Permit Application Status

PRRES20236029


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20236029
Building Permit - Residential
Certificate of Occupancy
CHOYCE LLC
NEW 3 OR 4 FAMILY
NEW TRIPLEX - UNFINISHED AND FINISHED BASEMENT - COVERED DECKS - ROOF TRUSSES (DEF) - TILE ROOF
11/14/2023
12/12/2023
05/20/2024
03/17/2025
Locations
Contacts
KEVIN HIGDON CONSTRUCTION, LLC, Address:P O BOX 847, Phone:(816) 524-9797  
CHOYCE LLC, Address:PO BOX 847  
kevin higdon, Address:po box 847  
KEVIN@HIGDONBUILDERS.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
INTERSTATE CONSTRUCTION SERVICES, Address:1450 SE BROADWAY DR, Phone:(816) 524-9797  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New 3 or 4 Family $4,017.66 $4,017.66 Paid 12/12/2023
8331507-Sanitary Sewer Development Fee $6,477.00 $6,477.00 Paid 12/12/2023
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 12/12/2023
7232302-Residential License Tax Fee $1,860.48 $1,860.48 Paid 12/12/2023
8331401-Water Tap Fee $11,280.00 $11,280.00 Paid 12/12/2023
8350015-Water Meter Fee $2,041.38 $2,041.38 Paid 12/12/2023
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 03/12/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 11/06/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 11/06/2024
Outstanding Fees Amount Paid Owing Date Paid


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Erosion Control Inspection Residential Failed 2/29/2024 02/29/2024
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
02/29/2024
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Sewer Service Inspection - R Passed 2/29/2024 2/29/2024 02/29/2024
Erosion Control Inspection Residential Failed 3/4/2024 03/04/2024
DCM5 ESC INSP DENIED
Corrective Action Required
02/29/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. -PROVIDE EROSION CONTROL ALONG THE STREET, INCLUDING THE EAST SIDE OF THE LOT -PROVIDE EROSION CONTROL AROUND THE REAR STORM INLET
Underslab Plumbing Inspection - Residential Not Ready 3/4/2024 3/4/2024 03/04/2024
Misc
Corrective Action Required
03/04/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. -PROVIDE EROSION CONTROL ALONG THE STREET, INCLUDING THE EAST SIDE OF THE LOT -PROVIDE EROSION CONTROL AROUND THE REAR STORM INLET
Erosion Control Inspection Residential Failed 3/5/2024 03/05/2024
DCM5 ESC INSP DENIED
Corrective Action Required
03/04/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. -PROVIDE EROSION CONTROL ALONG THE STREET, INCLUDING THE EAST SIDE OF THE LOT -PROVIDE EROSION CONTROL AROUND THE REAR STORM INLET
Underslab Plumbing Inspection - Residential Not Ready 3/5/2024 3/5/2024 03/05/2024
Misc
Corrective Action Required
03/04/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. -PROVIDE EROSION CONTROL ALONG THE STREET, INCLUDING THE EAST SIDE OF THE LOT -PROVIDE EROSION CONTROL AROUND THE REAR STORM INLET
Underslab Electrical Inspection - Residential Not Ready 3/5/2024 3/5/2024 03/05/2024
Misc
Corrective Action Required
03/05/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. -PROVIDE EROSION CONTROL ALONG THE STREET, INCLUDING THE EAST SIDE OF THE LOT -PROVIDE EROSION CONTROL AROUND THE REAR STORM INLET
Underslab Electrical Inspection - Residential Passed 3/14/2024 3/14/2024 03/14/2024
Misc
Resolved
03/14/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. -PROVIDE EROSION CONTROL ALONG THE STREET, INCLUDING THE EAST SIDE OF THE LOT -PROVIDE EROSION CONTROL AROUND THE REAR STORM INLET
Underslab Plumbing Inspection - Residential Passed 3/14/2024 3/14/2024 03/14/2024
Misc
Resolved
03/14/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. -PROVIDE EROSION CONTROL ALONG THE STREET, INCLUDING THE EAST SIDE OF THE LOT -PROVIDE EROSION CONTROL AROUND THE REAR STORM INLET
Erosion Control Inspection Residential Passed 3/14/2024 03/14/2024
DCM5 ESC INSP DENIED
Resolved
03/14/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. -PROVIDE EROSION CONTROL ALONG THE STREET, INCLUDING THE EAST SIDE OF THE LOT -PROVIDE EROSION CONTROL AROUND THE REAR STORM INLET
Water Service Inspection - R Passed 3/14/2024 3/14/2024 03/14/2024
Erosion Control Inspection Residential Failed 8/9/2024 08/09/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
08/09/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
DCM5 ESC INSP DENIED
Corrective Action Required
08/09/2024
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. - NO ADDRESS POSTED - NO GRAVEL FILTER - NO EROSION CONTROL IN PLACE SILT FENCE ALL DOWN
All Rough Inspection - Residential Failed 8/9/2024 8/9/2024 08/09/2024
Misc
Corrective Action Required
08/09/2024
INSPECTION DENIDE - NO ADDRESS POSTED - NO GRAVEL FILTER - NO EROSION CONTROL IN PLACE SILT FENCE ALL DOWN 2 WORKING DAYS TO BE COMPLIENT
Electrical Service Inspection Failed 8/20/2024 8/20/2024 08/20/2024
Misc
Corrective Action Required
08/20/2024
Ground service to ufer rebar
Gas Service Inspection - Residential Failed 8/20/2024 8/20/2024 08/20/2024
Misc
Corrective Action Required
08/20/2024
-Complete underground gas line to middle unit *pressure test for interior gas line OK
All Rough Inspection - Residential Failed 8/20/2024 8/20/2024 08/20/2024
Misc
Corrective Action Required
08/09/2024
**RESTORE EROSION CONTROL ALONG EAST SIDE; GRAVEL AT DRIVEWAYS **Provide truss plan on site 825: -Secure shaft wall to framing -Tie down girder trusses to wall; trusses to entry wall -Provide 4 studs at girder support in front closet -Roof ventilation cannot be within 4 ft of firewall -Engineer to address repair for damaged truss above master bathroom -Double every other joists under bathroom tile floor per plan 827: -Nail siding to sill plate near AC unit -Tie down front girder truss to wall -Close gap at top of firewall above master bathroom -Provide 4 studs at girder support in front closet 829: -Secure shaft wall to framing -Install roof flashing for plumbing -Nail stud at master bathroom wall intersection -Engineer to address repair for damaged truss above master closet -Tie down front girder truss to wall -Provide 4 studs at girder support in front closet **OK TO INSULATE
Erosion Control Inspection Residential Failed 8/20/2024 08/20/2024
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
08/09/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
DCM5 ESC INSP DENIED
Resolved
08/20/2024
Rated Assembly Inspection Passed 8/20/2024 8/20/2024 08/20/2024
Electrical Service Inspection Passed 8/30/2024 8/30/2024 08/30/2024
Misc
Resolved
08/30/2024
Ground service to ufer rebar
Gas Service Inspection - Residential Passed 8/30/2024 8/30/2024 08/30/2024
Misc
Resolved
08/30/2024
-Complete underground gas line to middle unit *pressure test for interior gas line OK
All Rough Inspection - Residential Failed 8/30/2024 8/30/2024 08/30/2024
Misc
Corrective Action Required
08/20/2024
825: -Roof ventilation cannot be within 4 ft of firewall **Cover the damaged area with FlameBlock board 827: 829: -Engineer to address repair for damaged truss above master closet, master bed, and garage. Check throughout
All Rough Inspection - Residential Failed 9/9/2024 09/09/2024
Misc
Corrective Action Required
08/30/2024
825, 827: OK to rock 829: -Engineer to address repair for damaged truss above master bed
Footing Inspection - Residential Passed 09/09/2024
Informational
09/09/2024
Footing approved by engineer
Driveway Inspection Partial 9/11/2024 9/11/2024 09/11/2024
Misc
Informational
09/11/2024
9-11-24 NS Site visited and it appears that driveway meets city standards will come back and check after it is poured
Sidewalk Inspection Partial 9/12/2024 9/12/2024 09/12/2024
Misc
Informational
09/12/2024
9-12-24 DP SW was formed, aggregate compacted, cross slopes in compliance but conditions can change. Approved to pour.
Sidewalk Inspection Partial 9/12/2024 9/12/2024 09/12/2024
Misc
Informational
09/12/2024
9-12-24 DP SW was formed, aggregate compacted, cross slopes in compliance but conditions can change. Approved to pour. This is for sidewalk at 825 827 829
All Rough Inspection - Residential Failed 9/17/2024 9/17/2024 09/17/2024
Misc
Corrective Action Required
09/09/2024
825, 827: OK to rock 829: -Engineer to address repair for damaged truss above master bed **Engineer repair requires 2x4 scab on each face of the truss
All Rough Inspection - Residential Passed 9/17/2024 09/17/2024
Misc
Resolved
09/17/2024
825, 827: OK to rock 829: -Engineer to address repair for damaged truss above master bed **Engineer repair requires 2x4 scab on each face of the truss
Plot Plan Inspection Passed 10/24/2024 10/24/2024
Erosion Control Inspection Residential Passed 11/5/2024 11/05/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
11/05/2024
EROSION CONTROL REQUIRED. EROSION CONTROL SHALL BE IN COMPLIANCE WITHIN TWO BUSINESS DAYS.
Occupancy Inspection - Codes Residential Failed 11/5/2024 11/5/2024 11/05/2024
Misc
Corrective Action Required
11/05/2024
829: -Obtain lawn irrigation permit and submit backflow valve test report to city -Sidewalk and driveway not approved on record -Splash block at downspout -Dryer duct length exceed code. Max allowed length is 20 ft with current number of elbows. -Fb floor opening below bathroom tub -Provide water pressure regulator **Only 829 inspected
Occupancy Inspection - Codes Residential Ready for Temp CO 11/6/2024 11/6/2024 11/06/2024
Misc
Corrective Action Required
11/05/2024
-Sidewalk and driveway not approved on record **Only 829 inspected **TCO approved for 829
Driveway Inspection Passed 11/07/2024
Misc
Informational
09/11/2024
9-11-24 NS Site visited and it appears that driveway meets city standards will come back and check after it is poured 11-7-24 NS site visited and it appears driveway and sidewalk meet city standards passed
Sidewalk Inspection Passed 11/07/2024
Misc
Informational
09/12/2024
9-12-24 DP SW was formed, aggregate compacted, cross slopes in compliance but conditions can change. Approved to pour. This is for sidewalk at 825 827 829 11-7-24 NS site visited and it appears driveway and sidewalk meet city standards passed
Occupancy Inspection - Codes Residential Failed 3/5/2025 3/7/2025 03/07/2025
Misc
Corrective Action Required
11/06/2024
**Only 829 inspected **TCO approved for 829
Misc
Corrective Action Required
03/07/2025
Outside: -Label units on service disconnects -Install screens at dryer exhaust dampers 825: -Master bedroom smoke alarm not interconnected -Verify that the master shower door is safety tempered glazing -Dryer duct length exceed maximum allowed. Provide compliance with IRC M1502.4.5&6 827: -Verify that the master shower door is safety tempered glazing -Dryer duct length exceed maximum allowed. Provide compliance with IRC M1502.4.5&6 -Provide afci protection for master closet outlets **Dryer duct length requirements ** M1502.4.5 Duct length. The maximum allowable exhaust duct length shall be determined by one of the methods specified in Sections M1502.4.5.1 through M1502.4.5.3. M1502.4.5.1 Specified length. The maximum length of the exhaust duct shall be 35 feet (10 668 mm) from the connection to the transition duct from the dryer to the outlet terminal. Where fittings are used, the maximum length of the exhaust duct shall be reduced in accordance with Table M1502.4.5.1. The maximum length of the exhaust duct does not include the transition duct. M1502.4.5.2 Manufacturer's instructions. The size and maximum length of the exhaust duct shall be determined by the dryer manufacturer's installation instruc-tions. The code official shall be provided with a copy of the installation instructions for the make and model of the dryer at the concealment inspection. In the absence of fitting equivalent length calculations from the clothes dryer manufacturer, Table M1502.4.5.1 shall be used. M1502.4.5.3 Dryer exhaust duct power ventilator. The maximum length of the exhaust duct shall be determined in accordance with the manufacturer's instructions for the dryer exhaust duct power ventilator. M1502.4.6 Length identification. Where the exhaust duct equivalent length exceeds 35 feet (10 668 mm), the equivalent length of the exhaust duct shall be identified on a permanent label or tag. The label or tag shall be located within 6 feet (1829 mm) of the exhaust duct connection.
Occupancy Inspection - Codes Residential Failed 3/11/2025 3/11/2025 03/11/2025
Misc
Corrective Action Required
03/07/2025
**Only 829 inspected **TCO approved for 829
Misc
Corrective Action Required
03/07/2025
Outside: -Label units on service disconnects -Install screens at dryer exhaust dampers 825: -Verify that the master shower door is safety tempered glazing -Dryer duct length exceed maximum allowed. Provide compliance with IRC M1502.4.5&6 827: -Verify that the master shower door is safety tempered glazing -Dryer duct length exceed maximum allowed. Provide compliance with IRC M1502.4.5&6 **M1502.4.6 Length identification. Where the exhaust duct equivalent length exceeds 35 feet (10 668 mm), the equivalent length of the exhaust duct shall be identified on a permanent label or tag. The label or tag shall be located within 6 feet (1829 mm) of the exhaust duct connection. The equivalent length is 35 ft + 10 ft for two elbows = 45 ft. The dryer must be able to exhaust min 45 ft
Occupancy Inspection - Codes Residential Full C of O 3/17/2025 3/17/2025 03/17/2025
Misc
Resolved
03/17/2025
**Only 829 inspected **TCO approved for 829
Misc
Resolved
03/17/2025
825: -Dryer duct length exceed maximum allowed. Provide compliance with IRC M1502.4.5&6 827: -Dryer duct length exceed maximum allowed. Provide compliance with IRC M1502.4.5&6 **M1502.4.6 Length identification. Where the exhaust duct equivalent length exceeds 35 feet (10 668 mm), the equivalent length of the exhaust duct shall be identified on a permanent label or tag. The label or tag shall be located within 6 feet (1829 mm) of the exhaust duct connection. The equivalent length is 35 ft + 10 ft for two elbows = 45 ft. The dryer must be able to exhaust min 45 ft
Documents & Images
Date Uploaded File Type Document Name
11/14/2023 Lees Summit Residental Permit Application lot 13 triplex chapel ridge
11/14/2023 TCR013 Triplex - Sealed Plans (November 13, 2023)
11/14/2023 LOT 13 FINAL
11/21/2023 Permit Codes Residential Plan Review
11/22/2023 TCR013 Triplex - Sealed Plans (November 21, 2023)
11/22/2023 Permit Codes Residential Plan Review
11/22/2023 Approved Plans APPROVED PLANS
11/22/2023 Plot Plan approved plot plan
11/22/2023 Permit Codes Residential Plan Review
12/12/2023 Permit DS Building Permit
12/12/2023 Receipt Receipt for transaction:2023-009054
02/29/2024 Letter INSPECTION SUMMARY
02/29/2024 Letter INSPECTION SUMMARY
02/29/2024 Engineer Report/Study 3RD PARTY INSPECTION
03/04/2024 Letter INSPECTION SUMMARY
03/04/2024 Letter INSPECTION SUMMARY
03/05/2024 Letter INSPECTION SUMMARY
03/05/2024 Letter INSPECTION SUMMARY
03/05/2024 Letter INSPECTION SUMMARY
03/12/2024 Receipt Receipt for transaction:2024-001549
03/14/2024 Letter INSPECTION SUMMARY
03/14/2024 Letter INSPECTION SUMMARY
03/14/2024 Letter INSPECTION SUMMARY
03/14/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter INSPECTION SUMMARY
08/09/2024 Letter INSPECTION SUMMARY
08/20/2024 Letter INSPECTION SUMMARY
08/20/2024 Letter INSPECTION SUMMARY
08/20/2024 Letter INSPECTION SUMMARY
08/20/2024 Letter INSPECTION SUMMARY
08/20/2024 Letter INSPECTION SUMMARY
08/20/2024 Letter INSPECTION SUMMARY
08/30/2024 240654 D4 & H3 Repairs
08/30/2024 Approved Plans APPROVED TRUSS PACKAGE
08/30/2024 Letter INSPECTION SUMMARY
08/30/2024 Letter INSPECTION SUMMARY
09/09/2024 Letter INSPECTION SUMMARY
09/09/2024 Letter INSPECTION SUMMARY
09/12/2024 Letter INSPECTION SUMMARY
09/12/2024 Letter INSPECTION SUMMARY
09/17/2024 240654 B4 Repair
09/17/2024 Letter INSPECTION SUMMARY
09/17/2024 Letter INSPECTION SUMMARY
09/17/2024 Letter INSPECTION SUMMARY
09/17/2024 Letter INSPECTION SUMMARY
10/22/2024 LOT 13 ASBUILT
10/23/2024 Plot Plan approved as graded plot plan
10/24/2024 Letter INSPECTION SUMMARY
11/05/2024 Letter INSPECTION SUMMARY
11/05/2024 Letter INSPECTION SUMMARY
11/06/2024 Letter INSPECTION SUMMARY
11/06/2024 Certificate/License Codes Temporary Certificate of Occupancy
11/06/2024 Receipt Receipt for transaction:2024-008787
11/07/2024 Letter INSPECTION SUMMARY
11/07/2024 Letter INSPECTION SUMMARY
03/07/2025 Letter INSPECTION SUMMARY
03/11/2025 Letter INSPECTION SUMMARY
03/17/2025 Letter Field Certificate of Occupancy
03/17/2025 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home