Permit Application Status

PRRES20221010


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20221010
Building Permit - Residential
Certificate of Occupancy
CHOYCE LLC
NEW SINGLE FAMILY
NEW HOUSE - TILE ROOF - UNFINISHED BASEMENT - COVERED PATIO
03/18/2022
03/23/2022
06/09/2023
Locations
Contacts
KEVIN HIGDON CONSTRUCTION, LLC, Address:P O BOX 847, Phone:(816) 524-9797  
CHOYCE LLC, Address:PO BOX 847  
Kevin higdon, Address:Po box 847  
KEVIN@HIGDONBUILDERS.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
INTERSTATE ELECTRICAL CONSTRUCTION, Address:3710 ROBINSON PIKE RD, Phone:(816) 761-0200  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $360.00 $360.00 Paid 03/23/2022
Right of Way Permit Fee $85.00 $85.00 Paid 03/23/2022
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 03/23/2022
Water Tap Fee $3,655.00 $3,655.00 Paid 03/23/2022
Water Meter Fee $479.24 $479.24 Paid 03/23/2022
Valuation Fee New Single Family $1,160.55 $1,160.55 Paid 03/23/2022
8331506-EFHB Maybrook, Full $511.32 $511.32 Paid 03/23/2022
Not Ready Inspection Fee $50.00 $50.00 Paid 12/16/2022
Temporary Occupancy Fee $50.00 $50.00 Paid 12/19/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 5/19/2022 05/19/2022
Erosion Control Inspection Residential Failed 6/21/2022 06/21/2022
Miscellaneous Correction
Resolved
06/21/2022
4-26-22 the truck that dropped off rock to the property spilled it all over the road. Needs to be cleaned up immediately
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
06/21/2022
DEFICIENT EROSION CONTROL INSTALLATION. RESTORE EROSION CONTROL ALONG THE STREET NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Underslab Plumbing Inspection - Residential Not Ready 6/21/2022 6/21/2022 06/21/2022
Misc
Corrective Action Required
06/21/2022
NOTHING HAS BEEN DONE. THE WATER IN THE BASEMENT IS STILL BEING PUMPED OUT. **6/21-NOT-READY FEE ASSESSED
Underslab Plumbing Inspection - Residential Passed 7/6/2022 7/6/2022 07/06/2022
Misc
Resolved
07/06/2022
**6/21-NOT-READY FEE ASSESSED
Erosion Control Inspection Residential Failed 7/6/2022 07/06/2022
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
07/06/2022
DEFICIENT EROSION CONTROL INSTALLATION. RESTORE THE EROSION CONTROL ALONG THE STREET NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
All Rough Inspection - Residential Failed 8/17/2022 8/17/2022 08/17/2022
Misc
Corrective Action Required
08/17/2022
INSPECTION DENIED - NO CITY STAMPED PLANS - COMPLETE MEP'S - INSTALL WINDOWS AND DOORS - FIRE BLOCK THROUGHOUT PFH NAIL PATTERN TO SHEETING OK
All Rough Inspection - Residential Failed 9/9/2022 9/9/2022 09/09/2022
Misc
Corrective Action Required
08/17/2022
-Nail siding to sill plate per code -Provide security blocking for garage exterior door -Provide 7-studs supports for garage I beam -Provide 6-stud support for I beam at mud wall corner -Complete electrical to microwave and oven -Fb pantry wall -Nail hangers above rear dining area -Brace ends of lvl roof beam from rotation -Complete installing fireplace, gas, etc -Fb gap along the top of north-south wall; Fb floor penetration and gap at top of fireplace space -Provide security blocking at master bedroom exterior door -Complete electrical at master bathroom sink -Fb foyer and garage wall from roof -Pan off return air space from front bathroom tub -Install stud support underneath roof support strut at front bedroom/bathroom wall -Brace interior walls per plan -Over notched joist under master bathroom -Bond gas piping **OK TO INSULATE
Electrical Service Inspection Failed 9/9/2022 9/9/2022 09/09/2022
Misc
Corrective Action Required
09/09/2022
-Complete service installation
Gas Service Inspection - Residential Passed 9/9/2022 9/9/2022 09/09/2022
Piers/Caissons Inspection - Residential Passed 9/20/2022 09/20/2022
All Rough Inspection - Residential Failed 10/4/2022 10/4/2022 10/04/2022
Misc
Corrective Action Required
09/09/2022
-Nail siding to sill plate per code **siding at front exterior garage walls at both sides of garage -Complete installing fireplace, gas, etc **complete gas line connection to fireplace; install bushing at electrical wiring entrance into fireplace -Pan off return air space from front bathroom tub **not done at return air stud space between front bedroom and bathroom -Brace interior walls per plan. Brace wall by gypsum method fastener schedule will be inspected later after approval for rock
Electrical Service Inspection Passed 10/4/2022 10/4/2022 10/04/2022
Misc
Resolved
10/04/2022
-Complete service installation
All Rough Inspection - Residential Partial 10/7/2022 10/7/2022 10/07/2022
Misc
Corrective Action Required
10/04/2022
-Complete installing fireplace, gas, etc **complete gas line connection to fireplace; install bushing at electrical wiring entrance into fireplace -Brace interior walls per plan. Brace wall by gypsum method fastener schedule will be inspected later after approval for rock **OK TO ROCK
All Rough Inspection - Residential Passed 10/17/2022 10/17/2022 10/17/2022
Misc
Resolved
10/17/2022
-Complete installing fireplace, gas, etc **complete gas line connection to fireplace; install bushing at electrical wiring entrance into fireplace -Brace interior walls per plan. Brace wall by gypsum method fastener schedule will be inspected later after approval for rock **OK TO ROCK
Sewer Service Inspection - R Passed 10/26/2022 (1:00) 10/26/2022 10/26/2022
Water Service Inspection - R Passed 10/27/2022 (11:00) 10/27/2022 10/27/2022
Driveway Inspection Partial 11/21/2022
Misc
Informational
11/21/2022
11-21-22 AN forms are in place aggregate is present and compacted compacted
Driveway Inspection Failed 11/22/2022 11/22/2022 11/28/2022
Misc
Informational
11/21/2022
11-21-22 AN forms are in place aggregate is present and compacted compacted 11-28-22 AN. Driveway looks good but the whole curb needs to be replaced in front of the driveway.
Driveway Inspection Partial 11/30/2022 11/30/2022 12/06/2022
Misc
Informational
11/28/2022
11-21-22 AN forms are in place aggregate is present and compacted compacted 11-28-22 AN. Driveway looks good but the whole curb needs to be replaced in front of the driveway. 12-6-22 AN crew is replacing the curb
Occupancy Inspection - Codes Residential Ready for Temp CO 12/16/2022 12/16/2022 12/16/2022
Misc
Corrective Action Required
12/16/2022
-Driveway not approved on record -Final grade, sod, downspout and sump pump extension -Install tamper-proof caps at AC valves -Provide receptacle at fireplace cabinet wall space. FYI: receptacle located inside the cabinet does not meet the requirement
Driveway Inspection Passed 12/7/2022 4/5/2023 04/05/2023
Misc
Informational
12/06/2022
11-21-22 AN forms are in place aggregate is present and compacted compacted 11-28-22 AN. Driveway looks good but the whole curb needs to be replaced in front of the driveway. 12-6-22 AN crew is replacing the curb 4-5-2023 NS. Site visited driveway appears to pass city standards.
Erosion Control Inspection Residential Passed 04/26/2023
DCM2 ESC DEFICIENT INSTALLATION
Resolved
04/26/2023
DEFICIENT EROSION CONTROL INSTALLATION. RESTORE THE EROSION CONTROL ALONG THE STREET NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED.
Occupancy Inspection - Codes Residential Failed 4/26/2023 4/26/2023 04/26/2023
Misc
Corrective Action Required
04/26/2023
-Install tamper-proof caps at AC valves -Provide receptacle at fireplace cabinet wall space. FYI: receptacle located inside the cabinet does not meet the requirement
Occupancy Inspection - Codes Residential Failed 5/30/2023 5/30/2023 05/30/2023
Misc
Corrective Action Required
05/30/2023
-Install tamper-proof caps at AC valves -Provide receptacle at fireplace cabinet wall space. FYI: receptacle located inside the cabinet does not meet the requirement
Occupancy Inspection - Codes Residential Full C of O 06/09/2023
Misc
Resolved
06/09/2023
-Install tamper-proof caps at AC valves -Provide receptacle at fireplace cabinet wall space. FYI: receptacle located inside the cabinet does not meet the requirement
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your permit