Permit Application Status

PRRES20191010


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20191010
Building Permit - Residential
Certificate of Occupancy
KEVIN HIGDON CONSTRUCTION LLC
NEW SINGLE FAMILY
NEW HOUSE, COVERED DECK FINISHED/UNFINISHED BASEMENT
04/22/2019
05/09/2019
06/24/2020
Locations
Contacts
KEVIN HIGDON CONSTRUCTION LLC, Address:PO BOX 847, Phone:(816) 524-9797  
KEVIN@HIGDONBUILDERS.COM  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
LUCAS ELECTRIC , Address:517 MARGARET LN, Phone:(816) 807-4432  
MILLER PLUMBING CO, Address:PO BOX 393 , Phone:(913) 851-1333  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 04/24/2019 04/24/2019
Steve Conrick
As-graded plot plan
Corrective Action Required
04/22/2019

A as-graded plot plan per Section 7-160, Code of Ordinances, is required prior to occupancy. *Please add note that states "AS-GRADED PLOT PLAN IS REQUIRED PRIOR TO SODDING."
Drainage swales
Corrective Action Required
04/22/2019

Drainage swales (where required); show spot elevations within the swale as required to conform to the approved master drainage plan (if applicable), must be provideD *Move the swale arrow and lettering into the swale to minimize confusion.
Residential Plan Review Approved 04/24/2019 04/22/2019
Dylan Eppert
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $378.71 $378.71 Paid 05/09/2019
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 05/09/2019
8331504-EFHB Middle Big Creek, Full $435.24 $435.24 Paid 05/09/2019
8331507-Sewer Connection Fee $390.00 $390.00 Paid 05/09/2019
8331401-Water Tap Fee $3,409.00 $3,409.00 Paid 05/09/2019
8350015-Water Meter Fee $408.37 $408.37 Paid 05/09/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 5/13/2019 (3:30) 5/13/2019 at 3:30 PM 05/13/2019
Underslab Plumbing Inspection - Residential Failed 6/5/2019 6/5/2019 at 2:55 PM 06/05/2019
Misc
Corrective Action Required
06/05/2019
NO ADDRESS POSTED. NO EROSION CONTROL.
Erosion Control Inspection Residential Failed 6/5/2019 at 2:30 PM 06/05/2019
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
06/05/2019
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Underslab Plumbing Inspection - Residential Passed 6/12/2019 6/12/2019 06/12/2019
Misc
Resolved
06/12/2019
Sewer Service Inspection - R Failed 6/24/2019 06/24/2019
Misc
Corrective Action Required
06/24/2019
-piping not on adequate gravel -pit full of water, could not see connection
Sewer Service Inspection - R Failed 6/25/2019 6/25/2019 at 8:45 AM 06/25/2019
Misc
Corrective Action Required
06/24/2019
-piping not on adequate gravel -pit full of water, could not see connection
Sewer Service Inspection - R Passed 6/25/2019 at 10:00 AM 06/25/2019
Misc
Resolved
06/25/2019
-piping not on adequate gravel -pit full of water, could not see connection
Water Service Inspection - R Failed 6/26/2019 (1:00) 6/26/2019 at 1:30 PM 06/26/2019
Misc
Corrective Action Required
06/26/2019
CITY OF LS REQUIRES 10' OF COPPEER ON THE HOUSE SIDE OF THE METER. METER IS JUST UNDER 14" NEEDS TO BE BETWEEN 14" AND 18"
Water Service Inspection - R Passed 6/27/2019 6/27/2019 at 9:15 AM 06/27/2019
Misc
Resolved
06/27/2019
CITY OF LS REQUIRES 10' OF COPPEER ON THE HOUSE SIDE OF THE METER. METER IS JUST UNDER 14" NEEDS TO BE BETWEEN 14" AND 18"
Piers/Caissons Inspection - Residential Passed 7/11/2019 (9:00) 7/11/2019 at 9:16 AM 07/11/2019
Gas Piping Inspection - Residential Passed 9/16/2019 9/16/2019 09/16/2019
Erosion Control Inspection Residential Failed 09/16/2019
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
06/05/2019
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED. Vegetation also needs to be maintained per city code. Clean up dirt and debris off of the curb and street.
All Rough Inspection - Residential Failed 10/24/2019 10/24/2019 10/24/2019
Misc
Corrective Action Required
10/24/2019
Joist hanger needed in laundry room Clean up lot of debris and trash Establish erosion control at back of lot to protect inlet to the east Ok to insulate
Electrical Service Inspection Passed 10/24/2019
Gas Service Inspection - Residential Passed 10/24/2019
All Rough Inspection - Residential Failed 10/29/2019 10/29/2019
Misc
Corrective Action Required
10/24/2019
Joist hanger needed in laundry room Clean up lot of debris and trash Establish erosion control at back of lot to protect inlet to the east Ok to insulate
All Rough Inspection - Residential Passed 11/1/2019 11/1/2019 11/01/2019
Misc
Corrective Action Required
10/29/2019
Establish erosion control at back of lot to protect inlet to the east Ok to insulate
Driveway Inspection Partial 11/8/2019 11/8/2019 11/08/2019
Misc
Corrective Action Required
11/08/2019
Forms were placed and aggregate was present. Cross slope of driveway approach is out of tolerance of ADA specs. RP 11-8-19
Misc
Informational
11/08/2019
After further investigation, lot 4011 does NOT have a sidewalk. The driveway approach is GOOD to pour as is. RP 11-8-19
Plot Plan Inspection Passed 4/21/2020 04/21/2020
Occupancy Inspection - Codes Residential Failed 6/19/2020 6/19/2020 06/19/2020
Misc
Corrective Action Required
06/19/2020
- Furnace to be properly hardwired - Water heater discharge pipe shall terminate not more than 6” and not less than two times the discharge pipe diameter size above the floor - Correct broken hold down clamps for main service line above electric service panel - Install dishwasher to complete kitchen plumbing - Seal all exterior penetrations in siding
Driveway Inspection Passed 06/23/2020
Misc
Resolved
06/23/2020
Forms were placed and aggregate was present. Cross slope of driveway approach is out of tolerance of ADA specs. RP 11-8-19
Misc
Informational
06/23/2020
No sidewalk or ADA through the approach.
Occupancy Inspection - Codes Residential Full C of O 06/24/2020
Misc
Resolved
06/24/2020
Contact Mark Harding -MARK HARDING 06/23/2020 1:05 PM, personal items and occupied without approval.
Documents & Images
Date Uploaded File Type Document Name
04/22/2019 Letter Codes Residential Plan Review
04/25/2019 SKM_C36819042313380
05/09/2019 Receipt Receipt for transaction: 2019-001861
05/09/2019 Letter Codes Building Permit
05/09/2019 Plot Plan DOC050919-05092019161737
05/13/2019 Letter INSPECTION SUMMARY
06/05/2019 Letter INSPECTION SUMMARY
06/05/2019 Letter INSPECTION SUMMARY
06/12/2019 Letter INSPECTION SUMMARY
06/24/2019 Letter INSPECTION SUMMARY
06/25/2019 Letter INSPECTION SUMMARY
06/25/2019 Letter INSPECTION SUMMARY
06/26/2019 Letter INSPECTION SUMMARY
06/27/2019 Letter INSPECTION SUMMARY
07/11/2019 Letter INSPECTION SUMMARY
09/16/2019 Letter INSPECTION SUMMARY
09/16/2019 Letter INSPECTION SUMMARY
10/24/2019 Letter INSPECTION SUMMARY
10/24/2019 Letter INSPECTION SUMMARY
10/24/2019 Letter INSPECTION SUMMARY
10/29/2019 Letter INSPECTION SUMMARY
11/01/2019 Letter INSPECTION SUMMARY
11/08/2019 Letter INSPECTION SUMMARY
11/08/2019 Letter INSPECTION SUMMARY
11/08/2019 Letter INSPECTION SUMMARY
04/20/2020 LOT 119 ASBUILT
04/21/2020 Letter INSPECTION SUMMARY
06/19/2020 Letter INSPECTION SUMMARY
06/23/2020 Letter INSPECTION SUMMARY
06/23/2020 Letter INSPECTION SUMMARY
06/24/2020 Letter Field Certificate of Occupancy
06/24/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home