Permit Application Status

PRRES20211710


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20211710
Building Permit - Residential
Certificate of Occupancy
NEW SINGLE FAMILY
NEW HOUSE - FINISHED AND UNFINISHED BASEMENT - COVERED DECK
04/09/2021
04/13/2021
04/18/2022
Locations
Contacts
SAB CONSTRUCTION INC, Address:PO BOX 942, Phone:(816) 524-3855  
CURTIS@SABHOMES.COM  
MIKE BRYANT HEATING & COOLING , Address:1711 E 123RD , Phone:(913) 441-7807  
C-R ELECTRICAL LLC, Address:4539 RIDGEWAY, Phone:(816) 803-3500  
GARRISON PLUMBING, Address:15430 S MAHAFFIE ST STE 102, Phone:(913) 768-1311  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 04/14/2021 04/12/2021
Brandon Kalwei
As-graded plot plan
Corrective Action Required
04/12/2021

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy.
Residential Plan Review Approved 04/14/2021 04/12/2021
Brandon Kalwei
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,081.92 $1,081.92 Paid 04/13/2021
8331507-Sewer Connection Fee $480.00 $480.00 Paid 04/13/2021
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 04/13/2021
7232302-Residential Excise Tax Fee $1,077.12 $1,077.12 Paid 04/13/2021
8331401-Water Tap Fee $3,581.00 $3,581.00 Paid 04/13/2021
8350015-Water Meter Fee $455.54 $455.54 Paid 04/13/2021
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Sewer Service Inspection - R Passed 6/11/2021 (10:15) 6/11/2021 06/11/2021
Water Service Inspection - R Partial 6/11/2021 06/11/2021
Misc
Informational
06/11/2021
PARTIAL WATER 15' PEX TO METER PIT
Underslab Plumbing Inspection - Residential Passed 6/14/2021 6/14/2021 06/14/2021
Erosion Control Inspection Residential Failed 06/14/2021
Misc
Corrective Action Required
06/14/2021
-Erosion control requires continuous maintenance. Repair damaged sections at front and rear property lines within 48 hours
Miscellaneous Inspection Failed 06/14/2021
Misc
Corrective Action Required
06/14/2021
post site address
Footing Inspection - Residential Passed 06/14/2021
Water Service Inspection - R Passed 6/14/2021 (1:00) 6/14/2021 06/14/2021
Misc
Resolved
06/14/2021
PARTIAL WATER 15' PEX TO METER PIT
Piers/Caissons Inspection - Residential Passed 7/13/2021 07/13/2021
Gas Service Inspection - Residential Passed 12/1/2021 12/1/2021 12/01/2021
Electrical Service Inspection Failed 12/1/2021 12/1/2021 12/01/2021
Misc
Corrective Action Required
12/01/2021
Gas bond not connected
All Rough Inspection - Residential Failed 12/1/2021 12/1/2021 12/01/2021
Miscellaneous Correction
Corrective Action Required
12/01/2021
- fire block penetration return air space at basement bathroom by furnace - Nail corner bedroom 3 - Add support to lvl from twisting over stairs - Fire block penetration in return bedroom 2 - Address missing vent boot master closet - Security block back doors 3 stud bays - Address over bored 3 pack 2x4’s master bedroom fire place lvl support - Address missing vent boot above kitchen and throughout - Keep outlet accessible for master tub - Nail outside sheeting sill plate
Electrical Service Inspection Passed 12/8/2021 12/8/2021 12/08/2021
Misc
Resolved
12/08/2021
All Rough Inspection - Residential Failed 12/8/2021 12/8/2021 12/08/2021
Miscellaneous Correction
Corrective Action Required
12/01/2021
- fire block penetration return air space at basement bathroom by furnace ( by pex ) - Fire block penetration in return bedroom 2 - Security block back doors 3 stud bays - Address over bored 3 pack 2x4’s master bedroom fire place lvl support - Keep outlet accessible for master tub - Nail outside sheeting sill plate
All Rough Inspection - Residential Failed 12/10/2021 12/10/2021
Miscellaneous Correction
Resolved
12/10/2021
All Rough Inspection - Residential Passed 12/16/2021 12/16/2021 12/16/2021
Erosion Control Inspection Residential Failed 4/5/2022 04/05/2022
Misc
Resolved
04/05/2022
-Erosion control requires continuous maintenance. Repair damaged sections at front and rear property lines within 48 hours
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/05/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Occupancy Inspection - Codes Residential Failed 4/5/2022 4/5/2022 04/05/2022
Misc
Corrective Action Required
04/05/2022
-No further inspections until Eros control is in compliance -sod -address siding from ground at back of lot -Address to be of contrasting colors -seat top of A/c disconnect and all other exterior penetrations -splash blocks and sump pump discharge to extend 36” from foundation -security screws at back doors -jet tub pump to be accessible to code -sheet off set screw for anti syphon device at water -remove rebar from street -driveway inspection still pending
Driveway Inspection Passed 2/10/2022 2/10/2022 04/07/2022
Misc
Informational
02/10/2022
On Thursday 2.10.2022 I performed a driveway inspection and pass the subgrade to pour concrete.
Plot Plan Inspection Passed 4/8/2022 04/08/2022
Occupancy Inspection - Codes Residential Temporary C of O 4/12/2022 4/12/2022 04/12/2022
Misc
Corrective Action Required
04/05/2022
-sod -address siding from ground at back of lot -seat top of A/c disconnect and all other exterior penetrations -splash blocks and sump pump discharge to extend 36” from foundation -driveway inspection still pending
Driveway Inspection Passed 4/7/2022 4/7/2022 04/12/2022
Misc
Informational
02/10/2022
On Thursday 2.10.2022 I performed a driveway inspection and pass the subgrade to pour concrete.
Erosion Control Inspection Residential Passed 4/18/2022 04/18/2022
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
04/05/2022
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Occupancy Inspection - Codes Residential Full C of O 4/18/2022 4/18/2022 04/18/2022
Misc
Resolved
04/18/2022
-sod -address siding from ground at back of lot -seat top of A/c disconnect and all other exterior penetrations -splash blocks and sump pump discharge to extend 36” from foundation -driveway inspection still pending
Documents & Images
Date Uploaded File Type Document Name
04/09/2021 Application Form APPLICATION
04/09/2021 Application Form excise tax
04/09/2021 E732 - Air Combustion Calculation
04/09/2021 E732 - Final Plot Plan
04/09/2021 E732 - City Approved Plans 4_9_21
04/12/2021 Approved Plans APPROVED PLANS
04/13/2021 Receipt Receipt for transaction:2021-001942
04/13/2021 Letter DS Building Permit
04/20/2021 E732 - Final Engineered Plans
04/20/2021 Approved Plans APPROVED PLANS
05/26/2021 LOT 732 FINAL 5-25-21
06/01/2021 M L Crose 2345 SW Old Port Rd LSMO Eagle Creek Lot 732 SAB Permit 2021-1710 3rd Party Footing Inspection Report 6-1-21
06/11/2021 Letter INSPECTION SUMMARY
06/11/2021 Letter INSPECTION SUMMARY
06/14/2021 Letter INSPECTION SUMMARY
06/14/2021 Letter INSPECTION SUMMARY
06/14/2021 Letter INSPECTION SUMMARY
06/14/2021 Letter INSPECTION SUMMARY
06/14/2021 Letter INSPECTION SUMMARY
07/13/2021 Letter INSPECTION SUMMARY
12/01/2021 Letter INSPECTION SUMMARY
12/01/2021 Letter INSPECTION SUMMARY
12/01/2021 Letter INSPECTION SUMMARY
12/08/2021 Letter INSPECTION SUMMARY
12/08/2021 Letter INSPECTION SUMMARY
12/10/2021 Letter INSPECTION SUMMARY
12/16/2021 Letter INSPECTION SUMMARY
02/10/2022 Letter INSPECTION SUMMARY
04/05/2022 Letter INSPECTION SUMMARY
04/05/2022 Letter INSPECTION SUMMARY
04/07/2022 Plot Plan APPROVED AS GRADED PLOT PLAN
04/07/2022 Letter INSPECTION SUMMARY
04/08/2022 Letter INSPECTION SUMMARY
04/12/2022 Letter INSPECTION SUMMARY
04/12/2022 Letter Codes Temporary Certificate of Occupancy
04/18/2022 Letter Codes Final Certificate of Occupancy
04/18/2022 Letter Field Certificate of Occupancy
04/18/2022 Letter INSPECTION SUMMARY
04/27/2022 Letter INSPECTION SUMMARY
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home