Summary
PRRES20215173
Building Permit - Residential
Certificate of Occupancy
Classic Design Homes LLC
NEW SINGLE FAMILY
NEW HOUSE. FINISHED WALKOUT BASEMENT. COVERED DECK. TILE ROOF.
10/04/2021
10/20/2021
04/03/2022
08/31/2022
Locations
Contacts
Classic Design Homes LLC, Address:909 SE Scarlet Ct  
Classic Design Homes LLC, Address:909 SE Scarlet Ct  
Chad Butler, Address:909 SE Scarlet Ct, Phone:(816) 699-7727  
C.M. MOSE & SON, Address:6603 ROYAL ST BLDG E, Phone:(816) 781-4707  
Aesir Electric LLC, Address:27202 E 283RD ST, Phone:(816) 288-4309  
CENTURY PLUMBING, Address:14001 CENTURY LN, Phone:(816) 765-6066  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
8331507-Sewer Connection Fee $420.00 $420.00 Paid 10/20/2021
Water Tap Fee $3,655.00 $3,655.00 Paid 10/20/2021
Water Meter Fee $479.24 $479.24 Paid 10/20/2021
Right of Way Permit Fee $85.00 $85.00 Paid 10/20/2021
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 10/20/2021
Valuation Fee New Single Family $955.21 $955.21 Paid 10/20/2021
8331506-EFHB Maybrook, Full $596.54 $596.54 Paid 10/20/2021
Not Ready Inspection Fee $50.00 $50.00 Paid 08/24/2022
Temporary Occupancy Fee $50.00 $50.00 Paid 08/31/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 12/1/2021 12/01/2021
Erosion Control Inspection Residential Failed 12/1/2021 12/1/2021 12/01/2021
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
12/01/2021
EROSION CONTROL REQUIRED ALONG THE STREET. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Water Service Inspection - R Partial 12/30/2021 12/30/2021
Sewer Service Inspection - R Passed 12/30/2021 12/30/2021
Water Service Inspection - R Partial 1/3/2022 (1:30) 1/3/2022 01/03/2022
Water Service Inspection - R Passed 1/4/2022 (1:30) 1/4/2022 01/04/2022
Underslab Plumbing Inspection - Residential Passed 1/18/2022 1/18/2022 01/18/2022
Suspended Slab Inspection Passed 1/18/2022 (1:00) 1/18/2022 01/18/2022
Informational
01/18/2022
GARAGE STRUCTURAL SLAB-OK
All Rough Inspection - Residential Failed 4/15/2022 4/15/2022 04/15/2022
Misc
Corrective Action Required
04/15/2022
**PROVIDE EROSION CONTROL ALONG THE STREET -Nail siding to sill plate @6” oc -Provide (2)11-7/8” lvl beam for deck. -Install trim and flashing above windows -Provide a receptacle within 25 ft of AC unit; one receptacle at front -Protect wiring at bottom wall plate near deck door -Nail all required hanger holes above front bedroom -Nail rafters to ceiling joists -Provide (3)2x4 support for lvl roof beam behind fireplace -Provide vertical Fb of basement stair wall/foundation wall per code -Secure wiring within 8” of stair wall receptacle box -Support kitchen island drain every 4 ft or less -At basement slider wall, anchor sill plate within 12” of end. Anchors must be within middle 1/3 -Provide vapor barrier at slide door wall -Provide BOCA plate at top plate for kitchen island drain -Install another stud next to the over bored stud at electrical service panel -Holes in joists for electrical wiring shall be min 2” apart. Have engineer address this for joists along the east basement wall -Fb floor at tub trap -Secure wiring within 12” of box outside basement bedroom -Strap across cut top plates in rear basement bedroom -Fb basement wall from soffit **DO NOT INSULATE
Electrical Service Inspection Failed 4/15/2022 4/15/2022 04/15/2022
Misc
Corrective Action Required
04/15/2022
-Must provide space behind service panel for R-13 insulation -Provide insulating bushings at SE cable connections to panel and meter -Cut out excessive bare conductor inside meter box
Gas Service Inspection - Residential Passed 4/15/2022 04/15/2022
All Rough Inspection - Residential Failed 4/19/2022 4/19/2022 04/19/2022
Misc
Corrective Action Required
04/15/2022
**PROVIDE EROSION CONTROL ALONG THE STREET -Nail siding to sill plate @6” oc -Provide (2)11-7/8” lvl beam for deck. -Nail all required hanger holes above front bedroom -Nail rafters to ceiling joists -Provide vapor barrier at slide door wall -Install another stud next to the over bored stud at electrical service panel -Holes in joists for electrical wiring shall be min 2” apart. Have engineer address this for joists along the east basement wall -Fb basement wall from soffit **OK TO INSULATE
Electrical Service Inspection Passed 4/19/2022 4/19/2022 04/19/2022
Misc
Resolved
04/19/2022
-Must provide space behind service panel for R-13 insulation -Provide insulating bushings at SE cable connections to panel and meter -Cut out excessive bare conductor inside meter box
All Rough Inspection - Residential Failed 4/19/2022 04/19/2022
Misc
Corrective Action Required
04/19/2022
**PROVIDE EROSION CONTROL ALONG THE STREET -Provide (2)11-7/8” lvl beam for deck. -Holes in joists for electrical wiring shall be min 2” apart. Have engineer address this for joists along the east basement wall -Support bottom of the triple rafter at front bedroom
Driveway Inspection Not Ready 4/25/2022 04/25/2022
Miscellaneous Correction
Corrective Action Required
04/25/2022
4-25-22 AN Not ready. There is not 4in for rock and what is there is not compacted.
All Rough Inspection - Residential Failed 4/25/2022 4/26/2022 04/26/2022
Misc
Corrective Action Required
04/19/2022
**PROVIDE EROSION CONTROL ALONG THE STREET **4/26-EROCION CONTROL NOT INSTALLED. DRIVEWAY AND STOOP CONCRETE JUST GOT POURED -Provide (2)11-7/8” lvl beam for deck. -Holes in joists for electrical wiring shall be min 2” apart. Have engineer address this for joists along the east basement wall -Support bottom of the triple rafter at front bedroom
All Rough Inspection - Residential Passed 4/27/2022 4/27/2022 04/27/2022
Misc
Resolved
04/27/2022
-Provide (2)11-7/8” lvl beam for deck.
Driveway Inspection Passed 4/26/2022 4/26/2022 04/29/2022
Miscellaneous Correction
Corrective Action Required
04/25/2022
4-25-22 AN Not ready. There is not 4in for rock and what is there is not compacted.
Misc
Informational
04/29/2022
4-29-22 AN fixes were made and driveway looks good and has expansion joints at curb and right of way.
Plot Plan Inspection Passed 6/7/2022 06/07/2022
Erosion Control Inspection Residential Passed 08/24/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Resolved
08/24/2022
EROSION CONTROL REQUIRED ALONG THE STREET. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Occupancy Inspection - Codes Residential Failed 8/24/2022 8/24/2022 08/24/2022
Misc
Corrective Action Required
08/24/2022
-Not ready fee assessed on 4/25/22 has not been paid -Obtain lawn irrigation permit and submit backflow valve test report to city -Fix grading at front, sod -Deck bottom landing shall be min 3 ft in depth -Secure AC whip within 12” of disconnect -Seal exterior wall penetrations; seal above AC disconnect, seal exterior lights, etc -Provide CO&smoke alarm outside all bedrooms -Luminaire clearance to closet storage space not compliant (front bedroom) -Provide fall protection for all windows with bottom of openings more than 72” above grade -No power to master bathroom receptacles -Provide security strike plate for deck door with min 3” screws per security code -Provide box extension for all electrical boxes recessed more than 1/4” behind non-combustible wall finish -Provide gfci protection for dishwasher outlet -Garage door not self-closing -Provide 5/8” gypsum fire protection cover underneath attic access -Luminaire clearance to closet storage space not compliant (rear basement bedroom) -Provide AFCI protection for all outlets required per NEC 210.12
Occupancy Inspection - Codes Residential Failed 8/30/2022 8/30/2022 08/30/2022
Misc
Corrective Action Required
08/24/2022
-Obtain lawn irrigation permit and submit backflow valve test report to city **permit has not been issued. Please recheck with city -Fix grading at front, sod ** Per email, this will be repaired by Water Dept -Deck bottom landing shall be min 3 ft in depth **provide solid and level extension of the concrete landing -Provide security strike plate for deck door with min 3” screws per security code ****************************************** Sec. 7-1408.2. - Strike plates. Exterior door strike plates shall be a minimum of eighteen (18) gauge metal with four (4) offset screw holes. Strike plates shall be attached to wood with not less than three (3) inch wood screws, which shall have a minimum of one inch penetration into the nearest stud. Note: For side lighted units, refer to Section 7-1408.5. (Ord. No. 8584, § 1, 3-19-2019) ******************************************* -Provide AFCI protection for all outlets required per NEC 210.12 **afci required for all outlets located in kitchen, dining, habitable room, laundry, etc. FYI: all outlets must be afci-protected, except outlets in: outdoor, underfloor space, unfinished basement, fire alarm outlet, garage, bathroom, and attic. If your outlets are not located in the above areas, then provide afci protection at breakers.
Occupancy Inspection - Codes Residential Ready for Temp CO 8/31/2022 8/31/2022 08/31/2022
Misc
Corrective Action Required
08/30/2022
-Deck bottom landing shall be min 3 ft in depth **provide solid and level extension of the concrete landing
Occupancy Inspection - Codes Residential Temporary C of O 08/31/2022
Misc
Corrective Action Required
08/31/2022
-Deck bottom landing shall be min 3 ft in depth **provide solid and level extension of the concrete landing
Occupancy Inspection - Codes Residential Full C of O 8/31/2022 08/31/2022
Misc
Resolved
08/31/2022
-Deck bottom landing shall be min 3 ft in depth **provide solid and level extension of the concrete landing
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home

*PLEASE NOTE - You must be logged in with your registered user account to view any documents related to your permit