Permit Application Status

PRRES20244021


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20244021
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - UNCOVERED DECK - ROOF TRUSSES -
08/01/2024
08/15/2024
02/02/2025
04/30/2025
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
Summit Homes, Address:120 SE 30th St, Phone:(816) 434-5074 Ext:320  
Bruce Roach, Address:120 SE 30th St., Phone:(816) 434-5074 Ext:321  
BRUCER@SUMMITHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sanitary Sewer Development Fee $2,285.00 $2,285.00 Paid 08/15/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 08/15/2024
7232302-Residential License Tax Fee $1,022.72 $1,022.72 Paid 08/15/2024
8331401-Water Tap Fee $3,973.00 $3,973.00 Paid 08/15/2024
8350015-Water Meter Fee $748.03 $748.03 Paid 08/15/2024
9110078-Valuation Fee New Single Family $2,142.76 $2,142.76 Paid 08/15/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 03/26/2025
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 03/26/2025
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 03/26/2025
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 04/25/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 9/18/2024 9/18/2024 09/18/2024
Misc
Informational
09/17/2024
Inspection performed by thied party inspector.
Sewer Service Inspection - R Passed 9/25/2024 9/25/2024 09/25/2024
Water Service Inspection - R Passed 9/26/2024 9/26/2024 09/26/2024
Erosion Control Inspection Residential Partial 10/3/2024 10/03/2024
Misc
Corrective Action Required
10/03/2024
- EROSION CONTROL IN PLACE AT TIME OF INSPECTION
Underslab Plumbing Inspection - Residential Passed 10/3/2024 10/3/2024 10/03/2024
Erosion Control Inspection Residential Failed 11/1/2024 11/01/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
10/03/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. - REMOVE GRAVEL AND DEBRIS FROM STREET
All Rough Inspection - Residential Failed 11/15/2024 11/15/2024 11/15/2024
Misc
Informational
11/06/2024
See engineer letter for LVL not upset
Misc
Corrective Action Required
11/15/2024
Garage portal frame approved
Erosion Control Inspection Residential Failed 12/13/2024 12/13/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
12/13/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS. - REMOVE GRAVEL AND DEBRIS FROM STREET
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
12/13/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - REPAIR SILT FENCE AT FRONT OF LOT
All Rough Inspection - Residential Not Ready 12/13/2024 12/13/2024 12/13/2024
Misc
Informational
11/15/2024
See engineer letter for LVL not upset
Misc
Informational
12/13/2024
Garage portal frame approved
Misc
Corrective Action Required
12/13/2024
INSPECTION DENIED - NO FIRE BLOCKING DONE - REPAIR SILT FENCE
All Rough Inspection - Residential Failed 12/17/2024 12/17/2024 12/17/2024
Misc
Informational
12/13/2024
See engineer letter for LVL not upset
Misc
Informational
12/13/2024
Garage portal frame approved
Misc
Corrective Action Required
12/13/2024
INSPECTION DENIED - NO FIRE BLOCKING DONE - REPAIR SILT FENCE
Misc
Corrective Action Required
12/17/2024
INSPECTION DENIED EROSION CONTROL NOT IN COMPLIANCE
Erosion Control Inspection Residential Failed 12/17/2024 12/17/2024
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
12/13/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - REPAIR SILT FENCE AT FRONT OF LOT
DCM5 ESC INSP DENIED
Corrective Action Required
12/17/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. - REPAIR SILT FENCE IN FRONT OF LOT - REMOVR GRAVRL FROMM STREET IN FRONT OF LOT
Erosion Control Inspection Residential Failed 12/18/2024 12/18/2024
DCM2 ESC DEFICIENT INSTALLATION
Resolved
12/18/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - REPAIR SILT FENCE AT FRONT OF LOT
DCM5 ESC INSP DENIED
Resolved
12/18/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. - REPAIR SILT FENCE IN FRONT OF LOT - REMOVR GRAVRL FROMM STREET IN FRONT OF LOT
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
12/18/2024
REQUESTED INSPECTION(S) DENIED. STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED.
Electrical Service Inspection Passed 12/18/2024 12/18/2024 12/18/2024
Gas Service Inspection - Residential Passed 12/18/2024 12/18/2024 12/18/2024
All Rough Inspection - Residential Failed 12/18/2024 12/18/2024 12/18/2024
Misc
Informational
12/17/2024
See engineer letter for LVL not upset
Misc
Resolved
12/18/2024
Garage portal frame approved
Misc
Resolved
12/18/2024
INSPECTION DENIED - NO FIRE BLOCKING DONE - REPAIR SILT FENCE
Misc
Resolved
12/18/2024
INSPECTION DENIED EROSION CONTROL NOT IN COMPLIANCE
Misc
Corrective Action Required
12/18/2024
Fire block top of double wall at kitchen/ garage - Dining room exterior wall is a CS-PF, no straps or sheeting nail pattern completed - Anchor steel column at dining/kitchen - Provide security blocking at front door hinges side - Install HD 83 hold downs as on plans - Sister over notched stud in basement pony wall near electrical panel - Tighten anchor bolts through out basement - Missing al LUS24 truss hangers
All Rough Inspection - Residential Passed 12/20/2024 12/20/2024 12/20/2024
Misc
Resolved
12/20/2024
See engineer letter for LVL not upset
Misc
Resolved
12/20/2024
Fire block top of double wall at kitchen/ garage - Dining room exterior wall is a CS-PF, no straps or sheeting nail pattern completed - Anchor steel column at dining/kitchen - Provide security blocking at front door hinges side - Install HD 83 hold downs as on plans - Sister over notched stud in basement pony wall near electrical panel - Tighten anchor bolts through out basement - Missing al LUS24 truss hangers
Driveway Inspection Partial 2/28/2025 2/28/2025 02/28/2025
Misc
Informational
02/28/2025
2-28-25 DP. DW was formed, aggregate compacted, told to keep cross slopes in compliance throughout the approach for the width of the sw. Approved to pour.
Sidewalk Inspection Partial 2/28/2025 2/28/2025 02/28/2025
Misc
Informational
02/28/2025
2-28-25 DP. SW was formed, aggregate compacted. Aggregate depth was too shallow. Contractor corrected while I was onsite. After adjustments I checked cross slopes which were in compliance. Rock depth fixed and recompacted and made contractor lay out expansion joint for property line. Approved to pour.
Piers/Caissons Inspection - Residential Passed 3/3/2025 3/3/2025 03/03/2025
Erosion Control Inspection Residential Failed 3/6/2025 03/06/2025
DCM6 ESC INSP DENIED STREET CLEAN UP
Resolved
03/06/2025
REQUESTED INSPECTION(S) DENIED. STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED.
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
03/06/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - Protect front of lot and street.
Plot Plan Inspection Passed 3/6/2025 03/06/2025
Occupancy Inspection - Codes Residential Failed 3/6/2025 3/6/2025 03/06/2025
Misc
Corrective Action Required
03/06/2025
1113 sw fiord - sidewalk and driveway inspection pending - Final grading and sod - Pull forms from driveway and sidewalk - Sump discharge to be 36” away from foundation - Provide splash pads to divert water to 36” away from foundation - Land sewer trace wire at grade - Water meter pit at grade - Provide landing for deck stairs - Maintain 6” clearance from siding to grade at back of house - Owners entry to be self closing and latch - Provide landing at basement sliding door - Secondary lock at basement sliding door not operating
Occupancy Inspection - Codes Residential Not Ready 3/17/2025 3/17/2025 03/17/2025
Misc
Corrective Action Required
03/06/2025
1113 sw fiord - sidewalk and driveway inspection pending - Final grading and sod - Pull forms from driveway and sidewalk - Sump discharge to be 36” away from foundation - Provide splash pads to divert water to 36” away from foundation - Land sewer trace wire at grade - Water meter pit at grade - Provide landing for deck stairs - Maintain 6” clearance from siding to grade at back of house - Provide landing at basement sliding door
Misc
Informational
03/17/2025
NOT READY NOTHING CHANGED NO PATIO OR LANDING IN BACK
Driveway Inspection Passed 3/25/2025 3/25/2025 03/25/2025
Misc
Informational
02/28/2025
2-28-25 DP. DW was formed, aggregate compacted, told to keep cross slopes in compliance throughout the approach for the width of the sw. Approved to pour. 3-25-25 DW was poured, forms removed, cross slopes in compliance. Passed
Sidewalk Inspection Passed 3/25/2025 3/25/2025 03/25/2025
Misc
Informational
02/28/2025
2-28-25 DP. SW was formed, aggregate compacted. Aggregate depth was too shallow. Contractor corrected while I was onsite. After adjustments I checked cross slopes which were in compliance. Rock depth fixed and recompacted and made contractor lay out expansion joint for property line. Approved to pour. 3-25-25 DP. SW was poured, forms removed and cross slopes are in compliance. passed
Occupancy Inspection - Codes Residential Failed 3/25/2025 3/25/2025 03/25/2025
Misc
Corrective Action Required
03/17/2025
- Pay all outstanding fees - sidewalk and driveway inspection pending - Final grading and sod - Sump discharge to be 36” away from foundation - Provide splash pads to divert water to 36” away from foundation - Land sewer trace wire at grade - Water meter pit at grade
Misc
Resolved
03/25/2025
NOT READY NOTHING CHANGED NO PATIO OR LANDING IN BACK
Erosion Control Inspection Residential Partial 3/25/2025 03/25/2025
DCM2 ESC DEFICIENT INSTALLATION
Resolved
03/25/2025
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. - Protect front of lot and street.
Misc
Corrective Action Required
03/25/2025
- EROSION CONTROL IN PLACE AT TIME OF INSPECION.
Occupancy Inspection - Codes Residential Ready for Temp CO 3/26/2025 3/26/2025 03/26/2025
Misc
Corrective Action Required
03/25/2025
- Pay all outstanding fees - sidewalk and driveway inspection pending - Final grading and sod - Sump discharge to be 36” away from foundation - Provide splash pads to divert water to 36” away from foundation - Land sewer trace wire at grade - Water meter pit at grade
Erosion Control Inspection Residential Passed 4/25/2025 04/25/2025
Misc
Resolved
04/25/2025
- EROSION CONTROL IN PLACE AT TIME OF INSPECION.
Occupancy Inspection - Codes Residential Ready for Temp CO 4/25/2025 04/25/2025
Misc
Corrective Action Required
03/26/2025
- Pay all outstanding fees - Sump discharge to be 36” away from foundation - Provide splash pads to divert water to 36” away from foundation
Occupancy Inspection - Codes Residential Failed 4/28/2025 4/28/2025 04/28/2025
Misc
Corrective Action Required
04/25/2025
- Pay all outstanding fees
Occupancy Inspection - Codes Residential Failed 4/29/2025 4/29/2025 04/29/2025
Misc
Corrective Action Required
04/28/2025
- Pay all outstanding fees
Occupancy Inspection - Codes Residential Full C of O 4/30/2025 4/30/2025 04/30/2025
Misc
Resolved
04/30/2025
Documents & Images
Date Uploaded File Type Document Name
08/01/2024 HM #208 - Permit App
08/06/2024 Permit Codes Residential Plan Review
08/06/2024 Permit Codes Residential Plan Review
08/06/2024 Approved Plans APPROVED PLANS
08/06/2024 Approved Plans APPROVED TRUSS LAYOUT
08/06/2024 Approved Plans APPROVED TRUSS PACKAGE
08/15/2024 Permit Codes Residential Plan Review
08/15/2024 Permit Codes Residential Plan Review
08/15/2024 Plot Plan APPROVED PLOT PLAN
08/15/2024 Permit DS Building Permit
08/15/2024 Permit DS Building Permit
08/15/2024 Receipt Receipt for transaction:2024-006946
09/17/2024 3RD Party Insp Report THIRD PARTY FOOTING INSPECTION
09/18/2024 Letter INSPECTION SUMMARY
09/25/2024 Letter INSPECTION SUMMARY
09/26/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
11/01/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
11/15/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/18/2024 Letter INSPECTION SUMMARY
12/20/2024 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
02/28/2025 Letter INSPECTION SUMMARY
03/03/2025 Letter INSPECTION SUMMARY
03/06/2025 Letter INSPECTION SUMMARY
03/06/2025 Letter INSPECTION SUMMARY
03/06/2025 Letter INSPECTION SUMMARY
03/06/2025 Letter INSPECTION SUMMARY
03/06/2025 Letter INSPECTION SUMMARY
03/25/2025 Letter INSPECTION SUMMARY
03/25/2025 Letter INSPECTION SUMMARY
03/25/2025 Letter INSPECTION SUMMARY
03/25/2025 Letter INSPECTION SUMMARY
03/25/2025 Letter INSPECTION SUMMARY
03/26/2025 Letter INSPECTION SUMMARY
03/26/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/26/2025 Certificate/License Codes Temporary Certificate of Occupancy
03/26/2025 Receipt Receipt for transaction:2025-001802
04/25/2025 Certificate/License Codes Temporary Certificate of Occupancy
04/25/2025 Certificate/License Codes Temporary Certificate of Occupancy
04/25/2025 Receipt Receipt for transaction:2025-002597
04/28/2025 Letter INSPECTION SUMMARY
04/29/2025 Letter INSPECTION SUMMARY
04/30/2025 Letter Field Certificate of Occupancy
04/30/2025 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home