PRRES20226242


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20226242
Building Permit - Residential
Expired
HUNZIKER ROGER
ALTERATION SINGLE FAMILY
BASEMENT FINISH
12/27/2022
12/27/2022
Locations
Contacts
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
MPLUMBER49@GMAIL.COM  
HUNZIKER ROGER, Address:1604 SE WILLOW RD  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
TOTAL HOME SERVICE, Address:3408 N 26TH ST, Phone:(816) 405-6924  
Reviews
Review Type Outcome Est. Completion Date Completed
Licensed Contractors Approved 12/27/2022 12/27/2022
Brandon Kalwei
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for Add/Alter Single Family $111.13 $111.13 Paid 12/27/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Final Inspection - Residential Pending
All Rough Inspection - Residential Pending
Misc
Corrective Action Required
03/06/2023
- Dryer exhaust duct shall have a smooth interior finish and be constructed of metal not less than 0.0157 inch with a 4" diammeter. M1502.4.1 ** Al the way to outside - remove copper tubing and cap gas line at old laundry - cap drain at old laundry - missing outlet cover at sump pump - outlet at sump to be single and labeled non-GFCI - GFCI outlet to be within 24” of sink in bathroom - laundry outlet to be GFCI protected - All outlets in living areas must be AFCI protected - All electrical to be brought up to 2018 code GFCI"s installed were required. - label electrical panel OK to insulate and rock
Underslab Plumbing Inspection - Residential Passed 12/28/2022 12/28/2022
Misc
Informational
12/28/2022
inspected underslab plumbing for laundry and shower.
All Rough Inspection - Residential Failed 12/28/2022 12/28/2022 12/28/2022
Misc
Corrective Action Required
12/28/2022
- Fire block fur out vertically every 10’ - Fire block top of fur out to joist space - Install electrical panel - Land all electrical wiring - Provide combustion air vents, high and low - All outlets in living areas must be AFCI protected - All electrical to be brought up to 2018 code
All Rough Inspection - Residential Failed 1/4/2023 1/4/2023 01/04/2023
Misc
Corrective Action Required
12/28/2022
- Dryer exhaust duct shall have a smooth interior finish and be constructed of metal not less than 0.0157 inch with a 4" diammeter. M1502.4.1 - Install electrical panel - Land all electrical wiring - Provide combustion air vents, high and low - All outlets in living areas must be AFCI protected - All electrical to be brought up to 2018 code GFCI"s installed were required. OK to insulate and rock
Electrical Service Inspection Failed 3/2/2023 3/2/2023 03/02/2023
Misc
Corrective Action Required
03/02/2023
-Cut off the bare conductor from meter and service panel and connect the copper grounding conductor to the meter grounding lug -Route the rod grounding conductor inside pvc raceway or bond both ends of metal raceway to the grounding electrode conductor -Install the intersystem bonding terminal block -Shall ground the service to the copper water line -Shall bond the panel enclosure. Green main bonding screw not installed FYI: provide afci protection per code
All Rough Inspection - Residential Failed 3/6/2023 3/6/2023 03/06/2023
Misc
Corrective Action Required
01/04/2023
- Dryer exhaust duct shall have a smooth interior finish and be constructed of metal not less than 0.0157 inch with a 4" diammeter. M1502.4.1 ** Al the way to outside - remove copper tubing and cap gas line at old laundry - cap drain at old laundry - missing outlet cover at sump pump - outlet at sump to be single and labeled non-GFCI - GFCI outlet to be within 24” of sink in bathroom - laundry outlet to be GFCI protected - All outlets in living areas must be AFCI protected - All electrical to be brought up to 2018 code GFCI"s installed were required. - label electrical panel OK to insulate and rock
Electrical Service Inspection Failed 3/6/2023 3/6/2023 03/06/2023
Misc
Corrective Action Required
03/02/2023
-Cut off the bare conductor from meter and service panel and connect the copper grounding conductor to the meter grounding lug -Route the rod grounding conductor inside pvc raceway or bond both ends of metal raceway to the grounding electrode conductor -Shall ground the service to the copper water line FYI: provide afci protection per code
Electrical Service Inspection Passed 3/8/2023 3/8/2023 03/08/2023
Misc
Resolved
03/08/2023
Documents & Images
Date Uploaded File Type Document Name
12/27/2022 Application Form APPLICATION
12/27/2022 Approved Plans APPROVED BASEMENT FINISH
12/27/2022 Permit DS Building Permit
12/27/2022 Receipt Receipt for transaction:2022-009654
12/28/2022 Letter INSPECTION SUMMARY
12/28/2022 Letter INSPECTION SUMMARY
01/04/2023 Letter INSPECTION SUMMARY
03/02/2023 Letter INSPECTION SUMMARY
03/06/2023 Letter INSPECTION SUMMARY
03/06/2023 Letter INSPECTION SUMMARY
03/08/2023 Letter INSPECTION SUMMARY
07/26/2023 Letter Codes 140 Day Letter
01/16/2024 Letter Codes 180 Day Letter
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home