Summary
PRRES20242006
Building Permit - Residential
Final Completion
MILLS BARBARA JEAN
NEW OTHER (RESIDENTIAL)
INSTALL 100 AMP SERVICE FOR MONUMENT
04/22/2024
04/22/2024
09/13/2024
Locations
Contacts
TEAGUE ELECTRIC CONSTRUCTION INC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
AGARCIA@TEAGUEELECTRIC.COM  
MILLS BARBARA JEAN, Address:258 NE EDGEWATER DR  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 04/22/2024 04/22/2024
Andrea Sessler
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New Other $50.00 $50.00 Paid 04/22/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Electrical Service Inspection Failed 5/6/2024 5/6/2024 05/06/2024
Misc
Corrective Action Required
05/06/2024
-Provide Bonding bushing and bond metal nipple to grounding buss bar -Bond metal service enclosure to grounded buss bar
Electrical Service Inspection Failed 9/5/2024 09/05/2024
Misc
Corrective Action Required
05/06/2024
-Provide min 36" depth of working space in front of the service equipment
Electrical Service Inspection Passed 9/13/2024 9/13/2024 09/13/2024
Misc
Resolved
09/13/2024
-Provide min 36" depth of working space in front of the service equipment
Final Inspection - Residential Passed 5/6/2024 9/13/2024 09/13/2024
Documents & Images
Date Uploaded File Type Document Name
04/22/2024 Scope of Work SCOPE OF WORK
04/22/2024 Permit DS Building Permit
04/22/2024 Receipt Receipt for transaction:2024-002571
05/06/2024 Letter INSPECTION SUMMARY
09/05/2024 Letter INSPECTION SUMMARY
09/05/2024 Letter INSPECTION SUMMARY
09/13/2024 Letter INSPECTION SUMMARY
09/13/2024 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home