Summary
PRRES20215174
Building Permit - Residential
Certificate of Occupancy
Classic Design Homes LLC
NEW SINGLE FAMILY
NEW HOUSE - FINISHED BASEMENT - COVERED DECK TILE ROOF
10/04/2021
11/09/2021
04/02/2022
10/11/2022
Locations
Contacts
Classic Design Homes LLC, Address:909 SE Scarlet Ct  
Classic Design Homes LLC, Address:909 SE Scarlet Ct  
Chad Butler, Address:909 SE Scarlet Ct, Phone:(816) 699-7727  
C.M. MOSE & SON, Address:6603 ROYAL ST BLDG E, Phone:(816) 781-4707  
Aesir Electric LLC, Address:27202 E 283RD ST, Phone:(816) 288-4309  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Right of Way Permit Fee $85.00 $85.00 Paid 11/09/2021
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 11/09/2021
8331506-EFHB Maybrook, Full $596.54 $596.54 Paid 11/09/2021
8331507-Sewer Connection Fee $420.00 $420.00 Paid 11/09/2021
Water Tap Fee $3,655.00 $3,655.00 Paid 11/09/2021
Water Meter Fee $479.24 $479.24 Paid 11/09/2021
Valuation Fee New Single Family $1,340.65 $1,340.65 Paid 11/09/2021
Not Ready Inspection Fee $50.00 $50.00 Paid 06/16/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 12/2/2021 (1:00) 12/2/2021 12/02/2021
Sewer Service Inspection - R Passed 1/3/2022 1/3/2022 01/03/2022
Water Service Inspection - R Partial 1/3/2022 1/3/2022 01/03/2022
Water Service Inspection - R Passed 1/4/2022 1/4/2022 01/04/2022
Underslab Plumbing Inspection - Residential Passed 1/19/2022 1/18/2022 01/18/2022
Suspended Slab Inspection Passed 1/18/2022 (1:00) 1/18/2022 01/18/2022
Informational
01/18/2022
GARAGE STRUCTURAL SLAB-OK
Electrical Service Inspection Failed 4/20/2022 4/20/2022 04/20/2022
Misc
Corrective Action Required
04/20/2022
-Connect the ufer GEC to the bus bar where the service grounded conductor is connected to. NEC 250.24(A). Or install a #4 CU jumper from the bus bar where the GEC is connected to, to the service grounded bus bar. NEC 250.24(A)(4)
All Rough Inspection - Residential Failed 4/20/2022 4/20/2022 04/20/2022
Misc
Corrective Action Required
04/20/2022
**REPAIR EROSION CONTROL ALONG THE PROPERTY LINE AND THE STREET. NO FURTHER INSPECTION IF NOT IN COMPLIANCE -Nail siding to sill plate @6” oc -Provide (2)11-7/8” lvl beam for deck and 3 stud support. Or submit engineer address -Provide receptacle at rear accessible from and reachable within 6.5 ft of grade; provide receptacle at front -Sister new stud to the over cut studs in garage and nail to stud and plate -Anchor garage PFH walls -Protect wiring at bottom wall plate near rear dining window -Tie together equipment grounding conductors inside boxes with listed device -Provide vertical Fb of basement stair wall/foundation wall per code -Provide 5 studs support under kitchen lvl point load in basement -Fb hole at top of basement bedroom wall space at deck beam support; provide vertical fire blocking at basement bedroom at ten ft or less interval; Fb wall from soffit at end -Provide min 8 nails on each side of the top plate cut out for the deck beam support -Holes in joists for electrical wiring shall be min 2” apart. Have engineer address this for joists along the east basement wall -Fb floor at tub trap -Install a new stud next to the damaged stud near furnace **OK TO INSULATE
Gas Service Inspection - Residential Passed 4/20/2022 04/20/2022
All Rough Inspection - Residential Failed 4/22/2022 4/22/2022 04/22/2022
Misc
Corrective Action Required
04/20/2022
**REPAIR EROSION CONTROL ALONG THE PROPERTY LINE AND THE STREET. NO FURTHER INSPECTION IF NOT IN COMPLIANCE **4/21-INSPECTION DENIED. PROVIDE EROSION CONTROL PER ABOVE AND VLEAN UP THE STREET -Nail siding to sill plate @6” oc -Provide (2)11-7/8” lvl beam for deck and 3 stud support. Or submit engineer address -Provide receptacle at rear accessible from and reachable within 6.5 ft of grade; provide receptacle at front -Sister new stud to the over cut studs in garage and nail to stud and plate -Anchor garage PFH walls -Protect wiring at bottom wall plate near rear dining window -Tie together equipment grounding conductors inside boxes with listed device -Provide vertical Fb of basement stair wall/foundation wall per code -Provide 5 studs support under kitchen lvl point load in basement -Fb hole at top of basement bedroom wall space at deck beam support; provide vertical fire blocking at basement bedroom at ten ft or less interval; Fb wall from soffit at end -Provide min 8 nails on each side of the top plate cut out for the deck beam support -Holes in joists for electrical wiring shall be min 2” apart. Have engineer address this for joists along the east basement wall -Fb floor at tub trap -Install a new stud next to the damaged stud near furnace **OK TO INSULATE
Driveway Inspection Not Ready 4/25/2022 04/25/2022
Miscellaneous Correction
Corrective Action Required
04/25/2022
4-25-22 AN Not ready. There is not 4in of rock and what is there is not compacted.
All Rough Inspection - Residential Failed 4/25/2022 4/26/2022 04/26/2022
Misc
Corrective Action Required
04/22/2022
**REPAIR EROSION CONTROL ALONG THE PROPERTY LINE AND THE STREET. NO FURTHER INSPECTION IF NOT IN COMPLIANCE **4/21-INSPECTION DENIED. PROVIDE EROSION CONTROL PER ABOVE AND VLEAN UP THE STREET **4/26-EROCION CONTROL NOT INSTALLED. DRIVEWAY AND STOOP CONCRETE JUST GOT POURED -Nail siding to sill plate @6” oc -Provide (2)11-7/8” lvl beam for deck and 3 stud support. Or submit engineer address -Provide receptacle at rear accessible from and reachable within 6.5 ft of grade; provide receptacle at front -Sister new stud to the over cut studs in garage and nail to stud and plate -Anchor garage PFH walls -Protect wiring at bottom wall plate near rear dining window -Tie together equipment grounding conductors inside boxes with listed device -Provide vertical Fb of basement stair wall/foundation wall per code -Provide 5 studs support under kitchen lvl point load in basement -Fb hole at top of basement bedroom wall space at deck beam support; provide vertical fire blocking at basement bedroom at ten ft or less interval; Fb wall from soffit at end -Provide min 8 nails on each side of the top plate cut out for the deck beam support -Holes in joists for electrical wiring shall be min 2” apart. Have engineer address this for joists along the east basement wall -Fb floor at tub trap -Install a new stud next to the damaged stud near furnace **OK TO INSULATE
All Rough Inspection - Residential Failed 4/27/2022 4/27/2022 04/27/2022
Misc
Corrective Action Required
04/26/2022
-Sister new stud to the over cut studs in garage and nail to stud and plate **not done -Anchor garage PFH walls **install 2”x2”x3/16” washers -Tie together equipment grounding conductors inside boxes with listed device **use listed crimp devices or wire nuts or any other listed devices -Provide vertical fire blocking at basement bedroom at ten ft or less interval **wall around the rear of bedroom; Fb wall from soffit at rear exterior wall end -Install a new stud next to the damaged stud near furnace
All Rough Inspection - Residential Passed 4/28/2022 4/28/2022 04/28/2022
Misc
Resolved
04/28/2022
Electrical Service Inspection Passed 4/29/2022 4/29/2022 04/29/2022
Misc
Resolved
04/29/2022
-Connect the ufer GEC to the bus bar where the service grounded conductor is connected to. NEC 250.24(A). Or install a #4 CU jumper from the bus bar where the GEC is connected to, to the service grounded bus bar. NEC 250.24(A)(4)
Driveway Inspection Passed 4/26/2022 4/26/2022 04/29/2022
Miscellaneous Correction
Corrective Action Required
04/25/2022
4-25-22 AN Not ready. There is not 4in of rock and what is there is not compacted.
Misc
Informational
04/29/2022
4-29-22 AN fixes made and driveway looks good and has expansion joints at curb and right of way
Plot Plan Inspection Failed 6/23/2022 06/23/2022
Misc
Corrective Action Required
06/23/2022
-Swale at the rear of the lot is not per plan
Occupancy Inspection - Codes Residential Failed 9/30/2022 9/30/2022 09/30/2022
Misc
Corrective Action Required
09/30/2022
-Secure AC whip within 12” of disconnect -Lag deck ledger board to rim joist staggered at 16”; provide min 2 lags at each end of ledger board -The fall protection devices for windows must comply with ASTM F2090 -Screw the exterior door embedded jamb brace into studs to through the 4 pre drilled holes -Receptacle within six ft of wet bar must be gfci-protected (open ground) -Provide AFCI protection for all outlets required per NEC 210.12. All outlets (definition: receptacle, light, utilization equipments, etc) shall be afci-protected unless located in following areas: outdoor, fire alarm outlet, underfloor space, unfinished basement, garage, bathroom, and attic. -Provide mean of clean out for furnace condensate pipe -Receptacles in unfinished basement must either be dedicated (equipment plugged into receptacles) and identified or they shall be gfci-protected -Provide breaker lock for out-of-sight water heater -Locate and make accessible the ufer grounding connection. Is the service grounded at all?
Plot Plan Inspection Passed 10/07/2022
Misc
Resolved
10/07/2022
-Swale at the rear of the lot is not per plan
Occupancy Inspection - Codes Residential Failed 10/7/2022 10/7/2022 10/07/2022
Misc
Corrective Action Required
09/30/2022
-Receptacle within six ft of wet bar must be gfci-protected (open ground) **the receptacle on the right side of the wet bar sink is not tripping -Provide AFCI protection for all outlets required per NEC 210.12. All outlets (definition: receptacle, light, utilization equipments, etc) shall be afci-protected unless located in following areas: outdoor, fire alarm outlet, underfloor space, unfinished basement, garage, bathroom, and attic. **Not done. Install afci breakers at slots 13, 10, 12, 14, 16, and 18 -Provide mean of clean out for furnace condensate pipe **not done. Condensate drain line shall be configured to permit the clearing of blockages without requiring the drain line to be cut. IRC M1411.3.3 -Receptacles in unfinished basement must either be dedicated (equipment plugged into receptacles) and identified or they shall be gfci-protected **how about the 4-plug receptacle below the alarm but only one equipment (alarm) -Provide breaker lock for out-of-sight water heater **The handle tie for the water heater breaker serves a critical safety purpose. Reinstall a listed handle tie and a proper breaker lock -Locate and make accessible the ufer grounding connection. Is the service grounded at all? **Ground the service to ufer rebar
Occupancy Inspection - Codes Residential Full C of O 10/11/2022 10/11/2022 10/11/2022
Misc
Resolved
10/11/2022
-Receptacle within six ft of wet bar must be gfci-protected (open ground) **the receptacle on the right side of the wet bar sink is not tripping -Provide AFCI protection for all outlets required per NEC 210.12. All outlets (definition: receptacle, light, utilization equipments, etc) shall be afci-protected unless located in following areas: outdoor, fire alarm outlet, underfloor space, unfinished basement, garage, bathroom, and attic. **Not done. Install afci breakers at slots 13, 10, 12, 14, 16, and 18 -Provide mean of clean out for furnace condensate pipe **not done. Condensate drain line shall be configured to permit the clearing of blockages without requiring the drain line to be cut. IRC M1411.3.3 -Receptacles in unfinished basement must either be dedicated (equipment plugged into receptacles) and identified or they shall be gfci-protected **how about the 4-plug receptacle below the alarm but only one equipment (alarm) -Provide breaker lock for out-of-sight water heater **The handle tie for the water heater breaker serves a critical safety purpose. Reinstall a listed handle tie and a proper breaker lock
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your permit