Permit Application Status

PRRES20191007


In order to schedule inspections, you need to be signed in.

 / 

Note: You can collapse and expand individual sections by clicking the header of the section you wish to collapse/expand.

Summary
PRRES20191007
Building Permit - Residential
Certificate of Occupancy
KEVIN HIGDON CONSTRUCTION LLC
NEW SINGLE FAMILY
NEW HOUSE - UNFINISHED BASEMENT - NO DECK
04/22/2019
05/09/2019
07/07/2020
Locations
Contacts
KEVIN HIGDON CONSTRUCTION LLC, Address:PO BOX 847, Phone:(816) 524-9797  
KEVIN HIGDON CONSTRUCTION, LLC, Address:P O BOX 847, Phone:(816) 524-9797  
HENRY MILLER MECHANICAL LLC, Address:6609 ROYAL ST, SUITE 104, Phone:(816) 883-8818  
LUCAS ELECTRIC , Address:517 MARGARET LN, Phone:(816) 807-4432  
UNITED HEATING & COOLING, Address:301 DUCK RD, Phone:(816) 761-5262  
HIGGINBOTHAM.BRIAN@YAHOO.COM  
Reviews
Review Type Outcome Est. Completion Date Completed
Plot Plan Review Approved 04/24/2019 04/22/2019
Steve Conrick
Residential Plan Review Approved 04/24/2019 04/22/2019
Kim Brennan
Fees
Paid Fees Amount Paid Owing Date Paid
9110078-Valuation Fee New Single Family $1,246.68 $1,246.68 Paid 05/09/2019
9110073-Right of Way Permit Fee $80.00 $80.00 Paid 05/09/2019
8331504-EFHB Middle Big Creek, Full $535.68 $535.68 Paid 05/09/2019
8331507-Sewer Connection Fee $480.00 $480.00 Paid 05/09/2019
8331401-Water Tap Fee $3,409.00 $3,409.00 Paid 05/09/2019
8350015-Water Meter Fee $408.37 $408.37 Paid 05/09/2019
Outstanding Fees Amount Paid Owing Date Paid
No outstanding fees.


$0.00
Inspections
Inspection Outcome Requested Scheduled Date Inspected
Footing Inspection - Residential Passed 5/10/2019 (2:30) 5/10/2019 at 3:00 PM 05/10/2019
Underslab Plumbing Inspection - Residential Not Ready 6/5/2019 6/5/2019 at 3:20 PM 06/05/2019
Misc
Corrective Action Required
06/05/2019
NO ADDRESS POSTED NO EROSION CONTROL INSPECTION DENIED
Erosion Control Inspection Residential Failed 6/5/2019 06/05/2019
DCM1 ESC REQUIRED NO FURTHER INSP
Corrective Action Required
06/05/2019
EROSION CONTROL REQUIRED. NO FURTHER INSPECTIONS WILL BE PERFORMED UNTIL EROSION CONTROL IS INSTALLED AND IN COMPLIANCE.
Underslab Plumbing Inspection - Residential Failed 6/10/2019 6/10/2019 at 7:30 AM 06/10/2019
Misc
Resolved
06/10/2019
NO ADDRESS POSTED NO EROSION CONTROL INSPECTION DENIED
Misc
Corrective Action Required
06/10/2019
POST ADDRESS. FOUNDATION IS FULL OF WATER UNABLE TO INSPECT.
Underslab Plumbing Inspection - Residential Passed 6/12/2019 6/12/2019 06/12/2019
Misc
Resolved
06/12/2019
Sewer Service Inspection - R Passed 6/14/2019 (11:30) 6/14/2019 at 11:55 AM 06/14/2019
Water Service Inspection - R Passed 6/17/2019 6/17/2019 06/17/2019
Piers/Caissons Inspection - Residential Passed 7/24/2019 7/24/2019 07/24/2019
Gas Piping Inspection - Residential Failed 8/28/2019 8/28/2019 08/28/2019
Misc
Corrective Action Required
08/28/2019
House was locked ** Lock box code was not given**
Gas Piping Inspection - Residential Passed 8/29/2019 8/29/2019 08/29/2019
Misc
Resolved
08/29/2019
House was locked ** Lock box code was not given**
All Rough Inspection - Residential Failed 10/1/2019 10/01/2019
Misc
Corrective Action Required
10/01/2019
** Draft stop at fireplace ** Draft stop from garage to living area ** Main floor 1/2 bath - protect outlet in HVAC duct bay ** Main floor - Missing triple studs each side of stairs ** Bolt down columns in basement
Gas Service Inspection - Residential Passed 10/1/2019 10/1/2019 10/01/2019
Electrical Service Inspection Passed 10/1/2019 10/1/2019 10/01/2019
All Rough Inspection - Residential Passed 10/10/2019 10/10/2019 10/10/2019
Misc
Resolved
10/10/2019
** Draft stop at fireplace ** Draft stop from garage to living area ** Main floor 1/2 bath - protect outlet in HVAC duct bay ** Main floor - Missing triple studs each side of stairs ** Bolt down columns in basement
Driveway Inspection Partial 10/29/2019 10/29/2019 10/29/2019
Misc
Informational
10/29/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Driveway Inspection Passed 11/6/2019 11/22/2019
Misc
Informational
10/29/2019
PRE POUR INSPECTION The forms are set and there appears to be sufficient compacted aggregate.
Occupancy Inspection - Codes Residential Failed 3/27/2020 3/27/2020 03/27/2020
E3802.1 Bathroom receptacles
Corrective Action Required
03/27/2020
GFCI PROTECTION. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms shall have ground-fault circuit-interrupter protection for personnel. Master bathroom plugs at double sink area are not working correctly. GFCI not tripping.
Miscellaneous Correction
Corrective Action Required
03/27/2020
Check all items outside. The ground was wet and no sod was installed at time of inspection. TRACY DEISTER 03/27/2020 9:51 AM
Occupancy Inspection - Codes Residential Failed 5/27/2020 5/27/2020 05/27/2020
E3802.1 Bathroom receptacles
Corrective Action Required
03/27/2020
- GFCI Protection required at all exterior receptacles - All weather cover required at exterior receptacle W side - Place Sod - Deck currently being converted for stairs to grade, will need to inspect deck after all modifications are complete - Seal around all exterior light fixtures
Miscellaneous Correction
Resolved
05/27/2020
Check all items outside. The ground was wet and no sod was installed at time of inspection. TRACY DEISTER 03/27/2020 9:51 AM
Occupancy Inspection - Codes Residential Failed 5/28/2020 5/28/2020 05/28/2020
E3802.1 Bathroom receptacles
Resolved
05/28/2020
Misc
Corrective Action Required
05/28/2020
- Place Sod - Deck currently being converted for stairs to grade, will need to inspect deck after all modifications are complete, 5/28 - Contractor still working on deck conversion unable to inspect - Seal around all exterior light fixtures
Occupancy Inspection - Codes Residential Temporary C of O 05/28/2020
Misc
Corrective Action Required
05/28/2020
- Place Sod - Deck currently being converted for stairs to grade, will need to inspect deck after all modifications are complete, 5/28 - Contractor still working on deck conversion unable to inspect, exiting deck guardrail still in place - Seal around all exterior light fixtures OK for TCO
Plot Plan Inspection Passed 07/07/2020
Occupancy Inspection - Codes Residential Full C of O 7/7/2020 7/7/2020 07/07/2020
Misc
Resolved
07/07/2020
Documents & Images
Date Uploaded File Type Document Name
05/09/2019 Receipt Receipt for transaction: 2019-001861
05/09/2019 Letter Codes Building Permit
05/09/2019 Plot Plan DOC050919-05092019161744
05/10/2019 Letter INSPECTION SUMMARY
06/05/2019 Letter INSPECTION SUMMARY
06/05/2019 Letter INSPECTION SUMMARY
06/10/2019 Letter INSPECTION SUMMARY
06/12/2019 Letter INSPECTION SUMMARY
06/14/2019 Letter INSPECTION SUMMARY
06/17/2019 Letter INSPECTION SUMMARY
06/17/2019 Letter INSPECTION SUMMARY
07/24/2019 Letter INSPECTION SUMMARY
08/28/2019 Letter INSPECTION SUMMARY
08/29/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter INSPECTION SUMMARY
10/01/2019 Letter INSPECTION SUMMARY
10/10/2019 Letter INSPECTION SUMMARY
10/29/2019 Letter INSPECTION SUMMARY
11/22/2019 Letter INSPECTION SUMMARY
03/27/2020 Letter INSPECTION SUMMARY
05/27/2020 Letter INSPECTION SUMMARY
05/28/2020 Letter INSPECTION SUMMARY
05/28/2020 Letter Codes Temporary Certificate of Occupancy
07/07/2020 Letter INSPECTION SUMMARY
07/07/2020 Letter INSPECTION SUMMARY
07/07/2020 Letter Field Certificate of Occupancy
07/07/2020 Letter Codes Final Certificate of Occupancy
Upload Documents

Guidelines For Electronically Submitting Documents:

  • Submitted documents should be under 100MB in size.
  • Accepted file extensions:
    • pdf, jpg, xls, doc, xlsx, docx, dwg
  • All plans shall be to scale.
  • Recommended naming conventions:
    • Keep filename consistent.
    • Avoid the use of non-friendly filenames. (ex. k9dk38fj3.pdf)
    • Avoid inappropriate language in filenames.
  • Submitted documents will be stamped at the conclusion of the review.
    • The stamp will be placed in the upper right hand corner of the document. It is recommeded that this area, to the extent possible, be left blank so that no information is lost when the the stamp is applied.
Remember to click the Upload Document button. If you are applying for a New permit, make sure to click the "next step" button after you have completed the upload of documents

Select any documents you wish to provide:





Portal Home