2024 Permit Codes Residential Plan Review
10/01/2024 Plot Plan APPROVED PLOT PLAN
10/01/2024 Approved Plans APPROVED PLANS
10/01/2024 Permit Codes Residential Plan Review
10/09/2024 Permit DS Building Permit
10/09/2024 Receipt Receipt for transaction:2024-008228
10/10/2024 2786 SW 12th St LSMO Footing Inspection Report 10-9-24
10/11/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/18/2024 Letter INSPECTION SUMMARY
10/22/2024 Letter INSPECTION SUMMARY
10/23/2024 Letter INSPECTION SUMMARY
10/23/2024 Letter INSPECTION SUMMARY
11/13/2024 Letter INSPECTION SUMMARY
11/13/2024 Letter INSPECTION SUMMARY
12/13/2024 Letter INSPECTION SUMMARY
12/13/2024 Letter INSPECTION SUMMARY
12/27/2024 Letter INSPECTION SUMMARY
12/27/2024 Letter INSPECTION SUMMARY
01/02/2025 Letter INSPECTION SUMMARY
01/02/2025 Letter INSPECTION SUMMARY
01/02/2025 Letter INSPECTION SUMMARY
01/02/2025 Letter INSPECTION SUMMARY
01/07/2025 Letter INSPECTION SUMMARY
01/10/2025 Letter INSPECTION SUMMARY
03/10/2025 Letter INSPECTION SUMMARY
03/18/2025 Letter INSPECTION SUMMARY
03/19/2025 Letter INSPECTION SUMMARY
05/29/2025 Letter INSPECTION SUMMARY
05/29/2025 Letter INSPECTION SUMMARY
05/29/2025 Letter INSPECTION SUMMARY
06/13/2025 Letter Codes Final Certificate of Occupancy
06/13/2025 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home