Permit Application Status

PRRES20211949


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20211949
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - COVERED PATIO STOP WORK ORDER generated on 09/01/2021 12:00 AM by username 'Patrick Schonfeldt'. STOP WORK ORDER removed on 09/02/2021 12:00 AM by username 'Patrick Schonfeldt'.
04/21/2021
05/24/2021
10/19/2021
09/15/2022
Locations
Contacts
CLAYTON PROPERTIES GROUP, INC, Address:120 SE 30TH ST, Phone:(816) 246-6700  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
ARROW CIRCLE ELECTRIC, Address:1224 SE CENTURY DR, Phone:(816) 373-4888  
RELIABLE MECHANICAL SERVICES INC, Address:1025 W COUCHMAN DR, Phone:(816) 903-7674  
DUSTIN@SUMMITHOMESKC.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 05/26/2021 05/24/2021
Kim Brennan
Property boundary
Corrective Action Required
05/24/2021

Property boundary distances and bearings, as shown on the recorded plat, must be provided on the plot plan. Right side property distance should be 120.00
Easements
Corrective Action Required
05/24/2021

All easements with dimensions must be provided on the plot plan. Please show 7.5 U/E along the rear
Sidewalks
Corrective Action Required
05/24/2021

Sidewalks with dimensions must be provided on the plot plan.
Residential Plan Review Approved 05/26/2021 05/24/2021
Kim Brennan
Plot Plan Review Rejected 04/23/2021 04/22/2021
Kim Brennan
Property boundary
Corrective Action Required
04/22/2021

Property boundary distances and bearings, as shown on the recorded plat, must be provided on the plot plan. Right side property distance should be 120.00
Easements
Corrective Action Required
04/22/2021

All easements with dimensions must be provided on the plot plan. Please show 7.5 U/E along the rear
Sidewalks
Corrective Action Required
04/22/2021

Sidewalks with dimensions must be provided on the plot plan.
Residential Plan Review Approved 04/23/2021 04/22/2021
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,348.05 $1,348.05 Paid 05/24/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 05/24/2021
7232302-Residential License Tax Fee $1,077.12 $1,077.12 Paid 05/24/2021
8331504-EFHB Middle Big Creek, Full $669.60 $669.60 Paid 05/24/2021
8331507-Sewer Connection Fee $600.00 $600.00 Paid 05/24/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 05/24/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 05/24/2021
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/13/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/13/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/13/2022
9110080-3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 09/13/2022
9110080-Not Ready Inspection Fee $50.00 $50.00 Paid 09/13/2022
9110080-3rd and Subsequent Inspection Fee (Per Hour) $50.00 $50.00 Paid 09/13/2022
9110080-Not Ready Inspection Fee $75.00 $75.00 Paid 09/13/2022
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Underslab Plumbing Inspection - Residential Failed 9/1/2021 9/1/2021 09/01/2021
Misc
Corrective Action Required
09/01/2021
INSPECTION DENIED FOOTING POURED WITHOUT INSPECTION, ENGINEER REPORT REQUIRED TO BE SUBMITTED TO PERMIT WITHIN 48 HOURS OF INSPECTION
Footing Inspection - Residential Failed - Stop Work 9/1/2021 9/1/2021 09/01/2021
Misc
Corrective Action Required
09/01/2021
INSPECTION DENIED FOOTING POURED WITHOUT INSPECTION, ENGINEER REPORT REQUIRED TO BE SUBMITTED TO PERMIT WITHIN 48 HOURS OF INSPECTION
Footing Inspection - Residential Passed 9/2/2021 9/2/2021 09/02/2021
Misc
Informational
09/02/2021
-APPROVED PER BRADLEY HUXOL 7/21/21-
Underslab Plumbing Inspection - Residential Failed 9/3/2021 9/3/2021 09/03/2021
Misc
Corrective Action Required
09/01/2021
UNABLE TO PERFORM INSPECTION WITH MUD WATER COVERING DWV FROM RAIN, RESCHEDULE WHEN CONDITIONS ALLOW FOR INSPECTION MAINTAIN SILT FENCE AT FRONT OF LOT
Underslab Plumbing Inspection - Residential Passed 9/14/2021 9/14/2021 09/14/2021
Misc
Resolved
09/14/2021
Sewer Service Inspection - R Passed 11/4/2021 11/4/2021 11/04/2021
Water Service Inspection - R Partial 11/5/2021 (9:15) 11/5/2021 11/05/2021
Water Service Inspection - R Passed 11/5/2021 (1:00) 11/5/2021 11/05/2021
Erosion Control Inspection Residential Failed 3/8/2022 3/8/2022 03/08/2022
DCM2 ESC DEFICIENT INSTALLATION
Corrective Action Required
03/08/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. ADDRESS EROSION CONTROL ON LOT GRAVEL FILTER REQUIRED, MIN 6" LIFT 3/4" GRAVEL CLEAN ALL MUD FROM STREET
Gas Service Inspection - Residential Failed 4/4/2022 4/4/2022 04/04/2022
Misc
Corrective Action Required
04/04/2022
-Pressure at gauge only 5 psi -Bond metallic gas line before CSST connection
Electrical Service Inspection Passed 4/4/2022 4/4/2022 04/04/2022
All Rough Inspection - Residential Failed 4/4/2022 4/4/2022 04/04/2022
Misc
Corrective Action Required
04/04/2022
-Maintain erosion control methods at front of lot, clean debris from street -Attic access requires min 30” of clearance at garage -Exterior walls not connected at top plate at single car bay -Exterior walls not connected at top plates at back garage wall/pantry -Complete fireblocking at soffit line in garage at dwv and seal all penetrations -Provide H2.5 both ends of truss at single bay to double bay garage -Missing LIB at garage -Nail all LIB to sole plates -16g ,1.5” structural straps extending 6” each direction past bore with (4) 10d nails required at bored top plate in pantry, great room/bath 4, bath 4/bed 5 these are not the correct strap -Install SGD -Install missing nail at hanger at LVL in dining near stairs -Bocca plate at bottom plate of dead space in great room -Protect CSST through cabinet at fireplace-this should be hard piped per manufacturer -Remove sheathing and nail H2.5s to framing members at covered deck -Seal bottom plate penetration at bath 4 closet -Solid block between joists at load bearing wall bed 5 -Address bearing wall in bath 4 to be non load bearing- plans show this wall to be bed 5 wall, there is also no header in this doorway to support the floor joists and the load does not transfer the beam below-Have engineer address this wall or rebuild per plans -Address holes bored within 2” of each other at joists in bed 5 -Nail exterior corner connections per code -(4) studs at GT bearing bed 2 closet -Provide H2.5s and (4) bearing studs at bath 2 GT -Address damaged gusset plates at DWV bath 2 vanity vent -Provide roof boot at VTRs -Insulate behind shower at bath 3 -Install drain for master bath -Missing snow blocking master bed -Provide 1” clearance to combustibles at B vent/truss -Address damaged gusset plates at dwv above master shower -Bocca plate at pex lines in laundry -Seal top plate penetration at laundry/hallway -Protect nm secured less than 1.25” to face of stud at laundry -NM sheathing to extend into boxes at laundry -Address beam in basement undersized- plans show 10x26, 10x17 installed -Address holes bored less than 2” to bottom of joist at gas piping and less than 2” to top at dwv -Bond metallic gas line before ward flex connection -Gas pressure gauge only at 5 -1” clearance to combustibles required at flex b vent at furnace -Solid block between joists 48” oc and extend one bay past each way at island -Missing double 2x10 near egress window -Complete electrical in basement coiled up near stairs -Nail exterior sheathing per code
Gas Service Inspection - Residential Not Ready 4/14/2022 4/14/2022 04/14/2022
Misc
Corrective Action Required
04/04/2022
-Pressure at gauge only 5 psi -Bond metallic gas line before CSST connection
All Rough Inspection - Residential Failed 4/14/2022 4/14/2022 04/14/2022
Misc
Corrective Action Required
04/04/2022
-Complete fireblocking at soffit line in garage at dwv and seal all penetrations -Install missing nail at hanger at LVL in dining near stairs -Bocca plate at bottom plate of dead space in great room (plate must protect bottom plate and 2” above bottom plate) -Solid block between joists at load bearing wall bed 5 -Address bearing wall in bath 4 to be non load bearing- plans show this wall to be bed 5 wall, there is also no header in this doorway to support the floor joists and the load does not transfer the beam below-Have engineer address this wall or rebuild per plans (engineer letter confirms bath 4 wall non load bearing) -Address holes bored within 2” of each other at joists in bed 5 (repair per engineer letter) -Install drain for master bath -Address holes bored less than 2” to bottom of joist at gas piping and less than 2” to top at dwv (repair per engineer letter) -Bond metallic gas line before ward flex connection -Gas pressure gauge only at 5 ok to insulate
Erosion Control Inspection Residential Partial 4/14/2022 4/14/2022 04/14/2022
DCM2 ESC DEFICIENT INSTALLATION
Resolved
04/14/2022
DEFICIENT EROSION CONTROL INSTALLATION. NO FURTHER INSPECTIONS UNTIL ADEQUATE EROSION CONTROL PROVIDED. ADDRESS EROSION CONTROL ON LOT GRAVEL FILTER REQUIRED, MIN 6" LIFT 3/4" GRAVEL CLEAN ALL MUD FROM STREET
All Rough Inspection - Residential Not Ready 4/19/2022 4/19/2022 04/19/2022
Misc
Corrective Action Required
04/14/2022
-Address bearing wall in bath 4 to be non load bearing- plans show this wall to be bed 5 wall, there is also no header in this doorway to support the floor joists and the load does not transfer the beam below- (the replacement joists have been ripped to less than full depth, not acceptable) -Address holes bored within 2” of each other at joists in bed 5 (repair per engineer letter) -Install drain for master bath (plumbing should be stubbed through floor) -Address holes bored less than 2” to bottom of joist at gas piping and less than 2” to top at dwv (repair per engineer letter, 2’ CS-16 strap) -Gas pressure gauge only at 7 psi, must maintain 10 psi ok to insulate
Gas Service Inspection - Residential Failed 4/19/2022 4/19/2022 04/19/2022
Misc
Corrective Action Required
04/14/2022
-Pressure at gauge only 7 psi, must maintain 10 psi for test
All Rough Inspection - Residential Not Ready 4/20/2022 4/20/2022 04/20/2022
Misc
Corrective Action Required
04/19/2022
**4/20/22 - NOT READY, INSPECTION DENIED, CORRECTIONS NOT ADDRESSED** -Address bearing wall in bath 4 to be non load bearing- plans show this wall to be bed 5 wall, there is also no header in this doorway to support the floor joists and the load does not transfer the beam below- (the replacement joists have been ripped to less than full depth, not acceptable) -Address holes bored within 2” of each other at joists in bed 5 (repair per engineer letter) -Install drain for master bath (plumbing should be stubbed through floor) -Address holes bored less than 2” to bottom of joist at gas piping and less than 2” to top at dwv (repair per engineer letter, 2’ CS-16 strap) -Gas pressure gauge only at 7 psi, must maintain 10 psi ok to insulate
All Rough Inspection - Residential Failed 4/22/2022 4/22/2022 04/22/2022
Misc
Corrective Action Required
04/20/2022
**4/20/22 - NOT READY, INSPECTION DENIED, CORRECTIONS NOT ADDRESSED** -Address bearing wall in bath 4 to be non load bearing- plans show this wall to be bed 5 wall, there is also no header in this doorway to support the floor joists and the load does not transfer the beam below- (the replacement joists have been ripped to less than full depth, not acceptable) -Address holes bored within 2” of each other at joists in bed 5 (repair per engineer letter) -Install drain for master bath (plumbing should be stubbed through floor) -Address holes bored less than 2” to bottom of joist at gas piping and less than 2” to top at dwv (repair per engineer letter, 2’ CS-16 strap) -Gas pressure gauge only at 7 psi, must maintain 10 psi ok to insulate
Misc
Corrective Action Required
04/22/2022
Contact Mark Harding if you have questions. Sistered floor joist have been ripped to less than 9", used lumber has been installed andcross cut with skill saw, previously used with nails. Grade stamp is not visible on any sistered joist installed. All joist in this area need to be removed and replace with approved material. Engineer letter is denied and not applicable for this issue.
Gas Service Inspection - Residential Passed 4/20/2022 5/2/2022 05/02/2022
Misc
Resolved
05/02/2022
-Pressure at gauge only 7 psi, must maintain 10 psi for test
All Rough Inspection - Residential Failed 5/2/2022 5/2/2022 05/02/2022
Misc
Corrective Action Required
04/22/2022
-Address holes bored less than 2” to bottom of joist at gas piping and less than 2” to top at dwv (repair per engineer letter, 2’ CS-16 strap) -complete plumbing for master tub, plumbing should be penetrating floor and fireblock at trap ok to insulate
Misc
Resolved
05/02/2022
Contact Mark Harding if you have questions. Sistered floor joist have been ripped to less than 9", used lumber has been installed andcross cut with skill saw, previously used with nails. Grade stamp is not visible on any sistered joist installed. All joist in this area need to be removed and replace with approved material. Engineer letter is denied and not applicable for this issue.
Driveway Inspection Partial 5/4/2022 05/04/2022
Misc
Informational
05/04/2022
On 5.4.2022 I performed a driveway inspection and pass the sub-grade to pour concrete.
Sidewalk Inspection Partial 5/4/2022 05/04/2022
Misc
Informational
05/04/2022
On 5.4.2022 I performed a sidewalk inspection and pass the sub-grade to pour concrete.
All Rough Inspection - Residential Not Ready 5/6/2022 5/6/2022 05/06/2022
Misc
Corrective Action Required
05/02/2022
-Address holes bored less than 2” to bottom of joist at gas piping and less than 2” to top at dwv (repair per engineer letter, 2’ CS-16 strap), UNABLE TO PERFORM INSPECTION IN BASEMENT, NEAR FOOT OF STANDING WATER IN BASEMENT ok to insulate
All Rough Inspection - Residential Passed 5/9/2022 5/9/2022 05/09/2022
Misc
Resolved
05/09/2022
Erosion Control Inspection Residential Partial 5/9/2022 05/09/2022
Driveway Inspection Passed 9/8/2022 9/8/2022 09/08/2022
Misc
Informational
05/04/2022
On 5.4.2022 I performed a driveway inspection and pass the sub-grade to pour concrete. 9-8-22 RH. Driveway meets LS and ADA specification.
Sidewalk Inspection Passed 9/8/2022 9/8/2022 09/08/2022
Misc
Informational
05/04/2022
On 5.4.2022 I performed a sidewalk inspection and pass the sub-grade to pour concrete. 9-8-22 RH. Sidewalk meets LS and ADA specification.
Occupancy Inspection - Codes Residential Not Ready 9/9/2022 9/9/2022 09/09/2022
Misc
Corrective Action Required
09/09/2022
NO INSPECTION, DOORS LOCKED, NO LOCK BOX CODE PROVIDED
Erosion Control Inspection Residential Passed 9/13/2022 9/13/2022 09/13/2022
Occupancy Inspection - Codes Residential Failed 9/13/2022 9/13/2022 09/13/2022
Misc
Corrective Action Required
09/09/2022
-resolve outstanding inspection fees -repair rock at garage wall left of outlet -mark dedicated receptacles as not GFCI protected -provide access jacuzzi tub motor at master bath -AFCI protection all breaker locations per code, IRC E3902.16, NEC 210.12(A)
Occupancy Inspection - Codes Residential Failed 9/13/2022 9/13/2022 09/13/2022
Misc
Corrective Action Required
09/13/2022
-resolve outstanding inspection fees -repair rock at garage wall left of outlet -mark dedicated receptacles as not GFCI protected -provide access jacuzzi tub motor at master bath -AFCI protection all breaker locations per code, IRC E3902.16, NEC 210.12(A) -remove all construction debris and silt fence at rear of lot
Plot Plan Inspection Passed 9/13/2022 9/13/2022 09/13/2022
Occupancy Inspection - Codes Residential Full C of O 9/15/2022 9/15/2022 09/15/2022
Misc
Resolved
09/15/2022
Documents & Images
Date Uploaded File Type Document Name
04/21/2021 Application Form Permit Application and License Tax Form
04/22/2021 Approved Plans Approved Drawings
04/22/2021 Approved Plans Approved Truss Layout
04/22/2021 Approved Plans Approved Truss Package
04/22/2021 Letter Codes Residential Plan Review
05/24/2021 Plot Plan Approved Plot Plan
05/24/2021 Permit DS Building Permit
05/24/2021 Receipt Receipt for transaction:2021-003441
09/01/2021 Letter INSPECTION SUMMARY
09/01/2021 Letter Stop Work Order
09/01/2021 Lot 79 Reserve at Stoney Creek Footing Inspection
09/01/2021 Lot 79 Reserve at Stoney Creek Foundation Inspection
09/02/2021 Letter INSPECTION SUMMARY
09/03/2021 Letter INSPECTION SUMMARY
09/14/2021 Letter INSPECTION SUMMARY
11/04/2021 Letter INSPECTION SUMMARY
11/05/2021 Letter INSPECTION SUMMARY
11/05/2021 Letter INSPECTION SUMMARY
03/08/2022 Letter INSPECTION SUMMARY
04/04/2022 Letter INSPECTION SUMMARY
04/04/2022 Letter INSPECTION SUMMARY
04/04/2022 Letter INSPECTION SUMMARY
04/08/2022 RR 79 TRUSS GUSSETS
04/08/2022 79 RESERVE AT STONEY CREEK LETTER (002)
04/11/2022 RR 79 Basement pier
04/14/2022 Letter INSPECTION SUMMARY
04/14/2022 Letter INSPECTION SUMMARY
04/14/2022 Letter INSPECTION SUMMARY
04/19/2022 Letter INSPECTION SUMMARY
04/19/2022 Letter INSPECTION SUMMARY
04/20/2022 Letter INSPECTION SUMMARY
04/21/2022 RR 79 BR45 & GR
04/22/2022 Letter INSPECTION SUMMARY
05/02/2022 Letter INSPECTION SUMMARY
05/02/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/04/2022 Letter INSPECTION SUMMARY
05/06/2022 Letter INSPECTION SUMMARY
05/09/2022 Letter INSPECTION SUMMARY
05/09/2022 Letter INSPECTION SUMMARY
05/10/2022 Letter INSPECTION SUMMARY
09/08/2022 Letter INSPECTION SUMMARY
09/08/2022 Letter INSPECTION SUMMARY
09/09/2022 Letter INSPECTION SUMMARY
09/13/2022 Letter INSPECTION SUMMARY
09/13/2022 Letter INSPECTION SUMMARY
09/13/2022 Letter INSPECTION SUMMARY
09/13/2022 Letter INSPECTION SUMMARY
09/13/2022 Receipt Receipt for transaction:2022-007483
09/15/2022 Letter Field Certificate of Occupancy
09/15/2022 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home