Summary
PRRES20213072
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - FINSIHED BASEMENT - COVERED PATIO - LANDSCAPING REQUIREMENT NEEDED, SEE PLOT PLAN REVIEW COMMENTS FOR DETAILS Project taken over by bank. Bank is now listed as point of contact. See attached documents. *** PERMIT TAKEN OVER BY DUSTIN WEBBER. PERMIT UPDATED. ON 5/23/24 Brandon Kalwei 05/23/2024 8:35 AM
06/15/2021
11/22/2021
12/12/2021
06/04/2024
Locations
Contacts
Michael Powell, Address:1101 SW US 40 Highway, Phone:(816) 591-6013  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
TEAGUE ELECTRIC CONSTRUCTION LLC, Address:12425 W 92ND ST, Phone:(913) 529-4600  
A BRIGHT PLUMBING LLC, Address:201 NE WOODBURY DR, Phone:(816) 867-4540  
DUSTIN WEBBER , Address:1225 NE GOSHEN DR. , Phone:(314) 629-4352  
DUSTIN WEBBER , Address:1225 NE GOSHEN DR. , Phone:(314) 629-4352  
Reviews

There are no reviews for this permit application.

Fees
Paid Fees Amount Paid Owing Date Paid
Right of Way Permit Fee $80.00 $80.00 Paid 11/22/2021
Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 11/22/2021
Water Tap Fee $3,581.00 $3,581.00 Paid 11/22/2021
Water Meter Fee $455.54 $455.54 Paid 11/22/2021
Valuation Fee New Single Family $1,017.72 $1,017.72 Paid 11/22/2021
8331507-Sewer Connection Fee $420.00 $420.00 Paid 11/22/2021
Valuation Fee New Single Family $69.93 $69.93 Paid 07/13/2022
$1,087.05
Temporary Occupancy Fee $50.00 $50.00 Paid 02/06/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 03/08/2024
Temporary Occupancy Fee $50.00 $50.00 Paid 04/09/2024
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection - R Passed 11/22/2021 (10:30) 11/22/2021 11/22/2021
Underslab Plumbing Inspection - Residential Passed 11/23/2021 11/23/2021 11/23/2021
Water Service Inspection - R Passed 11/24/2021 (8:15) 11/24/2021 11/24/2021
All Rough Inspection - Residential Failed 2/24/2022 2/24/2022 02/24/2022
Misc
Corrective Action Required
02/24/2022
-Provide a receptacle at foyer guardrail -Install a hanger for ceiling beam connection to lvl beam at foyer/hallway -Brace the lvl beam ends from rotation -Install mid-span support for hip rafter above hallway -Protect wiring at hallway/master bedroom wall (at triple stud) -Nail corner studs per code -Provide full support for roof beam at front bedroom exterior wall -Complete shower plumbing at front bathroom -Install purlin support for rafters above bedroom 3 -Nail master bedroom ceiling beam hangers -Support ceiling framing above master bedroom -Connect duct to master bathroom bath fan -Reduce hip rafter span above master bedroom/bathroom -Protect water line at master shower wall -Above great room, install missing ceiling beam hanger. Nail all hanger holes -Install fireplace -Security blocking for rear exterior door -At rear dining, protect wiring. Fb plate penetrations -Nail together ceiling joists to rafters (3 nails) -Nail studs at wall intersection at pantry and master closet -Secure SE cable within 12” of meter enclosure -Protect wiring within six ft of attic access -Complete garage light electrical -Anchor 3rd car garage portal wall sill plates -Tighten down garage anchor nut -Install ceiling joist hanger at rear 3rd car garage wall -Install hangers at stair -Install missing I beam support column; locate rear column to correct location -Solid block joist ends at I beam -Install double joists under bearing wall between bedroom 2&3 in basement. You have return air and plumbing in the way; double joist under master bedroom/great room wall -Complete gas piping and pressure test -Have engineer address brace wall at rear dining. Plan shows two middle windows. Currently has 3 windows all thre way to corners **OK TO INSULATE
Gas Service Inspection - Residential Failed 2/24/2022 02/24/2022
Misc
Corrective Action Required
02/24/2022
Not ready
Erosion Control Inspection Residential Passed 2/24/2022 02/24/2022
Electrical Service Inspection Passed 2/24/2022 02/24/2022
Erosion Control Inspection Residential Failed 5/19/2022 05/19/2022
Misc
Corrective Action Required
05/19/2022
-Maintain silt fence -no address posted
Erosion Control Inspection Residential Failed 5/23/2022 6/15/2022 06/15/2022
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
05/19/2022
-EROSION CONTROL REQUIRED. REPAIR EROSION CONTROL NEAR THE STORM INLET -OVERGROWN VEGETATION SHALL BE MOWED **FAILURE TO CORRECT THE ABOVE DEFICIENCIES WILLL RESULT IN AN ISSUANCE OF A STOP-WORK ORDER
All Rough Inspection - Residential Failed 7/8/2022 7/8/2022 07/08/2022
Misc
Corrective Action Required
02/24/2022
-Install a hanger for ceiling beam connection to lvl beam at foyer/hallway **nail the hanger -Protect wiring at hallway/master bedroom wall (at triple stud) -Complete shower plumbing at front bathroom **fb adjacent wall space from roof -Nail master bedroom ceiling beam hangers -Reduce hip rafter span above master bedroom/bathroom -Above great room, install missing ceiling beam hanger. Nail all hanger holes -Nail together ceiling joists to rafters (3 nails) -Install missing I beam support column; locate rear column to correct location -Install double joist under master bedroom/great room wall **BASEMENT FINISH ROUGH-INS: -Upgrade permit to include finished basement -Fb basement wall from joist and soffit space; provide vertical fire blockings every 10 ft or less ; Fb space adjacent to basement bathroom shower from joist space; Fb floor penetration at front bedroom plumbing trap -Provide venting for water heater -Provide combustion air openings per code -Protect basement bathroom plumbing at bottom wall plate -Connect duct to basement bathroom fan; flexible duct cannot exceed 14 ft. Code no longer allow 3” flexible duct. Switch to 4” flexible duct and hard duct -Provide wall receptacle spacing per code st basement bedroom -Pan off return air space above basement bedroom -Protect 3” waste stack at bottom wall plate -Provide missing stud in storage room. Max 24” stud spacing **OK TO INSULATE
Gas Service Inspection - Residential Passed 7/8/2022 07/08/2022
Misc
Resolved
07/08/2022
Not ready
Footing Inspection - Residential Passed 7/8/2022 07/08/2022
Informational
07/08/2022
FOOTING APPROVED BY 3RD PARTY ENGINEER
Piers/Caissons Inspection - Residential Passed 7/8/2022 07/08/2022
Informational
07/08/2022
PIERS APPROVED BY 3RD PARTY ENGINEER
All Rough Inspection - Residential Failed 7/14/2022 7/14/2022 07/14/2022
Misc
Corrective Action Required
07/08/2022
7/14/22 - INSPECTION DENIED, NO ACCESS, DOORS LOCKED, NO LOCK BOX CODE PROVIDED, POST SITE ADDRESS -Install a hanger for ceiling beam connection to lvl beam at foyer/hallway **nail the hanger -Protect wiring at hallway/master bedroom wall (at triple stud) -Complete shower plumbing at front bathroom **fb adjacent wall space from roof -Nail master bedroom ceiling beam hangers -Reduce hip rafter span above master bedroom/bathroom -Above great room, install missing ceiling beam hanger. Nail all hanger holes -Nail together ceiling joists to rafters (3 nails) -Install missing I beam support column; locate rear column to correct location -Install double joist under master bedroom/great room wall **BASEMENT FINISH ROUGH-INS: -Upgrade permit to include finished basement -Fb basement wall from joist and soffit space; provide vertical fire blockings every 10 ft or less ; Fb space adjacent to basement bathroom shower from joist space; Fb floor penetration at front bedroom plumbing trap -Provide venting for water heater -Provide combustion air openings per code -Protect basement bathroom plumbing at bottom wall plate -Connect duct to basement bathroom fan; flexible duct cannot exceed 14 ft. Code no longer allow 3” flexible duct. Switch to 4” flexible duct and hard duct -Provide wall receptacle spacing per code st basement bedroom -Pan off return air space above basement bedroom -Protect 3” waste stack at bottom wall plate -Provide missing stud in storage room. Max 24” stud spacing **OK TO INSULATE
All Rough Inspection - Residential Failed 9/29/2022 9/29/2022 09/29/2022
Misc
Corrective Action Required
07/14/2022
-Protect wiring at hallway/master bedroom wall (at triple stud) **please install a metal plate where the wiring is within 1.25” of the stud surface -Complete shower plumbing at front bathroom **fb adjacent wall space from roof (gap around the 3” water heater vent) -Install double joist under master bedroom/great room wall **the double joist is not directly below the bearing wall. Install solid blocking underneath the double stud on the right side of the fireplace -Provide venting for water heater **Provide installation document for water heater. Check venting requirement -Provide combustion air openings per code **min 100 sq inches for each CA opening -Pan off return air space from soffit space above basement bedroom **OK TO INSULATE
All Rough Inspection - Residential Partial 10/25/2022 10/25/2022 10/25/2022
Misc
Corrective Action Required
09/29/2022
-Provide venting for water heater **Provide installation document for water heater. Check venting requirement -Provide combustion air openings per code **min 100 sq inches for each CA opening **OK TO ROCK
Driveway Inspection Passed 12/7/2022 12/7/2022 12/08/2022
Misc
Informational
12/08/2022
12-8-22 AN driveway looks. no sidewalk
Erosion Control Inspection Residential Failed 10/3/2023 10/03/2023
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
06/15/2022
-OVERGROWN VEGETATION SHALL BE MOWED **FAILURE TO CORRECT THE ABOVE DEFICIENCIES WILLL RESULT IN AN ISSUANCE OF A STOP-WORK ORDER
Erosion Control Inspection Residential Failed - Stop Work 10/10/2023 10/10/2023
DCM3 ESC REQUIRED 2 DAY
Corrective Action Required
10/03/2023
-OVERGROWN VEGETATION SHALL BE MOWED. **THE BUILDER (MR. MICHAEL POWELL) WAS CONTACTED AND INFORMED OF THE OVERGROWN VEGETATION. HE SAID HE ALREADY CALLED TO GET THE LOT MOWED. APPARENTLY, NOTHING WAS DONE. STOP-WORK ORDER ISSUED UNTIL OVERGROWN VEGETATION IS RESOLVED
All Rough Inspection - Residential Passed 1/10/2024 01/10/2024
Misc
Resolved
01/10/2024
-Provide venting for water heater **Provide installation document for water heater. Check venting requirement -Provide combustion air openings per code **min 100 sq inches for each CA opening **OK TO ROCK
Erosion Control Inspection Residential Passed 1/10/2024 01/10/2024
DCM3 ESC REQUIRED 2 DAY
Resolved
01/10/2024
-OVERGROWN VEGETATION SHALL BE MOWED. **THE BUILDER (MR. MICHAEL POWELL) WAS CONTACTED AND INFORMED OF THE OVERGROWN VEGETATION. HE SAID HE ALREADY CALLED TO GET THE LOT MOWED. APPARENTLY, NOTHING WAS DONE. STOP-WORK ORDER ISSUED UNTIL OVERGROWN VEGETATION IS RESOLVED
Occupancy Inspection - Codes Residential Failed 1/10/2024 01/10/2024
Misc
Corrective Action Required
01/10/2024
-Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -Provide permanent address on contrasting background and near source of light -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required -Exterior not inspected at this time. Check following: Final grade, sod, downspout and sump pump extension; seal all exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc; secure AC whip within 12” of disconnect -Provide sewer tracer wire port at grade -Install a box extension for floor receptacle at foyer -Provide power to all smoke/CO alarms for testing -Provide a missing wall receptacle at west master bedroom wall -Tighten down master bathroom tub faucet stand -Provide a receptacle at each cabinet wall spaces adjacent to fireplace -At rear exterior door, install a min 3” long screw through the pre-drilled hole adjacent to the dead bolt strike plate -Anchor basement steel column in electrical service rm -Install electrical service panel cover; label all breakers -Provide AFCI protection for all outlets required per NEC 210.12. (Refrigerator, slot 12) -Install ladders at basement bedroom window wells -Fire block floor opening under master bathroom tub -Provide min one gfci-protected receptacle in the unfinished portion of basement under master bathroom -Provide mean to clean out the furnace condensate drain pipe without removing the condensate pipe -Provide a gfci-protected receptacle near whole house humidifier -Fire block wall spaces adjacent to basement bathroom shower from joist space -Provide a water pressure reducer; secure water pex line to wall -Support pex line horizontally every 32” -Support water heater blower pipe every 4 ft. Pipe must be sloped upward toward exhaust min 1/8” per 4 ft
Occupancy Inspection - Codes Residential Failed 1/26/2024 1/26/2024 01/26/2024
Misc
Corrective Action Required
01/10/2024
-Addenum 1/11/24-the attic is not insulated. Attic shall be insulated to min R-30; make sure all AFCI breakers work properly -Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -Provide permanent address on contrasting background and near source of light -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required -Exterior not inspected at this time. Check following: Final grade, sod, downspout and sump pump extension; seal all exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc; secure AC whip within 12” of disconnect -Provide sewer tracer wire port at grade -Install a box extension for floor receptacle at foyer -Provide power to all smoke/CO alarms for testing -Provide a missing wall receptacle at west master bedroom wall -Tighten down master bathroom tub faucet stand -Provide a receptacle at each cabinet wall spaces adjacent to fireplace -At rear exterior door, install a min 3” long screw through the pre-drilled hole adjacent to the dead bolt strike plate -Anchor basement steel column in electrical service rm -Install electrical service panel cover; label all breakers -Provide AFCI protection for all outlets required per NEC 210.12. (Refrigerator, slot 12) -Install ladders at basement bedroom window wells -Fire block floor opening under master bathroom tub -Provide min one gfci-protected receptacle in the unfinished portion of basement under master bathroom -Provide mean to clean out the furnace condensate drain pipe without removing the condensate pipe -Provide a gfci-protected receptacle near whole house humidifier -Fire block wall spaces adjacent to basement bathroom shower from joist space -Provide a water pressure reducer; secure water pex line to wall -Support pex line horizontally every 32” -Support water heater blower pipe every 4 ft. Pipe must be sloped upward toward exhaust min 1/8” per 4 ft
Misc
Corrective Action Required
01/26/2024
-Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required -Final grade not inspected -No sod - No downspout or sump pump extensions -Seal all exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc. -Secure AC whip within 12” of disconnect -Provide sewer tracer wire port at grade -Install longer screws at box extension for floor receptacle at foyer -Tighten down master bathroom tub faucet stand -Provide a receptacle at each cabinet wall spaces adjacent to fireplace Sent from my iPhone
Occupancy Inspection - Codes Residential Failed 1/29/2024 01/29/2024
Misc
Resolved
01/29/2024
-Addenum 1/11/24-the attic is not insulated. Attic shall be insulated to min R-30; make sure all AFCI breakers work properly -Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -Provide permanent address on contrasting background and near source of light -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required -Exterior not inspected at this time. Check following: Final grade, sod, downspout and sump pump extension; seal all exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc; secure AC whip within 12” of disconnect -Provide sewer tracer wire port at grade -Install a box extension for floor receptacle at foyer -Provide power to all smoke/CO alarms for testing -Provide a missing wall receptacle at west master bedroom wall -Tighten down master bathroom tub faucet stand -Provide a receptacle at each cabinet wall spaces adjacent to fireplace -At rear exterior door, install a min 3” long screw through the pre-drilled hole adjacent to the dead bolt strike plate -Anchor basement steel column in electrical service rm -Install electrical service panel cover; label all breakers -Provide AFCI protection for all outlets required per NEC 210.12. (Refrigerator, slot 12) -Install ladders at basement bedroom window wells -Fire block floor opening under master bathroom tub -Provide min one gfci-protected receptacle in the unfinished portion of basement under master bathroom -Provide mean to clean out the furnace condensate drain pipe without removing the condensate pipe -Provide a gfci-protected receptacle near whole house humidifier -Fire block wall spaces adjacent to basement bathroom shower from joist space -Provide a water pressure reducer; secure water pex line to wall -Support pex line horizontally every 32” -Support water heater blower pipe every 4 ft. Pipe must be sloped upward toward exhaust min 1/8” per 4 ft
Misc
Corrective Action Required
01/26/2024
-Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required -Final grade per approved as-graded plot plan (not yet submitted), lay sod. Also make sure to clean debris out from the storm inlet -No downspout or sump pump extensions -Seal all exterior wall penetrations; seal above meter, AC disconnect, seal exterior lights, etc. -Secure AC whip within 12” of disconnect -Provide sewer tracer wire port at grade -Replace broken cover plate screw at the foyer floor receptacle. Install box extension (spark ring) flushed with the wood flooring -Provide a missing wall receptacle at west master bedroom wall -Tighten down master bathroom tub faucet stand -Provide a receptacle at each cabinet wall spaces adjacent to fireplace -The window well ladders must be fasten in place
Occupancy Inspection - Codes Residential Failed 2/2/2024 2/2/2024 02/02/2024
Misc
Corrective Action Required
01/29/2024
-Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required. Inspection of the plot grading is required prior to sodding -Final grade per approved as-graded plot plan (not yet submitted), lay sod. Also make sure to clean debris out from the storm inlet -Provide sewer tracer wire port at grade -Provide a missing wall receptacle at west master bedroom wall -Provide a receptacle at each cabinet wall spaces adjacent to fireplace
Occupancy Inspection - Codes Residential Ready for Temp CO 2/6/2024 2/6/2024 02/06/2024
Misc
Corrective Action Required
02/02/2024
-Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required. Inspection of the plot grading is required prior to sodding -Final grade per approved as-graded plot plan (not yet submitted), lay sod. Also make sure to clean debris out from the storm inlet -Provide sewer tracer wire port at grade
Occupancy Inspection - Codes Residential Ready for Temp CO 3/8/2024 03/08/2024
Misc
Corrective Action Required
02/06/2024
-Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required. Inspection of the plot grading is required prior to sodding -Final grade per approved as-graded plot plan (not yet submitted), lay sod. Also make sure to clean debris out from the storm inlet -Provide sewer tracer wire port at grade
Occupancy Inspection - Codes Residential Ready for Temp CO 4/9/2024 04/09/2024
Misc
Corrective Action Required
03/08/2024
-Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -As-graded plot plan is required. Inspection of the plot grading is required prior to sodding -Final grade per approved as-graded plot plan (not yet submitted), lay sod. Also make sure to clean debris out from the storm inlet -Provide sewer tracer wire port at grade
Plot Plan Inspection Passed 5/21/2024 5/21/2024 05/21/2024
Occupancy Inspection - Codes Residential Full C of O 6/4/2024 06/04/2024
Misc
Resolved
06/04/2024
-Provide landscaping at rear of lot (3 min 8 ft tall evergreen trees, 2 ornamental trees of min 3” caliper, and 3 bushes-all located within 20 ft of rear property line) -If lawn irrigation is installed, obtain lawn irrigation permit and submit backflow valve test report to city -Provide sewer tracer wire port at grade -Sod
Documents & Images
Date Uploaded File Type Document Name
06/15/2021 license tax form
06/15/2021 Permit Codes Residential Plan Review
08/18/2021 Plot Plan APPROVED PLOT PLAN
08/18/2021 Permit Codes Residential Plan Review
11/09/2021 M L Crose 1225 NE Goshen Dr LSMO Monticello Lot 73 Be Home Permit 2021-3072 Basement Foundation footing Inspection Report 11-2-21
11/22/2021 Permit DS Building Permit
11/22/2021 Receipt Receipt for transaction: 2021-008874
11/22/2021 Letter INSPECTION SUMMARY
11/23/2021 Letter INSPECTION SUMMARY
11/24/2021 Letter INSPECTION SUMMARY
02/01/2022 1225 NE Goshen Dr_DECK PIER INSP_2022-01-31
02/24/2022 Letter INSPECTION SUMMARY
02/24/2022 Letter INSPECTION SUMMARY
02/24/2022 Letter INSPECTION SUMMARY
02/24/2022 Letter INSPECTION SUMMARY
03/24/2022 Residental Permit Application_Lees summit - basement
03/24/2022 Approved Plans Approved Revised Drawings
05/18/2022 Lot 73 Monticello Letter
05/19/2022 Letter INSPECTION SUMMARY
05/19/2022 Letter INSPECTION SUMMARY
06/15/2022 Letter INSPECTION SUMMARY
06/15/2022 Letter INSPECTION SUMMARY
06/15/2022 INSPECTION SUMMARY (All Recipients) 20220615135906
07/07/2022 Lot 73 Monticello Letter
07/08/2022 Letter INSPECTION SUMMARY
07/08/2022 Letter INSPECTION SUMMARY
07/08/2022 Letter INSPECTION SUMMARY
07/08/2022 Letter INSPECTION SUMMARY
07/12/2022 Application Form application
07/12/2022 Approved Plans APPROVED PLANS
07/13/2022 Receipt Receipt for transaction:2022-005702
07/14/2022 Letter INSPECTION SUMMARY
09/29/2022 Letter INSPECTION SUMMARY
10/25/2022 Letter INSPECTION SUMMARY
12/08/2022 Letter INSPECTION SUMMARY
10/04/2023 Letter INSPECTION SUMMARY
10/10/2023 Letter Stop Work Order
10/10/2023 Letter Stop Work Order
11/21/2023 Letter Bank Owner Letter
01/10/2024 Letter INSPECTION SUMMARY
01/10/2024 Letter INSPECTION SUMMARY
01/10/2024 Letter INSPECTION SUMMARY
01/11/2024 Photograph Uninsulatd Attic 2
01/11/2024 Photograph Uninsulated Attic 1
01/29/2024 Letter INSPECTION SUMMARY
02/02/2024 Letter INSPECTION SUMMARY
02/02/2024 Letter INSPECTION SUMMARY
02/02/2024 Letter INSPECTION SUMMARY
02/06/2024 Certificate/License Codes Temporary Certificate of Occupancy
02/06/2024 Receipt Receipt for transaction:2024-000647
03/01/2024 Recorded Trustee's Deed w Affidavit
03/01/2024 TCO Extension Form 3_1_24
03/08/2024 Certificate/License Codes Temporary Certificate of Occupancy
03/08/2024 Receipt Receipt for transaction:2024-001469
04/09/2024 Application Form TCO EXTENSION
04/09/2024 Certificate/License Codes Temporary Certificate of Occupancy
04/09/2024 Receipt Receipt for transaction:2024-002257
05/20/2024 1225 NE Goshen As Graded Plot Plan 05_20_24
05/21/2024 Letter INSPECTION SUMMARY
05/22/2024 1225 NE Goshen Permit Application
05/22/2024 Goshen Warranty deed owners policy
05/23/2024 Letter DS Building Permit
06/04/2024 Letter Codes Final Certificate of Occupancy
06/04/2024 Letter Field Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.