Summary
PRRES20220601
Building Permit - Residential
Certificate of Occupancy
KEVIN HIGDON CONSTRUCTION LLC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED/UNFINISHED BASEMENT - COVERED PATIO TILE ROOF
02/16/2022
03/25/2022
09/18/2022
09/01/2023
Locations
Contacts
KEVIN HIGDON CONSTRUCTION, LLC, Address:P O BOX 847, Phone:(816) 524-9797  
KEVIN HIGDON CONSTRUCTION LLC, Address:PO BOX 847, Phone:(816) 524-9797  
kevin higdon, Address:po box 847  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
INTERSTATE CONSTRUCTION SERVICES, Address:1450 SE BROADWAY DR, Phone:(816) 524-9797  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
DOUG@HIGDONBUILDERS.COM  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Valuation Fee New Single Family $917.92 $917.92 Paid 03/25/2022
Right of Way Permit Fee $85.00 $85.00 Paid 03/25/2022
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 03/25/2022
8331506-EFHB Maybrook, Full $596.54 $596.54 Paid 03/25/2022
8331507-Sewer Connection Fee $420.00 $420.00 Paid 03/25/2022
Water Tap Fee $3,655.00 $3,655.00 Paid 03/25/2022
Water Meter Fee $479.24 $479.24 Paid 03/25/2022
Valuation Fee New Single Family $250.56 $250.56 Paid 09/01/2023
$1,168.48
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Failed 5/19/2022 (1:00) 5/19/2022 05/19/2022
Misc
Corrective Action Required
05/19/2022
5-19-22 -No footing at this site at this time
Underslab Plumbing Inspection - Residential Passed 10/27/2022 10/27/2022 10/27/2022
Sewer Service Inspection - R Partial 2/28/2023 (3:00) 2/28/2023 02/28/2023
Misc
Corrective Action Required
02/28/2023
Partial sewer about 40 ft from house
Footing Inspection - Residential Passed 3/13/2023 03/13/2023
Misc
Informational
03/13/2023
FOOTING APPROVED BY ENGINEER
Electrical Service Inspection Passed 3/13/2023 3/13/2023 03/13/2023
Gas Service Inspection - Residential Failed 3/13/2023 3/13/2023 03/13/2023
Misc
Corrective Action Required
03/13/2023
-Pressure gauge cannot be more than 30 psi range
All Rough Inspection - Residential Failed 3/13/2023 3/13/2023 03/13/2023
Misc
Corrective Action Required
03/13/2023
**PROVIDE EROSION CONTROL ALONG THE STREET -Shim gap between garage studs and sill plates -Strap top plates lapped less than 24" near garage I beam -Tie rafters to wall top plates or have engineer address. Plan calls for Simpson H2.5A or equivalent every 48” -Support bottom of rafter at pantry -Install rear exterior door and provide security blockings -Nail rear dining CSPF walls sheathing and strap header per code -Complete electrical to rear dining receptacle and all lighting above kitchen -Secure gas csst line per code inside fireplace space -Patch floor near great room/laundry wall -Replace spliced rafters between wall and purlin or have engineer address spliced rafters above master bedroom -Strap wall top plates bored more than 50% -Brace interior walls per plan -Lighting above foyer not installed -Provide reachable 2-way switch for stair light; provide stair lighting per code -Shim gap between (2)2x10 and bearing wall at stair -Install joist hangers around stair in basement -Screw and tape duct joints above basement rec room -Steel column at opening to mechanical space **OK TO INSULATE
Sewer Service Inspection - R Passed 3/15/2023 (10:15) 3/15/2023 03/15/2023
Misc
Resolved
03/15/2023
Partial sewer about 40 ft from house
Water Service Inspection - R Passed 3/16/2023 03/16/2023
All Rough Inspection - Residential Failed 3/27/2023 3/27/2023 03/27/2023
Misc
Corrective Action Required
03/13/2023
**PROVIDE EROSION CONTROL ALONG THE STREET -Shim gap between garage studs and sill plates -Strap top plates lapped less than 24" near garage I beam -Tie rafters to wall top plates or have engineer address. Plan calls for Simpson H2.5A or equivalent every 48” -Support bottom of rafter at pantry -Install rear exterior door and provide security blockings **Shim gap at strike plate side and at each hinge -Nail rear dining CSPF walls sheathing and strap header per code -Complete electrical to rear dining receptacle and all lighting above kitchen -Secure gas csst line per code inside fireplace space -Patch floor near great room/laundry wall -Replace spliced rafters between wall and purlin or have engineer address spliced rafters above master bedroom -Strap wall top plates bored more than 50% -Brace interior walls per plan -Lighting above foyer not installed -Provide reachable 2-way switch for stair light; provide stair lighting per code -Shim gap between (2)2x10 and bearing wall at stair -Screw and tape duct joints above basement rec room -Install I beam support steel column at opening to mechanical space **OK TO INSULATE
All Rough Inspection - Residential Failed 3/31/2023 3/31/2023 03/31/2023
Misc
Corrective Action Required
03/27/2023
**PROVIDE EROSION CONTROL ALONG THE STREET -Shim gap between garage studs and sill plates -Strap top plates lapped less than 24" near garage I beam -Tie rafters to wall top plates or have engineer address. Plan calls for Simpson H2.5A or equivalent every 48” -Support bottom of rafter at pantry -Install rear exterior door and provide security blockings **Shim gap at strike plate side and at each hinge -Nail rear dining CSPF walls sheathing and strap header per code -Complete electrical to rear dining receptacle and all lighting above kitchen -Secure gas csst line per code inside fireplace space -Patch floor near great room/laundry wall -Strap wall top plates bored more than 50% -Brace interior walls per plan -Lighting above foyer not installed -Provide reachable 2-way switch for stair light; provide stair lighting per code -Shim gap between (2)2x10 and bearing wall at stair -Screw and tape duct joints above basement rec room -Install I beam support steel column at opening to mechanical space **OK TO INSULATE
Gas Service Inspection - Residential Failed 3/31/2023 3/31/2023 03/31/2023
Misc
Corrective Action Required
03/13/2023
-Pressure gauge cannot be more than 30 psi range
Piers/Caissons Inspection - Residential Passed 4/3/2023 (11:00) 4/3/2023 04/03/2023
All Rough Inspection - Residential Failed 4/18/2023 4/18/2023 04/18/2023
Misc
Corrective Action Required
03/31/2023
-Install rear exterior door and provide security blockings **Shim gap at strike plate side and at each hinge -Nail rear dining CSPF walls sheathing per code -Secure gas csst line per code inside fireplace space -Strap wall top plates bored more than 50%
Sidewalk Inspection Partial 6/5/2023 6/5/2023 06/05/2023
Misc
Informational
06/05/2023
6-5-23 NS Site visited for a driveway and sidewalk inspection and it appears that the driveway and sidewalk meet city standards. Will need to come back and check the ADA.
Driveway Inspection Passed 6/26/2023 8/3/2023 08/03/2023
Misc
Informational
06/05/2023
4-25-23 NS site visited and driveway still has not been formed I am going to schedule this out to July. 6-5-23 NS Site visited for a driveway and sidewalk inspection and it appears that the driveway and sidewalk meet city standards. Will need to come back and check the ADA. 8-3-23 NS Site visited and it appears that driveway and sidewalk meets city standards ADA passed.
All Rough Inspection - Residential Failed 8/25/2023 8/25/2023 08/25/2023
Misc
Corrective Action Required
04/18/2023
-Nail rear dining CSPF walls sheathing per code **OK TO ROCK NOW
Gas Service Inspection - Residential Passed 8/25/2023 8/25/2023 08/25/2023
Misc
Resolved
08/25/2023
-Pressure gauge cannot be more than 30 psi range
All Rough Inspection - Residential Passed 9/1/2023 9/1/2023 09/01/2023
Misc
Resolved
09/01/2023
-Nail rear dining CSPF walls sheathing per code **OK TO ROCK NOW
Occupancy Inspection - Codes Residential Failed 9/1/2023 9/1/2023 09/01/2023
Corrective Action Required
09/01/2023
-Front and master bathrooms GFC'sI are not installed -Sump pump needs to state it is non GFCI protected
Erosion Control Inspection Residential Passed 9/1/2023 09/01/2023
Plot Plan Inspection Passed 9/1/2023 09/01/2023
Sidewalk Inspection Passed 09/01/2023
Misc
Informational
06/05/2023
6-5-23 NS Site visited for a driveway and sidewalk inspection and it appears that the driveway and sidewalk meet city standards. Will need to come back and check the ADA. 9-1-23 A.A SW has been poured. Cross and running slopes are in compliance. Forms are pulled. Passed
Driveway Inspection Passed 4/25/2023 09/01/2023
Misc
Informational
04/25/2023
4-25-23 NS site visited and driveway still has not been formed I am going to schedule this out to July. 9-1-23 A.A Driveway is poured. Forms are pulled. Cross and running slopes are in compliance. Passed
Driveway Inspection Passed 6/5/2023 6/5/2023 09/01/2023
Misc
Informational
04/25/2023
4-25-23 NS site visited and driveway still has not been formed I am going to schedule this out to July. 6-5-23 NS Site visited for a driveway and sidewalk inspection and it appears that the driveway and sidewalk meet city standards. Will need to come back and check the ADA.
Occupancy Inspection - Codes Residential Full C of O 9/1/2023 09/01/2023
Misc
Resolved
09/01/2023
-Front and master bathrooms GFC'sI are not installed -Sump pump needs to state it is non GFCI protected
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents