Permit Application Status

PRRES20242861


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20242861
Building Permit - Residential
Issued
NEW DUPLEX
NEW DUPLEX - FINISHED AND UNFINISHED BASEMENT - SUSPENDED SLAB -
06/04/2024
07/11/2024
12/03/2024
Locations
Contacts
ROCK CREEK HOMES, Address:6126 METCALF LANE, Phone:(913) 522-1945  
Kevin Guinan, Address:6126 Metcalf Lane  
KEVIN@ROCKCREEKHOMESKC.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
PRIDE SERVICES INC, Address:3842 GEORGIA TERR, Phone:(785) 242-9700  
BILL'S PLUMBING SERVICE LLC, Address:308 E PARK STREET, Phone:(913) 829-8213  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Duplex $2,603.66 $2,603.66 Paid 07/11/2024
8331507-Sanitary Sewer Development Fee $4,570.00 $4,570.00 Paid 07/11/2024
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 07/11/2024
8331401-Water Tap Fee $7,946.00 $7,946.00 Paid 07/11/2024
8350015-Water Meter Fee $1,496.06 $1,496.06 Paid 07/11/2024
7232302-Residential License Tax Fee $1,240.32 $1,240.32 Paid 07/11/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Foundation Inspection - Commercial Pending
Occupancy Inspection - Codes Residential Pending
Erosion Control Inspection Residential Pending
Miscellaneous Correction
Informational
01/17/2025
Full erosion control measures are in place and must be properly maintained until CofO
Driveway Inspection Pending
Misc
Informational
03/24/2025
3-24-25 Driveway is formed up with aggregate place and compacted. Ready for concrete.
Plot Plan Inspection Pending 5/8/2025
Footing Inspection - Residential Passed 9/10/2024 9/10/2024 09/10/2024
Sewer Service Inspection - R Partial 10/3/2024 10/3/2024 10/03/2024
Misc
Informational
10/03/2024
- 1444 ONLY
Water Service Inspection - R Partial 10/3/2024 10/3/2024 10/03/2024
Misc
Corrective Action Required
10/03/2024
- 1444, 1442 PARTIAL, POLY OUT OF FOUNDATION
Erosion Control Inspection Residential Failed 10/3/2024 10/03/2024
DCM6 ESC INSP DENIED STREET CLEAN UP
Corrective Action Required
10/03/2024
REQUESTED INSPECTION(S) DENIED. STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED. - CLEAN STORM INLET - REPAIR SILT FENCE
Sewer Service Inspection - R Passed 10/4/2024 10/4/2024 10/04/2024
Misc
Informational
10/03/2024
- 1444 and 1442
Water Service Inspection - R Partial 10/4/2024 10/4/2024 10/04/2024
Misc
Corrective Action Required
10/03/2024
- 1444, 1442 PARTIAL, POLY OUT OF FOUNDATION
Water Service Inspection - R Passed 10/4/2024 10/4/2024 10/04/2024
Misc
Resolved
10/04/2024
- 1444, 1442 PARTIAL, POLY OUT OF FOUNDATION
Underslab Electrical Inspection - Residential Passed 10/8/2024 10/8/2024 10/08/2024
Erosion Control Inspection Residential Partial 10/8/2024 10/8/2024 10/08/2024
DCM6 ESC INSP DENIED STREET CLEAN UP
Resolved
10/08/2024
REQUESTED INSPECTION(S) DENIED. STREET CLEAN UP REQUIRED IMMEDIATELY, AND SHALL BE COMPLETED PRIOR TO REQUESTED INSPECTION(S) BEING PERFORMED. - CLEAN STORM INLET - REPAIR SILT FENCE
Miscellaneous Correction
Informational
10/08/2024
Full erosion control measures are in place and must be properly maintained until CofO
Underslab Plumbing Inspection - Residential Passed 10/11/2024 10/11/2024 10/11/2024
Misc
Resolved
10/03/2024
Erosion Control Inspection Residential Failed 10/11/2024 10/11/2024
Miscellaneous Correction
Resolved
10/11/2024
Full erosion control measures are in place and must be properly maintained until CofO
Miscellaneous Correction
Corrective Action Required
10/11/2024
Gravel from the street to the foundation has been covered with dirt from dirt work being done. Restore as soon as possible Full erosion control measures must be in place and properly maintained until CofO
Suspended Slab Inspection Passed 10/24/2024 10/24/2024
Miscellaneous Correction
Informational
10/24/2024
Garage suspended slab passed by a third party
Erosion Control Inspection Residential Partial 12/19/2024 12/19/2024
Miscellaneous Correction
Resolved
12/19/2024
Gravel from the street to the foundation has been covered with dirt from dirt work being done. Restore as soon as possible Full erosion control measures must be in place and properly maintained until CofO
Miscellaneous Correction
Informational
12/19/2024
Full erosion control measures are in place and must be properly maintained until CofO
Electrical Service Inspection Passed 12/19/2024 12/19/2024
Gas Service Inspection - Residential Passed 12/19/2024 12/19/2024
Rated Assembly Inspection Failed 12/19/2024 12/19/2024 12/19/2024
Miscellaneous Correction
Corrective Action Required
12/19/2024
Both units Nail sheet rock 8 inches on center to rafter in garage Everything else passed
All Rough Inspection - Residential Failed 12/19/2024 12/19/2024 12/19/2024
Miscellaneous Correction
Corrective Action Required
12/19/2024
1442 and 1444 SW Winthrop. All rough 1442 Bottom plate anchor bolt in garage at S/E demising wall needs to be located within 4-12 inches from the end of the plate Sister 2x4 king stud that has been over notched for an anchor bolt in garage at demising wall Install purlin strut above stairs every 4 feet on center Install purlin struts above living room every 4 feet on center Stud shoe in bathroom 2 is missing nails Nail master bedroom corner at demising wall to code Vertically fire block every 10 feet between bedroom 3-4 and bathroom 3 Strap 2x10 floor joist in game room where electrical has been drilled within 2 inches of the edge 1444 Install garage PFH anchor bolt in middle 1/3 of bottom plate (south side) Nail N/E corner of bedroom 2 to code Nail master bedroom outside corner to demising wall to code Air supply lines in basement by stairs, needs to be supported by brackets every 10 feet on center Install Support 2 inch DWV in game room to storage every 6 feet on center Stud shoe Fire block above Ibeam in game room to WIC 4 Support gas pipe in game room to WIC 4 every 10 feet on center Stud shoe Vertically fire block every 10 feet between bedroom 3-4 and bathroom 3 Water supply line for bathroom 3 is outside the stud into bedroom 4 Bottom stair string beams going to basement are not supported by at least 1 1/2 inches on the double 2x10
Rated Assembly Inspection Partial 12/27/2024 12/27/2024 12/27/2024
Miscellaneous Correction
Resolved
12/27/2024
Both units Nail sheet rock 8 inches on center to rafter in garage Everything else passed
Miscellaneous Correction
Informational
12/27/2024
Above ceiling and demising wall basement rim board on both sides passed and are okay to cover This is a partial pass only
All Rough Inspection - Residential Passed 12/27/2024 12/27/2024 12/27/2024
Miscellaneous Correction
Resolved
12/27/2024
1442 and 1444 SW Winthrop. All rough 1442 Bottom plate anchor bolt in garage at S/E demising wall needs to be located within 4-12 inches from the end of the plate Sister 2x4 king stud that has been over notched for an anchor bolt in garage at demising wall Install purlin strut above stairs every 4 feet on center Install purlin struts above living room every 4 feet on center Stud shoe in bathroom 2 is missing nails Nail master bedroom corner at demising wall to code Vertically fire block every 10 feet between bedroom 3-4 and bathroom 3 Strap 2x10 floor joist in game room where electrical has been drilled within 2 inches of the edge 1444 Install garage PFH anchor bolt in middle 1/3 of bottom plate (south side) Nail N/E corner of bedroom 2 to code Nail master bedroom outside corner to demising wall to code Air supply lines in basement by stairs, needs to be supported by brackets every 10 feet on center Install Support 2 inch DWV in game room to storage every 6 feet on center Stud shoe Fire block above Ibeam in game room to WIC 4 Support gas pipe in game room to WIC 4 every 10 feet on center Stud shoe Vertically fire block every 10 feet between bedroom 3-4 and bathroom 3 Water supply line for bathroom 3 is outside the stud into bedroom 4 Bottom stair string beams going to basement are not supported by at least 1 1/2 inches on the double 2x10
Erosion Control Inspection Residential Partial 1/17/2025 01/17/2025
Miscellaneous Correction
Informational
12/19/2024
Full erosion control measures are in place and must be properly maintained until CofO
Rated Assembly Inspection Passed 1/17/2025 1/17/2025 01/17/2025
Miscellaneous Correction
Resolved
01/17/2025
Above ceiling and demising wall basement rim board on both sides passed and are okay to cover This is a partial pass only
Driveway Inspection Passed 3/24/2025 3/24/2025 04/01/2025
Misc
Informational
03/24/2025
3-24-25 BR Driveway is formed up with aggregate place and compacted. Ready for concrete. 4-1-25 BR Driveway is constructed to LS specifications.
Sidewalk Inspection Passed 4/22/2025 4/22/2025 04/22/2025
Misc
Informational
04/17/2025
04-17-25 Jamie S, SW is formed, compacted and slopes are in compliance with city standards. 4-22-25 BR Sidewalk is constructed to LS specifications.
Sidewalk Inspection Passed 4/22/2025 4/22/2025 04/22/2025
Misc
Informational
04/17/2025
04-17-25 Jamie S, SW is formed, compacted and slopes are in compliance with city standards. 4-22-25 BR Sidewalk is constructed to LS specifications.
Documents & Images
Date Uploaded File Type Document Name
06/04/2024 Application - Lot 53
06/04/2024 Tax Form - Lot 53
06/06/2024 Permit Codes Residential Plan Review
06/06/2024 Approved Plans APPROVED PLANS
06/24/2024 Permit Codes Residential Plan Review
06/24/2024 Plot Plan APPROVED PLOT PLAN
07/11/2024 Permit DS Building Permit
07/11/2024 Receipt Receipt for transaction: 2024-005744
09/10/2024 Letter INSPECTION SUMMARY
09/26/2024 Approved Plans APPROVED PLANS
10/03/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
10/03/2024 Letter INSPECTION SUMMARY
10/04/2024 Letter INSPECTION SUMMARY
10/04/2024 Letter INSPECTION SUMMARY
10/04/2024 Letter INSPECTION SUMMARY
10/08/2024 Letter INSPECTION SUMMARY
10/08/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/11/2024 Letter INSPECTION SUMMARY
10/23/2024 2024_10_22_1442-44 SW Winthrop Terrace_Gslab_Report_Sealed
10/24/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/19/2024 Letter INSPECTION SUMMARY
12/27/2024 Letter INSPECTION SUMMARY
12/27/2024 Letter INSPECTION SUMMARY
01/17/2025 Letter INSPECTION SUMMARY
01/17/2025 Letter INSPECTION SUMMARY
03/24/2025 Letter INSPECTION SUMMARY
04/01/2025 Letter INSPECTION SUMMARY
04/01/2025 Letter INSPECTION SUMMARY
04/17/2025 Letter INSPECTION SUMMARY
04/22/2025 Letter INSPECTION SUMMARY
04/22/2025 Letter INSPECTION SUMMARY
04/22/2025 Letter INSPECTION SUMMARY
05/06/2025 As Grade Plot Plan - Lot 53
05/07/2025 Plot Plan APPROVED AS GRADED PLOT PLAN
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.