Summary
PRRES20215211
Building Permit - Residential
Certificate of Occupancy
KEVIN HIDGON CONSTRUCTION LLC
NEW 3 OR 4 FAMILY
NEW FOUR PLEX - UNFINISHED BASEMENTS - UNCOVERED DECKS - TILE ROOF FINISHED BASEMENT 4021 NE SAGAMORE DR. Andrea Sessler 12/19/2023 11:03 AM
10/05/2021
10/15/2021
04/05/2022
09/12/2024
Locations
Contacts
KEVIN HIGDON CONSTRUCTION, LLC, Address:P O BOX 847, Phone:(816) 524-9797  
KEVIN HIDGON CONSTRUCTION LLC, Address:1450 SE BROADWAY DR  
kevin higdon, Address:po box 847  
KEVIN@HIGDONBUILDERS.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
INTERSTATE CONSTRUCTION SERVICES, Address:1450 SE BROADWAY DR, Phone:(816) 524-9797  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee for New 3 or 4 Family $4,720.03 $4,720.03 Paid 10/15/2021
8331507-Sewer Connection Fee $840.00 $840.00 Paid 10/15/2021
9110073-Right of Way Permit Fee $85.00 $85.00 Paid 10/15/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 10/15/2021
8331401-Water Tap Fee $14,620.00 $14,620.00 Paid 10/15/2021
8350015-Water Meter Fee $1,916.96 $1,916.96 Paid 10/15/2021
8331506-EFHB Maybrook, Full $1,193.08 $1,193.08 Paid 10/15/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 05/16/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 05/16/2024
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 05/16/2024
9110078-Valuation Fee for New 3 or 4 Family $60.60 $60.60 Paid 01/05/2024
$5,580.72
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 05/16/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 05/16/2024
9110078-Temporary Occupancy Fee $50.00 $50.00 Paid 08/27/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Not Ready 12/20/2021 (8:15) 12/20/2021 12/20/2021
Misc
Corrective Action Required
12/20/2021
EROSION CONTROL IS NOT IN COMPLIANCE
Erosion Control Inspection Residential Failed 3/4/2022 03/04/2022
DCM5 ESC INSP DENIED
Corrective Action Required
03/04/2022
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. **PROVIDE EROSION CONTROL ALONG THE STREET. BOTTOM OF THE SILT FENCE SHALL BE BURIED MIN 6" BELOW SOIL
Underslab Plumbing Inspection - Residential Failed 3/4/2022 3/4/2022 03/04/2022
Misc
Corrective Action Required
03/04/2022
-INSPECTION DENIED DUE TO EROSION CONTROL NON-COMPLIANCE -SUBMIT 3RD PARTY APPROVAL FOR THE FOOTING
Sewer Service Inspection - R Failed 3/21/2022 (1:45) 3/21/2022 03/21/2022
Misc
Corrective Action Required
03/21/2022
**DO NOT COVER SEWER OUTSIDE UNIT 4021 AND 4023. CURRENTLY, SEWER FROM 4021 IS CONNECTED TO THE SAME SEWER STUB OF 4023. CONTACT WATER DEPARTMENT/FIELD SERVICE ENGINEER REGARDING MISSING SEWER STUB FOR UNIT 4021
Water Service Inspection - R Passed 3/25/2022 (1:00) 3/25/2022 03/25/2022
Sewer Service Inspection - R Passed 3/28/2022 03/29/2022
Misc
Resolved
03/28/2022
**DO NOT COVER SEWER OUTSIDE UNIT 4021 AND 4023. CURRENTLY, SEWER FROM 4021 IS CONNECTED TO THE SAME SEWER STUB OF 4023. CONTACT WATER DEPARTMENT/FIELD SERVICE ENGINEER REGARDING MISSING SEWER STUB FOR UNIT 4021
Misc
Informational
03/29/2022
3-29-22 AN contractor installed a new wye and stub on the sewer main because the lot originally was a 3 plex and they changed it to a 4 plex
Underslab Plumbing Inspection - Residential Passed 4/7/2022 4/7/2022 04/07/2022
Misc
Resolved
04/07/2022
-SUBMIT 3RD PARTY APPROVAL FOR THE FOOTING
Underslab Electrical Inspection - Residential Passed 4/7/2022 4/7/2022 04/07/2022
All Rough Inspection - Residential Failed 4/6/2023 4/6/2023 04/06/2023
Misc
Corrective Action Required
08/25/2022
Garage portal wall inspection only: -Nail sheathing to double studs @3” oc -Nail sheathing to LVL with 3” grid pattern
All Rough Inspection - Residential Failed 5/23/2023 5/23/2023 05/23/2023
Misc
Corrective Action Required
04/06/2023
Garage portal wall inspection only: -Nail sheathing to double studs @3” oc -Nail sheathing to LVL with 3” grid pattern -Nail to sill plate @ 3” oc
Rated Assembly Inspection Partial 5/23/2023 5/23/2023 05/23/2023
Misc
Informational
05/23/2023
Attic 2-hr firewall-1st layer ok
Rated Assembly Inspection Partial 5/30/2023 5/30/2023 05/30/2023
Misc
Informational
05/23/2023
Attic 2-hr firewall-2nd layer ok **provide fire protection under roof decking
Erosion Control Inspection Residential Failed 8/3/2023 08/03/2023
DCM5 ESC INSP DENIED
Corrective Action Required
03/04/2022
REQUESTED INSPECTION(S) DENIED DUE TO DEFICIENT EROSION CONTROL INSTALLATION. **PROVIDE EROSION CONTROL ALONG THE STREET. BOTTOM OF THE SILT FENCE SHALL BE BURIED MIN 6" BELOW SOIL **CLEAN STORM INLET
Rated Assembly Inspection Failed 8/3/2023 8/3/2023 08/03/2023
Misc
Informational
05/30/2023
Attic 2-hr firewall-2nd layer ok **provide fire protection under roof decking
MISC
Corrective Action Required
08/03/2023
- NO ACCESS - NO ANSWER TO CALL WAS ABLE TO GET IN 4033 BUT NO PLANS ON SIGHT.
All Rough Inspection - Residential Failed 8/3/2023 8/3/2023 08/03/2023
Misc
Corrective Action Required
05/23/2023
Garage portal wall inspection only: -Nail sheathing to double studs @3” oc -Nail sheathing to LVL with 3” grid pattern -Nail to sill plate @ 3” oc
Misc
Corrective Action Required
08/03/2023
- NO ACCESS - NO ANSWER TO CALL WAS ABLE TO GET IN 4033 BUT NO PLANS ON SIGHT.
Electrical Service Inspection Failed 8/3/2023 8/3/2023 08/03/2023
Misc
Corrective Action Required
08/03/2023
- NO ACCESS - NO ANSWER TO CALL WAS ABLE TO GET IN 4033 BUT NO PLANS ON SIGHT.
Electrical Service Inspection Failed 8/9/2023 8/9/2023 08/09/2023
Misc
Resolved
08/09/2023
Misc
Corrective Action Required
08/09/2023
-4027 Electrical- ground to gas line not complete, could not locate ufer -4025 Electrical not ready -4023 Electrical not ready -4021 Electrical not ready
Gas Service Inspection - Residential Failed 8/9/2023 8/9/2023 08/09/2023
Misc
Corrective Action Required
08/09/2023
-4027 Gas gauge faulty, unable to test -4025 Gas gauge faulty, unable to test -4023 Gas gauge faulty, unable to test -4021 Gas pressure gauge reads zero
All Rough Inspection - Residential Failed 8/9/2023 8/9/2023 08/09/2023
Misc
Partial Correction
08/09/2023
Garage portal wall inspection only: -Nail sheathing to LVL with 3” grid pattern
Misc
Resolved
08/09/2023
Misc
Corrective Action Required
08/09/2023
4021,4023,4025,4027 NE Sagamore -4727 address 3 inch nail pattern at right side garage LVL -4027 wall change not per plans between laundry and master closet resubmit plans with new changes -4027 reattach vent at top in laundry -4027 missing framing at fireplace top -4027 address missing fire blocking at master bathroom vanity wall top plate between rated assembly's -4027 missing nails at outside corner 2x4's -4027 missing nuts at basement sill plate -4027 missing nails at bottom of sheathing exterior -4027 missing bolts at post in basement -4027 Electrical- ground to gas line not complete, could not locate ufer -4027 Gas, faulty gauge unable to test -4025 Missing framing around furnace exhaust flue 1st and 2nd floor -4025 Missing stud in laundry next to ductwork -4025 secure gas line at fireplace -4025 missing fire blocking second story middle of the wall above the stairs -4025 missing fire blocking at bedroom 2 closet top plate -4025 missing bolts at post in basement -4025 Electrical not ready -4025 Gas, faulty gauge unable to test -4023 Missing framing around furnace exhaust glue 1st and 2nd floor -4023 secure gas line at fireplace -4023 missing fire blocking between rated assembly's at top plate between unit 4023 and 4021 -4023 missing bolts at post in basement -4021 secure duct in master bathroom left of vanities -4021 wall change not per plans between master closet and laundry resubmit plans with new changes -4021 east and south wall basement over-notched 2x6 at base plate -4021 Electrical not ready -4021 missing bolts at posts in basement -4021 gas line pressure at zero
Rated Assembly Inspection Passed 8/9/2023 8/9/2023 08/09/2023
Misc
Informational
08/03/2023
Attic 2-hr firewall-2nd layer ok **provide fire protection under roof decking
MISC
Resolved
08/09/2023
All Rough Inspection - Residential Failed 8/17/2023 8/17/2023 08/17/2023
Misc
Resolved
08/17/2023
Misc
Partial Correction
08/17/2023
-4027 wall change not per plans between laundry and master closet resubmit plans with new changes -4027 address daylight visible from the interior at the sill plate next to sheathing SE basement wall -4027 missing nuts at basement sill plate -4027 Electrical- ground to gas line not complete, could not locate ufer -4025 Missing stud in laundry next to ductwork -4025 secure gas line at fireplace -4025 missing fire blocking at bedroom 2 closet top plate hole for electrical -4025 Ufer not grounded to panel -4025 Gas, faulty gauge unable to test -4023 secure gas line at fireplace -4023 missing fire blocking between rated assembly's at top plate between unit 4023 and 4021 -4023 No pressure at gas gauge unable to test -4023 Could not locate ufer -4023 address daylight visible from the interior at the sill plate next to sheathing E side -4021 secure duct in master bathroom left of vanities -4021 wall change not per plans between master closet and laundry resubmit plans with new changes -4021 Electrical not grounded
All Rough Inspection - Residential Failed 10/17/2023 10/17/2023 10/17/2023
Misc
Partial Correction
08/17/2023
**10/17/23-NOT READY. ALLROUGH INSPECTION HAS NEVER BEEN APPROVED FOR SHEETROCK. THE WHOLE BUILDING IS ALREADY COVERED. -4027 wall change not per plans between laundry and master closet resubmit plans with new changes -4027 address daylight visible from the interior at the sill plate next to sheathing SE basement wall -4027 missing nuts at basement sill plate -4027 Electrical- ground to gas line not complete, could not locate ufer -4025 Missing stud in laundry next to ductwork -4025 secure gas line at fireplace -4025 missing fire blocking at bedroom 2 closet top plate hole for electrical -4025 Ufer not grounded to panel -4025 Gas, faulty gauge unable to test -4023 secure gas line at fireplace -4023 missing fire blocking between rated assembly's at top plate between unit 4023 and 4021 -4023 No pressure at gas gauge unable to test -4023 Could not locate ufer -4023 address daylight visible from the interior at the sill plate next to sheathing E side -4021 secure duct in master bathroom left of vanities -4021 wall change not per plans between master closet and laundry resubmit plans with new changes -4021 Electrical not grounded
All Rough Inspection - Residential Failed 10/18/2023 10/18/2023
Misc
Partial Correction
10/17/2023
4027: -Protect csst gas line at entry into fireplace -wall change not per plans between laundry and master closet resubmit plans with new changes -missing nuts at basement sill plate -Seal wall at SE basement wall sill plate 4025: -Missing stud in kitchen next to ductwork -Protect csst gas line at entry into fireplace 4023: -Protect csst gas line at entry into fireplace 4021: -Protect csst gas line at entry into fireplace -wall change not per plans between master closet and laundry resubmit plans with new changes -Seal wall at NE basement wall sill plate
Electrical Service Inspection Passed 10/18/2023 10/18/2023
Misc
Resolved
10/18/2023
Footing Inspection - Residential Passed 10/18/2023
Misc
Resolved
10/18/2023
EROSION CONTROL IS NOT IN COMPLIANCE
Rated Assembly Inspection Partial 10/18/2023 10/18/2023
Misc
Informational
08/03/2023
Attic 2-hr firewall-2nd layer ok Dwelling 2-hr firewall-1st layer OK
Rated Assembly Inspection Failed 10/25/2023 10/25/2023 10/25/2023
Misc
Informational
10/18/2023
Attic 2-hr firewall-2nd layer ok Dwelling 2-hr firewall-1st layer OK
Misc
Corrective Action Required
10/25/2023
Remove the concrete board from shower firewall at middle two units
Driveway Inspection Partial 10/31/2023 10/31/2023 10/31/2023
Misc
Informational
10/31/2023
10-31-23 NS Site visited and it appears that driveway and Sidewalk meet city standards for pre-pour.
Sidewalk Inspection Partial 10/31/2023 10/31/2023 10/31/2023
Misc
Informational
10/31/2023
10-31-23 NS Site visited and it appears that driveway and Sidewalk meet city standards for pre-pour.
Gas Service Inspection - Residential Failed 12/7/2023 12/7/2023 12/07/2023
Misc
Corrective Action Required
08/09/2023
No pressure on all the gauges, except 4021. Install working gauges and provide verification of min 12" burial depth of underground gas lines
Gas Service Inspection - Residential Not Ready 12/18/2023 12/18/2023 12/18/2023
Misc
Corrective Action Required
12/07/2023
No pressure on all the gauges, except 4021. Install working gauges and provide verification of min 12" burial depth of underground gas lines **12/18-Not ready fee assessed. Gas lines still not pressurized
Gas Service Inspection - Residential Not Ready 12/19/2023 12/19/2023 12/19/2023
Misc
Corrective Action Required
12/18/2023
No pressure on all the gauges, except 4021. Install working gauges and provide verification of min 12" burial depth of underground gas lines **12/18-Not ready fee assessed. Gas lines still not pressurized **12/19-Not ready fee assessed. Except for unit 4021, all other unit gas line pressure gauges are at zero pressure. Shall check for gas line leakage. Underground gas lines shall be verified for min 12" burial depth
Erosion Control Inspection Residential Failed 12/22/2023 12/22/2023 12/22/2023
DCM5 ESC INSP DENIED
Corrective Action Required
08/03/2023
**PROVIDE EROSION CONTROL ALONG THE STREET AND CREEK AT REAR OF LOT **CLEAN STORM INLET AT FRONT **NO FURTHER INSPECTION IF EROSION CONTROL IS NOT IN COMPLIANCE
Gas Service Inspection - Residential Passed 12/22/2023 12/22/2023
Misc
Resolved
12/22/2023
No pressure on all the gauges, except 4021. Install working gauges and provide verification of min 12" burial depth of underground gas lines **12/18-Not ready fee assessed. Gas lines still not pressurized **12/19-Not ready fee assessed. Except for unit 4021, all other unit gas line pressure gauges are at zero pressure. Shall check for gas line leakage. Underground gas lines shall be verified for min 12" burial depth
All Rough Inspection - Residential Failed 1/12/2024 1/12/2024 01/12/2024
Misc
Partial Correction
10/18/2023
4027: -Protect csst gas line at entry into fireplace -wall change not per plans between laundry and master closet resubmit plans with new changes -missing nuts at basement sill plate -Seal wall at SE basement wall sill plate 4025: -Missing stud in kitchen next to ductwork -Protect csst gas line at entry into fireplace 4023: -Protect csst gas line at entry into fireplace 4021: -wall change not per plans between master closet and laundry resubmit plans with new changes -Seal wall at NE basement wall sill plate **Basement finish-Underslab plumbing OK
All Rough Inspection - Residential Failed 1/25/2024 1/25/2024 01/25/2024
Misc
Partial Correction
01/12/2024
4027: -Protect csst gas line at entry into fireplace -wall change not per plans between laundry and master closet resubmit plans with new changes -missing nuts at basement sill plate -Seal wall at SE basement wall sill plate 4025: -Missing stud in kitchen next to ductwork -Protect csst gas line at entry into fireplace 4023: -Protect csst gas line at entry into fireplace 4021: -wall change not per plans between master closet and laundry resubmit plans with new changes -Seal wall at NE basement wall sill plate -Fb basement wall space from all soffits -Complete electrical. Also water line -Provide full support under 3x joist
All Rough Inspection - Residential Not Ready 1/30/2024 1/30/2024 01/30/2024
Misc
Partial Correction
01/25/2024
4027: -wall change not per plans between laundry and master closet resubmit plans with new changes -missing nuts at basement sill plate **anchor sill plate within 12” of basement walkout door. Min 2 anchors per plate 4025: -Missing stud in kitchen next to ductwork 4023-OK 4021: -wall change not per plans between master closet and laundry resubmit plans with new changes -Fb basement wall space from all soffits **not done -Provide full support under 3x joist **Fix the insulation please **REINSPECTION FEE ASSESSED FOR 3RD AND SUBSEQUENT FAILED INSPECTION
Rated Assembly Inspection Failed 1/30/2024 1/30/2024 01/30/2024
Misc
Informational
10/25/2023
Attic 2-hr firewall-2nd layer ok Dwelling 2-hr firewall-2nd layer OK, except at middle unit shower walls
Misc
Corrective Action Required
10/25/2023
Remove the concrete board from shower firewall at middle two units
All Rough Inspection - Residential Failed 2/2/2024 2/2/2024 02/02/2024
Misc
Partial Correction
01/30/2024
4027: -wall change not per plans between laundry and master closet resubmit plans with new changes -missing nuts at basement sill plate **anchor sill plate within 12” of basement walkout door. Min 2 anchors per plate 4025, 4023-OK to rock 4021-OK to rock -wall change not per plans between master closet and laundry resubmit plans with new changes
Driveway Inspection Partial 2/26/2024 02/26/2024
Misc
Informational
10/31/2023
10-31-23 NS Site visited and it appears that driveway and Sidewalk meet city standards for pre-pour.
Rated Assembly Inspection Passed 4/10/2024 4/10/2024 04/10/2024
Misc
Resolved
04/10/2024
Attic 2-hr firewall-2nd layer ok Dwelling 2-hr firewall-2nd layer OK
Misc
Resolved
04/10/2024
Remove the concrete board from shower firewall at middle two units
All Rough Inspection - Residential Failed 4/10/2024 4/10/2024 04/10/2024
Misc
Partial Correction
02/02/2024
4027: -missing nuts at basement sill plate **anchor sill plate within 12” of basement walkout door. Min 2 anchors per plate 4021 to 4024-OK to rock
Plot Plan Inspection Failed 4/23/2024 04/23/2024
Misc
Corrective Action Required
04/23/2024
Uncover the sewer manhole at NW corner of 4021
Occupancy Inspection - Codes Residential Failed 5/14/2024 5/14/2024 05/14/2024
Misc
Corrective Action Required
05/14/2024
4021 only inspected 4021 -address deck post to beam connection. Not to code.
Erosion Control Inspection Residential Passed 05/15/2024
DCM5 ESC INSP DENIED
Resolved
05/15/2024
**PROVIDE EROSION CONTROL ALONG THE STREET AND CREEK AT REAR OF LOT **CLEAN STORM INLET AT FRONT **NO FURTHER INSPECTION IF EROSION CONTROL IS NOT IN COMPLIANCE
All Rough Inspection - Residential Passed 5/15/2024 5/15/2024 05/15/2024
Misc
Resolved
05/15/2024
4027: -missing nuts at basement sill plate **anchor sill plate within 12” of basement walkout door. Min 2 anchors per plate 4021 to 4024-OK to rock
Occupancy Inspection - Codes Residential Failed 5/15/2024 5/15/2024 05/15/2024
Misc
Corrective Action Required
05/14/2024
-Bring sewer manhole at front NW lot corner to grade level -Sidewalk and driveway not approved on record Unit 4021: -Provide sewer tracer wire port at grade -Provide backflow preventer at garage hose bib -Install security strike plate for exterior doors -Provide tamper resistant receptacles in laundry, kitchen, and basement bathroom **Units 4023-4027 not yet inspected
Occupancy Inspection - Codes Residential Failed 5/16/2024 5/16/2024 05/16/2024
Misc
Corrective Action Required
05/15/2024
-Bring sewer manhole at front NW lot corner to grade level -Sidewalk and driveway not approved on record Unit 4021: Inside ok **Units 4023-4027 not yet inspected
Occupancy Inspection - Codes Residential Ready for Temp CO 05/16/2024
Misc
Corrective Action Required
05/16/2024
-Bring sewer manhole at front NW lot corner to grade level -Sidewalk and driveway not approved on record **Units 4023-4027 not yet inspected **TCO approved for unit 4021 only
Driveway Inspection Passed 05/20/2024
Misc
Informational
02/26/2024
10-31-23 NS Site visited and it appears that driveway and Sidewalk meet city standards for pre-pour.
Misc
Informational
05/20/2024
5-20-24 Dustin A, Dw's 4021-4027 have been poured and meet city specs
Sidewalk Inspection Passed 05/20/2024
Misc
Informational
10/31/2023
10-31-23 NS Site visited and it appears that driveway and Sidewalk meet city standards for pre-pour. 5-20-24 Dustin A, SW's have been poured to city specs and slopes are in compliance. Passed
Occupancy Inspection - Codes Residential Failed 8/20/2024 8/20/2024 08/20/2024
Misc
Corrective Action Required
05/16/2024
-Bring sewer manhole at front NW lot corner to grade level 825: -Provide sewer tracer wire port at grade -Paint gas service piping -Fix front and rear receptacle weatherproof covers -Provide box extension for all electrical boxes recessed more than 1/4” behind non-combustible wall finish -Install anti-tipping device for kitchen range -Fb openings below range **Units 4023 and 4027 not yet inspected **TCO approved for unit 4021 only
Occupancy Inspection - Codes Residential Ready for Temp CO 8/27/2024 8/27/2024 08/27/2024
Misc
Corrective Action Required
08/20/2024
-Bring sewer manhole at front NW lot corner to grade level 825: -Firecaulk firewall around I beam in basement **Units 4023 and 4027 not yet inspected **TCO approved for unit 4021 and 4025only
Plot Plan Inspection Passed 09/04/2024
Misc
Resolved
09/04/2024
Uncover the sewer manhole at NW corner of 4021
Occupancy Inspection - Codes Residential Failed 9/4/2024 9/4/2024 09/04/2024
Misc
Corrective Action Required
08/27/2024
-Bring sewer manhole at front NW lot corner to grade level 4023: -Obtain lawn irrigation permit and submit backflow valve test report to city -Provide sewer tracer wire port at grade -Install a weatherproof cover for deck receptacle -Provide box extension for all electrical boxes recessed more than 1/4” behind non-combustible wall finish -Fix receptacle ground fault condition in laundry -Provide gfci protection for sprinkler receptacle or install single plug receptacle 4025: -Obtain lawn irrigation permit and submit backflow valve test report to city -Firecaulk firewall around I beam in basement 4027: -Obtain lawn irrigation permit and submit backflow valve test report to city -Provide sewer tracer wire port at grade -Provide guardrail at open side of stoop more than 30” above grade, as measured 36” out from edge down to grade -Provide a wall receptacle at short wall adjacent to refrigerator -Provide box extension for all electrical boxes recessed more than 1/4” behind non-combustible wall finish -Reinforce north deck post -Smoke alarm must be min 10 ft from stove -Provide full bearing under triple joists in basement -Seal foundation crack under service panel -Where’s the gfci for the bathroom receptacles? **TCO approved for unit 4021 and 4025 only
Occupancy Inspection - Codes Residential Full C of O 9/12/2024 9/12/2024 09/12/2024
Misc
Resolved
09/12/2024
-Bring sewer manhole at front NW lot corner to grade level 4023: -Obtain lawn irrigation permit and submit backflow valve test report to city 4025: -Obtain lawn irrigation permit and submit backflow valve test report to city -Firecaulk firewall around I beam in basement 4027: -Obtain lawn irrigation permit and submit backflow valve test report to city **TCO approved for unit 4021 and 4025 only
Documents & Images
Date Uploaded File Type Document Name
10/05/2021 Lees Summit Residental Permit Application lot 15 chaperl ridge 4 unit
10/05/2021 exciseapplication 4021-4027 ne sagamore lot 15
10/07/2021 Permit Codes Residential Plan Review
10/15/2021 Plot Plan APPROVED PLOT PLAN
10/15/2021 Approved Plans approved plans
10/15/2021 Permit Codes Residential Plan Review
10/15/2021 Permit DS Building Permit
10/15/2021 Receipt Receipt for transaction:2021-008012
12/20/2021 Letter INSPECTION SUMMARY
03/04/2022 Letter INSPECTION SUMMARY
03/04/2022 Letter INSPECTION SUMMARY
03/21/2022 Letter INSPECTION SUMMARY
03/25/2022 Letter INSPECTION SUMMARY
03/28/2022 Letter INSPECTION SUMMARY
03/29/2022 Letter INSPECTION SUMMARY
04/07/2022 Letter INSPECTION SUMMARY
04/07/2022 Letter INSPECTION SUMMARY
04/21/2022 Approved Plans APPROVED PLANS
04/06/2023 Letter INSPECTION SUMMARY
05/23/2023 Letter INSPECTION SUMMARY
05/23/2023 Letter INSPECTION SUMMARY
05/30/2023 Letter INSPECTION SUMMARY
08/03/2023 Letter INSPECTION SUMMARY
08/03/2023 Letter INSPECTION SUMMARY
08/03/2023 Letter INSPECTION SUMMARY
08/03/2023 Letter INSPECTION SUMMARY
08/09/2023 Letter INSPECTION SUMMARY
08/09/2023 Letter INSPECTION SUMMARY
08/09/2023 Letter INSPECTION SUMMARY
08/09/2023 Letter INSPECTION SUMMARY
10/17/2023 Letter INSPECTION SUMMARY
10/18/2023 Letter INSPECTION SUMMARY
10/18/2023 Letter INSPECTION SUMMARY
10/18/2023 Letter INSPECTION SUMMARY
10/18/2023 Letter INSPECTION SUMMARY
10/18/2023 Letter INSPECTION SUMMARY
10/25/2023 Letter INSPECTION SUMMARY
10/31/2023 Letter INSPECTION SUMMARY
10/31/2023 Letter INSPECTION SUMMARY
12/07/2023 Letter INSPECTION SUMMARY
12/18/2023 Letter INSPECTION SUMMARY
12/19/2023 Letter INSPECTION SUMMARY
12/19/2023 Scope of Work SCOPE OF WORK
12/19/2023 Approved Plans APPROVED BASEMENT DRAWING
12/22/2023 Letter INSPECTION SUMMARY
12/22/2023 Letter INSPECTION SUMMARY
01/05/2024 Receipt Receipt for transaction:2024-000089
01/12/2024 Letter INSPECTION SUMMARY
01/25/2024 Letter INSPECTION SUMMARY
01/25/2024 TCR015 Townhome - Lee_s Summit, MO (Rev_ 3)
01/30/2024 Letter INSPECTION SUMMARY
01/30/2024 Letter INSPECTION SUMMARY
02/02/2024 Letter INSPECTION SUMMARY
03/11/2024 Engineer Report/Study ENGINEER REPORT
04/10/2024 Letter INSPECTION SUMMARY
04/10/2024 Letter INSPECTION SUMMARY
04/10/2024 Letter INSPECTION SUMMARY
04/22/2024 LOT 15 ASBUILT
04/22/2024 Plot Plan approved as graded plot plan
04/23/2024 Letter INSPECTION SUMMARY
05/14/2024 Letter INSPECTION SUMMARY
05/15/2024 Letter INSPECTION SUMMARY
05/15/2024 Letter INSPECTION SUMMARY
05/15/2024 Letter INSPECTION SUMMARY
05/16/2024 Letter INSPECTION SUMMARY
05/16/2024 Certificate/License Codes Temporary Certificate of Occupancy
05/16/2024 Receipt Receipt for transaction:2024-003569
05/20/2024 Letter INSPECTION SUMMARY
05/20/2024 Letter INSPECTION SUMMARY
08/20/2024 Letter INSPECTION SUMMARY
08/27/2024 Letter INSPECTION SUMMARY
08/27/2024 Certificate/License Codes Temporary Certificate of Occupancy
08/27/2024 Receipt Receipt for transaction:2024-007274
09/04/2024 Letter INSPECTION SUMMARY
09/04/2024 Letter INSPECTION SUMMARY
09/12/2024 Letter Field Certificate of Occupancy
09/12/2024 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home