Summary
PRRES20241347
Building Permit - Residential
Certificate of Occupancy
CHOYCE LLC
NEW 3 OR 4 FAMILY
NEW THREE PLEX. FINISHED/UNFINISHED BASEMENTS. COVERED DECKS. ROOF TRUSSES - DEFERRED.
03/21/2024
04/02/2024
09/22/2024
05/19/2025
Locations
Contacts
KEVIN HIGDON CONSTRUCTION, LLC, Address:P O BOX 847, Phone:(816) 524-9797  
CHOYCE LLC, Address:PO BOX 847  
kevin higdon, Address:po box 847  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
INTERSTATE CONSTRUCTION SERVICES, Address:1450 SE BROADWAY DR, Phone:(816) 524-9797  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
DOUG@HIGDONBUILDERS.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee for New 3 or 4 Family $4,079.23 $4,079.23 Paid 04/02/2024
Water Tap Fee $11,280.00 $11,280.00 Paid 04/02/2024
Water Meter Fee $2,041.38 $2,041.38 Paid 04/02/2024
Sanitary Sewer Development Fee $6,477.00 $6,477.00 Paid 04/02/2024
Right of Way Permit Fee $85.00 $85.00 Paid 04/02/2024
Residential Excise Tax Fee $1,860.48 $1,860.48 Paid 04/02/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 01/09/2025
Temporary Occupancy Fee $50.00 $50.00 Paid 01/13/2025
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Residential Passed 5/22/2024 5/22/2024 05/22/2024
Underslab Electrical Inspection - Residential Passed 5/22/2024 5/22/2024 05/22/2024
Sewer Service Inspection - R Passed 5/29/2024 5/29/2024 05/29/2024
Water Service Inspection - R Partial 5/30/2024 5/30/2024 05/30/2024
Misc
Corrective Action Required
05/30/2024
Partial water lines from building to meter location-OK
Water Service Inspection - R Passed 5/31/2024 05/31/2024
Misc
Resolved
05/31/2024
Partial water lines from building to meter location-OK
Rated Assembly Inspection Passed 10/23/2024 10/23/2024 10/23/2024
MISC
Informational
10/23/2024
824, 826, 828
Gas Service Inspection - Residential Partial 10/23/2024 10/23/2024 10/23/2024
Misc
Corrective Action Required
10/23/2024
828 only approved
Electrical Service Inspection Partial 10/23/2024 10/23/2024 10/23/2024
Misc
Corrective Action Required
10/23/2024
- Disconnect, meters approved - 828 approved only
All Rough Inspection - Residential Failed 10/23/2024 10/23/2024 10/23/2024
Misc
Corrective Action Required
10/23/2024
828 - Fire block top plate at fire place - Fire block penetration at shower main floor front - Anchor bolts to be middle third of plate basement North East bedroom 824, 826 not inspected
Erosion Control Inspection Residential Failed 10/31/2024 10/31/2024
DCM5 ESC INSP DENIED
Corrective Action Required
10/31/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION.
All Rough Inspection - Residential Failed 10/31/2024 10/31/2024 10/31/2024
Misc
Corrective Action Required
10/23/2024
**Inspection denied due to lack of erosion control 828 - Fire block top plate at fire place - Fire block penetration at shower main floor front - Anchor bolts to be middle third of plate basement North East bedroom 824, 826 not inspected
Gas Service Inspection - Residential Failed 10/31/2024 10/31/2024 10/31/2024
Misc
Corrective Action Required
10/23/2024
**10/31-Inspection denied due to lack of erosion control 828 only approved
Electrical Service Inspection Failed 10/31/2024 10/31/2024 10/31/2024
Misc
Corrective Action Required
10/23/2024
**10/31-Inspection denied due to lack of erosion control - 828 approved only
Electrical Service Inspection Passed 11/4/2024 11/4/2024 11/04/2024
Misc
Resolved
11/04/2024
**10/31-Inspection denied due to lack of erosion control
Gas Service Inspection - Residential Passed 11/4/2024 11/4/2024 11/04/2024
Misc
Resolved
11/04/2024
**10/31-Inspection denied due to lack of erosion control
Erosion Control Inspection Residential Failed 11/4/2024 11/04/2024
DCM5 ESC INSP DENIED
Corrective Action Required
10/31/2024
-Install erosion control around rear storm inlet
All Rough Inspection - Residential Failed 11/4/2024 11/4/2024 11/04/2024
Misc
Corrective Action Required
10/31/2024
**Provide truss package on site Outside: -Provide flashings above window trims -Nail siding to sill plates @ 6” oc 824: -Connect duct to bathroom fans -Support bath fan flex ducts -Provide engineer fix for broken truss above master closet -Fb laundry wall from attic -Fb gap between firewall and bottom of roof deck -Security blocking at deck door -Fb basement all wall from soffit space -Anchor sill plate per code at rear basement Rec room wall **OK TO INSULATE 826: -Extend firewall through garage soffit; seal gap -Remove construction debris from attic -Support bath fan flex ducts -Provide engineer fix for broken truss above master bathroom -Fb laundry wall from attic -Fb gap between firewall and bottom of roof deck -Secure shaft wall to framing -Protect plumbing at basement bathroom top plate -Fb basement all wall from soffit space **OK TO INSULATE 828: -Nail ZIP sheathing to studs @ 12” oc -Nail garage PFH wall sheathing to studs @3” oc -Extend firewall through garage soffit; seal gap **OK TO INSULATE
All Rough Inspection - Residential Failed 11/18/2024 11/18/2024 11/18/2024
Misc
Corrective Action Required
11/04/2024
**Provide truss package on site Outside: -Provide flashings above window trims -Nail siding to sill plates @ 6” oc 824: -Connect duct to bathroom fans -Support bath fan flex ducts -Provide engineer fix for broken truss above master closet **OK TO INSULATE 826: -Support bath fan flex ducts **min 1.5” wide straps, not zip ties -Provide engineer fix for broken truss above master bathroom -Secure shaft wall to framing **OK TO INSULATE 828-OK to rock
Driveway Inspection Partial 11/20/2024 11/20/2024 11/20/2024
Misc
Informational
11/20/2024
11-20-24 NS Site visited driveway and sidewalk meet city standards for pre-pour.
Sidewalk Inspection Partial 11/20/2024 11/20/2024 11/20/2024
Misc
Informational
11/20/2024
11-20-24 NS Site visited driveway and sidewalk meet city standards for pre-pour.
All Rough Inspection - Residential Failed 11/22/2024 11/22/2024 11/22/2024
Misc
Corrective Action Required
11/18/2024
Outside: -Provide flashings above window trims -Nail siding to sill plates @ 6” oc 824: -Install truss hangers above rear dining per truss layout -Provide engineer fix for broken truss above master closet **OK TO INSULATE 826, 828-OK to rock
All Rough Inspection - Residential Failed 12/9/2024 12/9/2024 12/09/2024
Misc
Corrective Action Required
11/22/2024
Outside: -Provide flashings above window trims -Nail siding to sill plates @ 6” oc 824: -Install truss hangers above rear dining per truss layout **Need truss layout -Provide engineer fix for broken truss above master closet. **Get back with engineer for the proper fix. The upper part of the broken original 2x3 truss member was taken out and replaced with the 2x4, then attached back to the truss at the gusset plate. This is not allowed and must be address by the truss engineer 826, 828-OK to rock
All Rough Inspection - Residential Passed 12/17/2024 12/17/2024 12/17/2024
Misc
Resolved
12/17/2024
Outside: -Provide flashings above window trims -Nail siding to sill plates @ 6” oc 824: -Install truss hangers above rear dining per truss layout **Need truss layout -Provide engineer fix for broken truss above master closet. **Get back with engineer for the proper fix. The upper part of the broken original 2x3 truss member was taken out and replaced with the 2x4, then attached back to the truss at the gusset plate. This is not allowed and must be address by the truss engineer 826, 828-OK to rock
Sidewalk Inspection Failed 12/20/2024 12/20/2024
Misc
Informational
11/20/2024
11-20-24 NS Site visited driveway and sidewalk meet city standards for pre-pour. 12-20-24 Dustin A, sw is poured . 2 panels attaching to existing on west side are not ada compliant. Pablo is aware and said he would get it fixed this is for 824
Sidewalk Inspection Failed 12/20/2024 12/20/2024 12/20/2024
Misc
Informational
12/20/2024
11-20-24 NS Site visited driveway and sidewalk meet city standards for pre-pour. 12-20-24 Dustin A, sw is poured . 2 panels attaching to existing on west side are not ada compliant. Pablo is aware and said he would get it fixed for 824 12-20-24 Dustin A, 828 was called in and depths of aggregate are not compliant
Sidewalk Inspection Partial 12/20/2024 12/20/2024 12/20/2024
Misc
Informational
12/20/2024
11-20-24 NS Site visited driveway and sidewalk meet city standards for pre-pour. 12-20-24 Dustin A, sw is poured . 2 panels attaching to existing on west side are not ada compliant. Pablo is aware and said he would get it fixed 12-20-24 Dustin A, 828 was called in and depths of aggregate are not compliant. 12-20-24 Dustin A,828 was called back in. Was dug deeper. Checked slopes and it is in compliane. Approved to pour
Footing Inspection - Residential Passed 01/08/2025
Informational
01/08/2025
Footing approved by engineer
Occupancy Inspection - Codes Residential Failed 1/8/2025 1/8/2025 01/08/2025
Misc
Corrective Action Required
01/08/2025
Unit 828 only: -Obtain lawn irrigation permit and submit backflow valve test report to city -Sewer manhole at front -Sidewalk and driveway not approved on record -As-graded plot plan is required -Final grade, sod, gutter, downspout and sump pump extension -Seal exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc -Secure AC whip within 12” of disconnect -Install tamper-proof caps at AC valves -Provide sewer tracer wire port at grade -Install kitchen hood -Master bathroom fan not working -Provide min 30 amp-rated circuit for cooktop -Install sump pump with battery backup -Provide a continuous and uninterrupted handrail for deck stair. -Install two 1/2” lag screws at each end of ledger board
Occupancy Inspection - Codes Residential Ready for Temp CO 1/9/2025 1/9/2025 01/09/2025
Misc
Corrective Action Required
01/08/2025
Unit 828 only: -Obtain lawn irrigation permit and submit backflow valve test report to city -Sewer manhole at front -Sidewalk and driveway not approved on record -As-graded plot plan is required -Final grade, sod, gutter, downspout and sump pump extension -Seal exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc -Provide sewer tracer wire port at grade -Provide a continuous and uninterrupted handrail for deck stair. -Install two 1/2” lag screws at each end of ledger board **TCO approved for unit 828
Occupancy Inspection - Codes Residential Ready for Temp CO 1/13/2025 01/13/2025
Misc
Corrective Action Required
01/09/2025
Unit 828 only: -Obtain lawn irrigation permit and submit backflow valve test report to city -Sewer manhole at front -Sidewalk and driveway not approved on record -As-graded plot plan is required -Final grade, sod, gutter, downspout extension -Provide sewer tracer wire port at grade **TCO approved for unit 828
Occupancy Inspection - Codes Residential Temporary C of O 1/15/2025 01/15/2025
Misc
Corrective Action Required
01/13/2025
Unit 828 only: -Obtain lawn irrigation permit and submit backflow valve test report to city -Sidewalk and driveway not approved on record -As-graded plot plan is required -Final grade, sod, gutter, downspout extension **TCO approved for unit 828
Plot Plan Inspection Passed 3/19/2025 03/19/2025
Driveway Inspection Passed 04/21/2025
Misc
Informational
11/20/2024
11-20-24 NS Site visited driveway and sidewalk meet city standards for pre-pour. 4-21-25 NS site visited for after pour inspection and it appears sidewalk and driveway meet city standards
Sidewalk Inspection Passed 1/3/2025 1/3/2025 04/21/2025
Misc
Informational
12/20/2024
11-20-24 NS Site visited driveway and sidewalk meet city standards for pre-pour. 12-20-24 Dustin A, sw is poured . 2 panels attaching to existing on west side are not ada compliant. Pablo is aware and said he would get it fixed 12-20-24 Dustin A, 828 was called in and depths of aggregate are not compliant. 12-20-24 Dustin A,828 was called back in. Was dug deeper. Checked slopes and it is in compliane. Approved to pour 4-21-25 NS site visited for after pour inspection and it appears sidewalk and driveway meet city standards
Erosion Control Inspection Residential Passed 05/05/2025
DCM5 ESC INSP DENIED
Resolved
05/05/2025
-Install erosion control around rear storm inlet
Occupancy Inspection - Codes Residential Failed 5/5/2025 5/5/2025 05/05/2025
Misc
Corrective Action Required
01/15/2025
Unit 826: -Obtain lawn irrigation permit and submit backflow valve test report to city -Water meter is buried -Reconnect sump pump discharge pipe -Kitchen island receptacle and receptacle adjacent to microwave are not gfci-protected; island receptacle shall be tamper-resistant -Install dedicated duplex receptacles for dump pump and battery backup Unit 824: -Sewer tracer port -Support front stoop receptacle yoke -Kitchen gfi receptacle adjacent to range keeps tripping -Install dedicated duplex receptacles for dump pump and battery backup **TCO approved for unit 828
Occupancy Inspection - Codes Residential Full C of O 5/19/2025 5/19/2025 05/19/2025
Misc
Resolved
05/19/2025
Unit 826: Unit 824: **TCO approved for unit 828
Documents & Images

No documents are currently available for viewing.

Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents